Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E R1 Readout of the setup data from Eeprom, Contents

Page 73

r1 Readout of the setup data from EEPROM

(Data in EEPROM contents, which have been changed at the local site, are read out together with data in EEPROM set at shipment from the factory.)

1.Push SET , , and buttons of the remote controller at the same time for 4 seconds or more. 1 (Corresponded with No. in Remote controller)

When group operation, the master indoor unit address is displayed at the first time. In this time, the item code (DN) 10 is displayed. The fan of the selected indoor unit operates and the flap starts swinging if any.

2.Every pushing button, the indoor unit address in the group are displayed successively. 2 Specify the indoor unit No. to be replaced.

3.Using the set temperature / buttons, the item code (DN) can be moved up and down one by one.3

4.First change the item code (DN) from 10 to 01. (Setting of filter sign lighting time) Make a note of the set data displayed in this time.

5.Next change the item code (DN) using the set temperature / buttons. Also make a note of the set data.

6.Repeat item 5. and make a note of the important set data as shown in the later table (Ex.).

01 to 9F are provided in the item code (DN). On the way of operation, DN No. may come out.

7.After finishing making a note, push button to return the status to usual stop status. 6 (Approx. 1 minute is required to start handling of the remote controller.)

Minimum requirements for item code

DN

Contents

 

 

10

Type

 

 

11

Indoor unit capacity

 

 

12

Line address

 

 

13

Indoor address

 

 

14

Group address

 

 

(1)Type and capacity of the indoor unit is necessary to set the revolutions frequency of the fan.

(2)If Line/Indoor/Group addresses differ from those before replacement, the mode enters in automatic address setup mode and a manual resetting may be required.

r2 Replacement of service P.C. board

1.Replace the P.C. board with a service P.C. board.

In this time, setting of jumper line (cut) or setting of (short-circuit) connecting connectors on the former P.C. board should be reflected on the service P.C. board.

2.According to the system configuration, turn on power of the indoor unit with any method in the following items.

a)In case of single (individual) operation Turn on the power supply.

1)Wait for completion of automatic address setup mode (Required time: Approx. 5 minutes) and then proceed to r3.

(Line address = 1, Indoor address = 1, Group address = 0 (Individual) are automatically set.)

2)Push SET , , and buttons of the remote controller at the same time for 4 seconds or more (1 operation), interrupt the automatic address setup mode, and then proceed to r3.

(Unit No. ALL is displayed.)

b)In case of group operation

Turn on power of the indoor unit of which P.C. board has been replaced with the service P.C. board with any method in the following items.

1)Turn on power of the replaced indoor unit only.

(However, the remote controller is also connected. Otherwise r3 operation cannot be performed.) Same as 1) and 2) in item a).

2)Turn on power of the multiple indoor units including replaced indoor unit.

Only 1 system for twin, triple, double twin

For all units in the group

Wait for completion of automatic address setup mode (Required time: Approx. 5 minutes) and then proceed to r3.

*The master unit of a group may change by setup of automatic address. The line address/indoor address of the replaced indoor unit are automatically set to the vacant addresses except addresses belonging to other indoor units which have not been replaced. It is recommended to make a note that the refrigerant line which includes the corresponding indoor unit and that the corresponding indoor unit is master or sub in the group control.

71

Image 73
Contents Split Type Contents Indoor Unit SpecificationsConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveCooling Capacity Variation Ratio According to TemperatureHeating AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct Construction Views External Views DimensionIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Indoor Unit/Outdoor Unit Systematic Refrigerating Cycle DiagramIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerColor Wiring DiagramIdentification MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Refrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping Materials and Joints Used1 Thicknesses of annealed copper pipes Thickness mm Processing of Piping MaterialsOuter diameter mm R410A R22 Nominal diameterR410A clutch type Clutch type Wing nut type Flare tool for Conventional flare toolR22 clutch type Clutch type Wing nut type DiameterWrenches available on the market Nm kgfcmRequired Tools ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingMaterials for Brazing Brazing of PipesFlux Never use gas other than Nitrogen gas BrazingIndoor Unit Control Main Sub master remote controller Weekly timerIndoor Control Circuit Outline of specifications Remarks Control SpecificationsRemote controller Outline of control Command Operation Heating AutoHeat Control temp C Last push priority Case of wired remote controllerCenter Operation ProhibitedTa˚C Normal control MCC-1402 Indoor Print Circuit BoardSM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsOutdoor Control Discharge temperature release controlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Allocations of fan tap revolutions Outdoor fan control Object SM560Cooling operation Heating operationHigh-pressure suppression TE control For SM800 Short intermittent operation preventive controlOver-current preventive control Current release value shift controlStart of heating operation Defrost controlPrint Circuit Board Outdoor ControlsMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Summary of Troubleshooting TroubleshootingWired remote controller type Before troubleshootingError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF Error Mode Detected by LED on Outdoor P.C. BoardCDB side Ipdu sideCheck code SW800 LED display in bit 1, bit 2, bit 3 OFFType a E01 error/*99 error Troubleshooting Procedure for Each Check CodeE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E18 error/97 error *99 error E10 error/CF errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorL30 error/B6 error L20 error/98 errorB7 error Central controller F10 error 0C error P10 error/Ob errorP12 error/11 error Single phase P22 error/1A errorRAV-SM1100AT-E, SM1400AT-E F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF04 error/19 error F06 error/18 errorF08 error/1b error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller F29 error / 12 error E03 error Master indoor unitP31 error Sub indoor unit Caracteristics-3 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-120 TE, TO, TS sensor TD sensor Caracteristics-4Case Replacement of Service Indoor P.C. BoardR2 Replacement of service P.C. board R1 Readout of the setup data from EepromContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Type Item code Memorandum for setup contents Item code table ExampleIndoor unit capacity Item code Test Run Setup on Remote Controller Setup AT Local Site and OthersSetup to Select Function Wired remote controllerDescription At shipment Item No. DN table Selection of functionSetup method Cabling and Setting of Remote Controller ControlOperation Contents Monitor Function of Remote Controller SwitchProcedure Group control operation Calling of error historyRequirement System exampleNetwork Address Setup Switch SW01 Microcomputer Block DiagramLED Display Specification Network AdapterCommunication circuit Communication cable specifications Communication Cable SpecificationsCable Connection Network cable connectionHow to set from the remote controller at indoor unit side How to Set an Address NumberHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsNetwork address No. setup table SW01 Requirement in ServiceAddress No Contents Remarks Address Setup Address SetupAddress setup procedure System configuration Address Setup & Group ControlOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingSetup completes Status returns to the usual stop status Manual setting from remote controllerTo know the position of indoor unit body by address Push button if the unit stopsPush and buttons simultaneously for 4 seconds or more Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1100AT-E 111Be sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 114 Exploded Views and Parts ListPart Description Location115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor