Toshiba RAV-SM561BT-E, RAV-SM1400AT-E Error mode detected by remote controller or network adapter

Page 52

Error mode detected by remote controller or network adapter

: Flash, : Go on, : Go off

50

Wireless sensor

lamp display

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired remote

controller

Check code

No check code is displayed. (Remote controller does not operate.)

E01*2

E02

E09

L20

Central remote

controller

98

*3

Central remote

controller

99

*3

Central remote

controller

97

Central remote

controller

b7

 

Diagnostic function

 

 

 

 

Cause of operation

Status of air conditioner

Condition

 

Judgment and measures

 

 

 

 

 

 

 

No communication with master indoor unit

Stop

Remote controller power error, Defective indoor EEPROM

Remote controller cable is not correctly

 

 

1.

Check remote controller inter-unit cables.

 

connected.

 

 

2.

Check remote controller.

Power of indoor unit is not turned on.

 

 

3.

Check indoor power cables.

• Automatic address cannot be completed.

 

 

4.

Check indoor P.C. board.

 

 

 

 

5.

Check indoor EEPROM. (including socket insertion)

 

 

 

 

 

: Phenomenon of automatic address repetition occurred.

 

 

 

 

No communication with indoor master unit

Stop

Displayed when

Signal receiving of remote controller is defective.

Disconnection of inter-unit cable between

(Automatic restart)

error is detected

1.

Check remote controller inter-unit cables.

 

remote controller and master indoor unit

* When there is center, operation

 

2.

Check remote controller.

 

(Detected at remote controller side)

continues.

 

3.

Check indoor power cables.

 

 

 

 

4.

Check indoor P.C. board.

Signal sending error to indoor unit

Stop

Displayed when

Signal sending of remote controller is defective.

(Detected at remote controller side)

(Automatic restart)

error is detected

1.

Check sending circuit inside of remote controller.

 

 

* When there is center, operation

 

 

: Replace remote controller.

 

 

continues.

 

 

 

Multiple master remote controllers are recognized.

Stop

Displayed when

1.

Check there are multiple master units for 2 remote controllers

(Detected at remote controller side)

(Sub unit continues operation.)

error is detected

 

(including wireless).

 

 

 

 

 

: Master unit is one and others are sub units.

Duplicated indoor central addresses on

Stop

Displayed when

1.

Check address setup of central control system network.

communication of central control system (AI-NET)

(Automatic restart)

error is detected

 

(Network adapter SW01)

(Detected by central controller side)

 

 

2.

Check network adapter P.C. board.

 

 

 

 

 

Multiple network adapters on remote controller

Operation continues.

Displayed when

1.

Check multiple network adapters.

communication line

 

error is detected

2.

Check inter-unit cable/miscabling of remote controller.

(Detected by central controller side)

 

 

 

: Only one network adapter on remote controller communication line

 

 

 

 

 

Interruption of central control system (AI-NET)

Operation continues.

Displayed when

1.

Check communication line/miscabling. Check power of indoor unit.

communication circuit

(According to handy remote controller)

error is detected

2.

Check communication. (XY terminals)

(Detected by central controller side)

 

 

3.

Check network adapter P.C. board.

 

 

 

 

4.

Check central controller (such as central control remote controller, etc.).

 

 

 

 

Indoor Gr sub unit error

Continuation/stop

Displayed when

Check the check code of corresponding unit by handy remote controller.

(Detected by central controller side)

(Based on a case)

error is detected

 

 

 

 

 

 

 

 

*2 Check code is not displayed by wired remote controller. (Usual operation of air conditioner is disabled.)

For wireless type models, E01 is notified by the display lamp.

*3 These errors are related to communication of remote controllers (A, B) and central system (AI-NET, X, Y), and [E01], [E02], [E03], [E09], or [E18] is displayed or no check code is displayed on the remote controller according to the error contents.

Image 52
Contents Split Type Contents Indoor Unit SpecificationsConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E Outdoor Unit RAV-SM560AT-E RAV-SM800AT-ERAV-SM1100AT-E RAV-SM1400AT-E Operation Characteristic Curve Cooling HeatingCooling Capacity Variation Ratio According to TemperatureHeating Static Pressure Characteristics of Each Model AIR Ducting WorkRAV-SM1101BT-E Round duct Dimension Construction Views External ViewsIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Systematic Refrigerating Cycle Diagram Indoor Unit/Outdoor UnitIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Strainer Second rps Fan Indoor OutdoorColor Wiring DiagramIdentification Color Identification MCC-813MCC-1359 For P.C. BoardMCC-1438 MCC-1398Specifications of Electrical Parts Parts name Type SpecificationsRAV-SM1100AT-E Safety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping Materials and Joints UsedProcessing of Piping Materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Nominal diameterFlare tool for Conventional flare tool R410A clutch type Clutch type Wing nut typeR22 clutch type Clutch type Wing nut type DiameterNm kgfcm Wrenches available on the marketRequired Tools ToolsGeneral tools Conventional tools can be used 1 Configuration of refrigerant charging Recharging of RefrigerantMaterials for Brazing Brazing of PipesFlux Brazing Never use gas other than Nitrogen gasIndoor Unit Control Main Sub master remote controller Weekly timerIndoor Control Circuit Outline of specifications Remarks Control SpecificationsRemote controller Outline of control Command Heating Auto OperationHeat Control temp C Case of wired remote controller Last push priorityCenter Operation ProhibitedTa˚C Normal control Indoor Print Circuit Board MCC-1402SM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTIndoor P.C. Board Optional Connector Specifications Function Connector Pin Specifications RemarksDischarge temperature release control Outdoor ControlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Outdoor fan control Object SM560 Allocations of fan tap revolutionsCooling operation Heating operationShort intermittent operation preventive control High-pressure suppression TE control For SM800Over-current preventive control Current release value shift controlDefrost control Start of heating operationPrint Circuit Board Outdoor ControlsMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Troubleshooting Summary of TroubleshootingWired remote controller type Before troubleshootingCheck Code List Error mode detected by indoor unitError mode detected by outdoor unit Diagnostic function Cause of operationError mode detected by remote controller or network adapter Timer Ready Wired remote Controller Check codeError Mode Detected by LED on Outdoor P.C. Board SW800 LED display in bit 1, bit 2, bit 3, bit 4 OFFCDB side Ipdu sideCheck code SW800 LED display in bit 1, bit 2, bit 3 OFFType a Troubleshooting Procedure for Each Check Code E01 error/*99 errorE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E10 error/CF error E18 error/97 error *99 errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorL30 error/B6 error L20 error/98 errorB7 error Central controller P10 error/Ob error F10 error 0C errorP12 error/11 error Single phase P22 error/1A errorRAV-SM1100AT-E, SM1400AT-E P19 error/08 error F02 error/0d errorF01 error/0F error P26 error/14 errorP29 error/16 error H03 error/17 errorF04 error/19 error F06 error/18 errorF08 error/1b error L29 error/1C error H02 error/1d errorP03 error/1E error H01 error/1F errorP04 error/21 error Error Central controller F29 error / 12 error E03 error Master indoor unitP31 error Sub indoor unit TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1 Caracteristics-320 TE, TO, TS sensor TD sensor Caracteristics-4Replacement of Service Indoor P.C. Board CaseR1 Readout of the setup data from Eeprom R2 Replacement of service P.C. boardContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Type Item code Memorandum for setup contents Item code table ExampleIndoor unit capacity Item code Setup AT Local Site and Others Test Run Setup on Remote ControllerSetup to Select Function Wired remote controllerItem No. DN table Selection of function Description At shipmentSetup method Cabling and Setting of Remote Controller ControlOperation Contents Monitor Function of Remote Controller SwitchProcedure Calling of error history Group control operationRequirement System exampleMicrocomputer Block Diagram Network Address Setup Switch SW01LED Display Specification Network AdapterCommunication Cable Specifications Communication circuit Communication cable specificationsCable Connection Network cable connectionHow to Set an Address Number How to set from the remote controller at indoor unit sideHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsNetwork address No. setup table SW01 Requirement in ServiceAddress No Contents Remarks Address Setup Address SetupAddress setup procedure Address Setup & Group Control System configurationOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingManual setting from remote controller Setup completes Status returns to the usual stop statusTo know the position of indoor unit body by address Push button if the unit stopsPush and buttons simultaneously for 4 seconds or more Part name Procedure Remarks DetachmentsNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Detachment AttachmentProcedure Remarks Part namePart name Procedure RequirementConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex 100 Requirement101 102 103 104 105 Product106 107 108 109 110 111 Case of RAV-SM1100AT-EBe sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 Exploded Views and Parts List 114Part Description Location904 901, 902, 903 35, 36, 37 115116 RAV-SM1001BT-E / SM1401BT-E117 RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-EInverter 118702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 11921,22 16,17 120706 121Inverter 26,27 23,24 28,29 122TH Sensor 123