Toshiba RAV-SM1401BT-E Short intermittent operation preventive control, Corrected value

Page 45

NOTIFICATION

It is not an abnormal phenomenon that electro-noise may be heard while heating the coil.

7. Short intermittent operation preventive control

The compressor may not stop for preventing the compressor for 3 to 10 minutes after start of the operation even if Thermo-OFF signal has been received from the indoor. This phenomenon is not abnormal. (Continuous operation time of the compressor differs according to the operating status.)

If the equipment is stopped from the remote controller, the operation does not continue.

8.High-pressure suppression TE control (For SM800)

This control suppresses that pressure becomes abnormally higher during cooling operation.

Stop the compressor under condition of TE 67°C, and count 1 on the error count.

ƒAfter 2 minutes 30 seconds passed, if TE < 67°C, the compressor restarts and the error count is cleared when the operation continues for 10 minutes.

When TE 67°C is detected again within 10 minutes, 1 is added to the error count and restart is repeated.

If the error counts 10 are recognized, it is determined as an error and restart is not performed. Error code ‘P04’ is displayed.

After restarting the compressor, continue controlling by using 70% to 90% of the control value of the current release control for minimum 30 minutes.

9.Over-current preventive control

This control function stops the compressor when over-current preventive circuit has detected an abnormal current.

The compressor restarts with error count 1 after 2 minutes 30 seconds.

ƒIf the error counts 4 are recognized, it is determined as an error and restart is not performed. Error code ‘H01’, ‘H02’ or ‘P26’ is displayed.

10.Current release value shift control

1)For SM800, SM1100, SM1400

This control function prevents troubles of the electron parts such as G-Tr of inverter of compressor drive system and troubles of the compressor during cooling operation.

This control function corrects the current release control value (1) in item 3 of 9-1. by Current release control.

ƒThe value to be corrected is based upon the following control diagram and correction value table.

TO [˚C]

T+8

T+7

T+5

T+4

T+2

T+1

T

T-1

Corrected value

I1 x a%

 

T

a

b

c

d

 

 

 

 

 

 

SM800

39°C

40%

60%

80%

85%

 

 

 

 

 

 

 

 

I1 x b%

SM1100

39°C

50%

70%

80%

90%

I1 x c%

SM1400

39°C

70%

80%

90%

95%

 

 

 

 

 

 

 

 

 

 

 

 

I1 x d%

 

 

 

 

 

 

As I1

 

 

 

 

 

 

2)For SM560

The current release value of a single-phase model is se- lected from the right table according to TO sensor value.

Current release value shift control

 

TO

SM560

 

 

 

45

TO

5.92

 

 

 

40

TO < 45

6.75

 

 

 

 

TO < 40

9.00

 

 

 

43

Image 45
Contents Split Type Contents Specifications Indoor UnitConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveCapacity Variation Ratio According to Temperature CoolingHeating AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct Construction Views External Views DimensionIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Indoor Unit/Outdoor Unit Systematic Refrigerating Cycle DiagramIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerWiring Diagram ColorIdentification MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Refrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping Materials and Joints Used1 Thicknesses of annealed copper pipes Thickness mm Processing of Piping MaterialsOuter diameter mm R410A R22 Nominal diameterR410A clutch type Clutch type Wing nut type Flare tool for Conventional flare toolR22 clutch type Clutch type Wing nut type DiameterWrenches available on the market Nm kgfcmTools Required ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingBrazing of Pipes Materials for BrazingFlux Never use gas other than Nitrogen gas BrazingMain Sub master remote controller Weekly timer Indoor Unit ControlIndoor Control Circuit Control Specifications Outline of specifications RemarksRemote controller Outline of control Command Operation Heating AutoHeat Control temp C Last push priority Case of wired remote controllerCenter Operation ProhibitedTa˚C Normal control MCC-1402 Indoor Print Circuit BoardSM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsOutdoor Control Discharge temperature release controlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Allocations of fan tap revolutions Outdoor fan control Object SM560Cooling operation Heating operationHigh-pressure suppression TE control For SM800 Short intermittent operation preventive controlOver-current preventive control Current release value shift controlStart of heating operation Defrost controlOutdoor Controls Print Circuit BoardMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Summary of Troubleshooting TroubleshootingWired remote controller type Before troubleshootingError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF Error Mode Detected by LED on Outdoor P.C. BoardCDB side Ipdu sideSW800 LED display in bit 1, bit 2, bit 3 OFF Check codeType a E01 error/*99 error Troubleshooting Procedure for Each Check CodeE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E18 error/97 error *99 error E10 error/CF errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorL20 error/98 error L30 error/B6 errorB7 error Central controller F10 error 0C error P10 error/Ob errorP12 error/11 error P22 error/1A error Single phaseRAV-SM1100AT-E, SM1400AT-E F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF06 error/18 error F04 error/19 errorF08 error/1b error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller E03 error Master indoor unit F29 error / 12 errorP31 error Sub indoor unit Caracteristics-3 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-120 TE, TO, TS sensor TD sensor Caracteristics-4Case Replacement of Service Indoor P.C. BoardR2 Replacement of service P.C. board R1 Readout of the setup data from EepromContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Memorandum for setup contents Item code table Example Type Item codeIndoor unit capacity Item code Test Run Setup on Remote Controller Setup AT Local Site and OthersSetup to Select Function Wired remote controllerDescription At shipment Item No. DN table Selection of functionCabling and Setting of Remote Controller Control Setup methodOperation Monitor Function of Remote Controller Switch ContentsProcedure Group control operation Calling of error historyRequirement System exampleNetwork Address Setup Switch SW01 Microcomputer Block DiagramLED Display Specification Network AdapterCommunication circuit Communication cable specifications Communication Cable SpecificationsCable Connection Network cable connectionHow to set from the remote controller at indoor unit side How to Set an Address NumberHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsRequirement in Service Network address No. setup table SW01Address No Contents Remarks Address Setup Address SetupAddress setup procedure System configuration Address Setup & Group ControlOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingSetup completes Status returns to the usual stop status Manual setting from remote controllerPush button if the unit stops To know the position of indoor unit body by addressPush and buttons simultaneously for 4 seconds or more Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1100AT-E 111Be sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 114 Exploded Views and Parts ListPart Description Location115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor