Toshiba RAV-SM801BT-E Item No. DN table Selection of function, Description At shipment

Page 77

Item No. (DN) table (Selection of function)

DN

01

02

03

06

0F

10

11

12

13

14

19

1E

28

2A

2b

2E

30

31

32

40

5d

60

8b

Item

 

 

 

Description

 

At shipment

 

 

 

 

 

 

 

Filter sign lighting

0000

: None

 

0001

: 150H

According to type

time

0002

: 2500H

 

0003

: 5000H

 

 

 

0004

: 10000H

 

0005

: Clogged sensor used

 

 

 

 

 

 

 

 

 

 

Dirty state of filter

0000

: Standard

 

0001

: High degree of dirt

0000

: Standard

 

 

 

 

 

(Half of standard time)

 

 

 

 

 

 

 

 

 

 

Central control

0001

: No.1 unit

to

0064

: No.64 unit

0099

: Unfixed

address

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating suction temp

0000

: No shift

 

0001

: +1°C

0002

: +2°C

shift

0002

: +2°C

to

0010

: -10°C

(Floor type 0000: 0°C)

 

 

 

 

 

(Up to recommendation + 6)

 

 

 

 

 

 

 

 

 

 

Cooling only

0000

: Heat pump

 

0001

: Cooling only

0000

: Shared for cooling/

 

 

 

 

 

(No display of [AUTO] [HEAT])

 

heating

 

 

 

 

Type

0000

: (Air discharge cassette 1) 0001 : (Air discharge cassette 4) to 0037

According to model type

 

 

 

 

 

 

Indoor unit capacity

0000

: Unfixed

 

0001 to 0034

According to capacity type

 

 

 

 

 

 

 

 

Line address

0001

: No.1 unit

to

0030

: No.30 unit

0099

: Unfixed

 

 

 

 

 

 

 

 

Indoor unit address

0001

: No.1 unit

to

0064

: No.64 unit

0099

: Unfixed

 

 

 

 

 

 

 

 

Group address

0000

: Individual

 

0001

: Master of group

0099

: Unfixed

 

0002

: Sub of group

 

 

 

 

 

 

 

 

 

 

 

 

Flap type

0000

: No flap

 

0001

: Swing only

According to type

(Adjustment of air

0004

: 4-way

 

 

 

 

 

direction)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp difference of

0000

: 0 deg

to

0010

: 10 deg

0003

: 3 deg

automatic cooling/

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

 

(Ts±1.5)

heating mode

 

 

 

 

 

 

 

selection COOL

 

 

 

 

 

 

 

HEAT, HEAT COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic reset of

0000

: None

 

0001

: Reset

0000

: None

power failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0002

: Default

 

 

 

 

 

 

Thermo output

0000

: Indoor thermo ON

0001

: Output of outdoor comp-ON

0000: Thermo. ON

selection (T10 ƒ)

 

 

 

 

receiving

 

 

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

Sensor selection

0000

: Body TA sensor

 

0001

: Remote controller sensor

0000

: Body sensor

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

0003

: Default

 

 

 

 

 

 

 

 

High ceiling selection

0000

: Standard filter

 

 

 

0000

: Standard

(Air volume selection)

0001

: Oil guard, Super-long life, Optical regenerative deodorization

 

 

 

0003

: High performance (65%), High performance (90%),

 

 

 

 

High antibacterial performance (65%)

 

 

 

 

 

 

 

 

 

Timer set

0000

: Available (Operable)

0001

: Unavailable (Operation prohibited)

0000

: Available

(Wired remote

 

 

 

 

 

 

 

controller)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correction of high

0000

: None

 

0001

: Correction

0000

: None

heat feeling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

Image 77
Contents Split Type Contents Concealed Duct Type SpecificationsIndoor Unit RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveHeating Capacity Variation Ratio According to TemperatureCooling AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct Construction Views External Views DimensionIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Indoor Unit/Outdoor Unit Systematic Refrigerating Cycle DiagramIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerIdentification Wiring DiagramColor MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Refrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping Materials and Joints Used1 Thicknesses of annealed copper pipes Thickness mm Processing of Piping MaterialsOuter diameter mm R410A R22 Nominal diameterR410A clutch type Clutch type Wing nut type Flare tool for Conventional flare toolR22 clutch type Clutch type Wing nut type DiameterWrenches available on the market Nm kgfcmGeneral tools Conventional tools can be used ToolsRequired Tools Recharging of Refrigerant 1 Configuration of refrigerant chargingFlux Brazing of PipesMaterials for Brazing Never use gas other than Nitrogen gas BrazingIndoor Control Circuit Main Sub master remote controller Weekly timerIndoor Unit Control Remote controller Outline of control Command Control SpecificationsOutline of specifications Remarks Operation Heating AutoHeat Control temp C Last push priority Case of wired remote controllerCenter Operation ProhibitedTa˚C Normal control MCC-1402 Indoor Print Circuit BoardSM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsOutdoor Control Discharge temperature release controlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Allocations of fan tap revolutions Outdoor fan control Object SM560Cooling operation Heating operationHigh-pressure suppression TE control For SM800 Short intermittent operation preventive controlOver-current preventive control Current release value shift controlStart of heating operation Defrost controlMCC-813 RAV-SM560AT-E Viewed from parts of P.C board Outdoor ControlsPrint Circuit Board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Summary of Troubleshooting TroubleshootingWired remote controller type Before troubleshootingError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF Error Mode Detected by LED on Outdoor P.C. BoardCDB side Ipdu sideType a SW800 LED display in bit 1, bit 2, bit 3 OFFCheck code E01 error/*99 error Troubleshooting Procedure for Each Check CodeE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E18 error/97 error *99 error E10 error/CF errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorB7 error Central controller L20 error/98 errorL30 error/B6 error F10 error 0C error P10 error/Ob errorP12 error/11 error RAV-SM1100AT-E, SM1400AT-E P22 error/1A errorSingle phase F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF08 error/1b error F06 error/18 errorF04 error/19 error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller P31 error Sub indoor unit E03 error Master indoor unitF29 error / 12 error Caracteristics-3 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-120 TE, TO, TS sensor TD sensor Caracteristics-4Case Replacement of Service Indoor P.C. BoardR2 Replacement of service P.C. board R1 Readout of the setup data from EepromContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Indoor unit capacity Item code Memorandum for setup contents Item code table ExampleType Item code Test Run Setup on Remote Controller Setup AT Local Site and OthersSetup to Select Function Wired remote controllerDescription At shipment Item No. DN table Selection of functionOperation Cabling and Setting of Remote Controller ControlSetup method Procedure Monitor Function of Remote Controller SwitchContents Group control operation Calling of error historyRequirement System exampleNetwork Address Setup Switch SW01 Microcomputer Block DiagramLED Display Specification Network AdapterCommunication circuit Communication cable specifications Communication Cable SpecificationsCable Connection Network cable connectionHow to set from the remote controller at indoor unit side How to Set an Address NumberHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsAddress No Requirement in ServiceNetwork address No. setup table SW01 Contents Remarks Address setup procedure Address SetupAddress Setup System configuration Address Setup & Group ControlOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingSetup completes Status returns to the usual stop status Manual setting from remote controllerPush and buttons simultaneously for 4 seconds or more Push button if the unit stopsTo know the position of indoor unit body by address Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1100AT-E 111Be sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 114 Exploded Views and Parts ListPart Description Location115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor