12-4. Display and Operation of Main Remote Controller and Central Control Remote Controller

1.Turn on all the power supplies of the air conditioner, and then turn on power of the central control remote controller (Line 16 RBC-SXC1P, Line 64 TCB-SC641). If both power supplies are simultaneously turned on or if they are turned on reversely, the check code [97] may be temporarily displayed on the central remote controller. When settings of connecting cables and central control address are correct, the connected air conditioner is displayed on the central control remote controller.

2.As shown in the following table, there is difference of LCD between main remote controller (RBC-AMT21) and the central control remote controller and also there are restriction and others of operation.

 

Item

 

Contents

 

Cautions

 

 

 

 

 

 

Main remote controller

Central control remote controller

 

 

 

 

 

 

 

 

 

 

1

Air volume selection

[SPEED]

[AUTO]

[VOL]

[AUTO]

Display of air speed selection differs.

 

 

 

[HH]

 

[H]

 

 

 

 

[H]

 

[M]

 

 

 

 

[L]

 

[L]

 

 

 

 

 

 

 

 

 

 

[SPEED]

 

[VOL]

 

In duct type

 

 

 

[HH]

 

[FIX]

Air speed becomes [H] and [FIX].

 

 

 

 

 

 

 

2

Air speed selection

[SPEED]

 

[VOL]

[AUTO]

When handling main remote controller, [AUTO] is

 

in FAN mode

 

[HH]

 

[H]

not displayed. If [AUTO] is selected at center side,

 

 

 

[H]

 

[M]

[AUTO] is displayed on the main remote controller.

 

 

 

[L]

 

[L]

In this time, the air speed becomes [HH].

 

 

 

 

 

 

 

3

Air speed selection

[SPEED]

[AUTO]

[VOL]

[AUTO]

On the central remote controller, only [AUTO] is

 

in DRY mode

 

[HH]

 

 

displayed. The display on the main remote

 

 

 

[H]

 

 

controller changes to [AUTO] by changing the

 

 

 

[L]

 

 

setup temperature/louver, and the air speed is

 

 

 

 

 

 

automatically selected.

 

 

 

 

 

 

4

Air direction

[SWING] and air

[LOUVER]

 

On the central remote controller, only [LOUVER] is

 

adjustment

direction adjustment

 

 

displayed. It is displayed while flap is swinging,

 

 

 

 

 

 

and the setup operation of [LOUVER] becomes

 

 

 

 

 

 

selection of swing ON/OFF.

 

 

 

 

 

 

To set up the air direction, use the main remote

 

 

 

 

 

 

controller.

 

 

 

 

 

 

 

(No display)

Manual operation for

In a model type without air direction adjustment

 

 

 

 

[LOUVER]

 

 

 

 

 

 

 

5

Check button

Test run (4 seconds)

Check code display and

The function of long-pushing operation for the

 

 

 

 

check reset (3 seconds)

check button differs. If the check reset operation

 

 

 

 

 

 

on the central remote controller is performed

 

 

 

 

 

 

during operation of air conditioner, the operation

 

 

 

 

 

 

stops once, and then the operation restarts. (Error

 

 

 

 

 

 

of air conditioner is cleared.)

 

 

 

 

 

6

Check code

3-digits display

2-digits display (alphabet

Display of check code differs.

 

 

(alphabet + 2-digits

or numeral)

Ex. : Float switch operation

 

 

numeral)

 

 

 

Main side: [P10]

 

 

 

 

 

 

Center side: [0b]

 

 

 

 

 

 

 

3.When using the remote controller together with the former one (RBC-AM1, AT1), the display on the main remote controller differs if [Last-push priority/Center/Operation Prohibited] is selected from the central control remote controller.

 

 

Contents

 

 

Item

 

 

 

 

Remarks

 

New remote controller

Former remote controller

 

 

 

 

 

(RBC-AMT21)

(RBC-AM1, AT1)

 

 

 

 

 

 

 

 

1

Last-push priority

(No display)

(No display)

All the settings and ON/OFF operations are

 

 

 

 

 

 

available.

 

 

 

 

 

 

 

2

Center

[CENTER] goes on

[CENTER] goes on

The setup contents on the central control remote

 

 

 

 

 

 

controller are fixed, and only ON/OFF operation

 

 

 

 

 

 

and timer setup operation are available on the

 

 

 

 

 

 

main remote controller.

 

 

 

 

 

 

 

3

Operation prohib-

 

 

[CENTER] flashes

The setup contents on the central control remote

 

ited

 

 

 

 

controller are fixed, and the air conditioner stops.

 

 

 

 

 

 

Operation from the main remote controller is

 

 

 

 

 

 

unavailable.

 

 

 

 

 

 

 

83

Image 85
Contents Split Type Contents Indoor Unit SpecificationsConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveCooling Capacity Variation Ratio According to TemperatureHeating AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct Construction Views External Views DimensionIndoor Unit Concealed Duct Type RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-ERAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Indoor Unit/Outdoor Unit Systematic Refrigerating Cycle DiagramIndoor unit Outdoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerColor Wiring DiagramIdentification MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Refrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping Materials and Joints Used1 Thicknesses of annealed copper pipes Thickness mm Processing of Piping MaterialsOuter diameter mm R410A R22 Nominal diameterR410A clutch type Clutch type Wing nut type Flare tool for Conventional flare toolR22 clutch type Clutch type Wing nut type DiameterWrenches available on the market Nm kgfcmRequired Tools ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingMaterials for Brazing Brazing of PipesFlux Never use gas other than Nitrogen gas BrazingIndoor Unit Control Main Sub master remote controller Weekly timerIndoor Control Circuit Outline of specifications Remarks Control SpecificationsRemote controller Outline of control Command Operation Heating AutoHeat Control temp C Last push priority Case of wired remote controllerCenter Operation ProhibitedTa˚C Normal control MCC-1402 Indoor Print Circuit BoardSM1401BT-E RAV-SM561BT-E / SM801BT-E / SM1101BTFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsOutdoor Control Discharge temperature release controlOutline of Main Controls Pulse Modulating Valve PMV controlMAX Allocations of fan tap revolutions Outdoor fan control Object SM560Cooling operation Heating operationHigh-pressure suppression TE control For SM800 Short intermittent operation preventive controlOver-current preventive control Current release value shift controlStart of heating operation Defrost controlPrint Circuit Board Outdoor ControlsMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Summary of Troubleshooting TroubleshootingWired remote controller type Before troubleshootingError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF Error Mode Detected by LED on Outdoor P.C. BoardCDB side Ipdu sideCheck code SW800 LED display in bit 1, bit 2, bit 3 OFFType a E01 error/*99 error Troubleshooting Procedure for Each Check CodeE09 error/*99 error New Check Code/Present Check Code Central Control SideE04 error/04 error E18 error/97 error *99 error E10 error/CF errorE08, L03, L07, L08 error/ *96 error 99 error L09 error/46 errorL30 error/B6 error L20 error/98 errorB7 error Central controller F10 error 0C error P10 error/Ob errorP12 error/11 error Single phase P22 error/1A errorRAV-SM1100AT-E, SM1400AT-E F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF04 error/19 error F06 error/18 errorF08 error/1b error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller F29 error / 12 error E03 error Master indoor unitP31 error Sub indoor unit Caracteristics-3 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-120 TE, TO, TS sensor TD sensor Caracteristics-4Case Replacement of Service Indoor P.C. BoardR2 Replacement of service P.C. board R1 Readout of the setup data from EepromContents Minimum requirements for item codeR3 Writing of the setup contents to Eeprom Type Item code Memorandum for setup contents Item code table ExampleIndoor unit capacity Item code Test Run Setup on Remote Controller Setup AT Local Site and OthersSetup to Select Function Wired remote controllerDescription At shipment Item No. DN table Selection of functionSetup method Cabling and Setting of Remote Controller ControlOperation Contents Monitor Function of Remote Controller SwitchProcedure Group control operation Calling of error historyRequirement System exampleNetwork Address Setup Switch SW01 Microcomputer Block DiagramLED Display Specification Network AdapterCommunication circuit Communication cable specifications Communication Cable SpecificationsCable Connection Network cable connectionHow to set from the remote controller at indoor unit side How to Set an Address NumberHow to set by the switch on the network adapter P.C. board Procedure Set the network address while the unit stopsNetwork address No. setup table SW01 Requirement in ServiceAddress No Contents Remarks Address Setup Address SetupAddress setup procedure System configuration Address Setup & Group ControlOnly turning on source power supply Automatic completion Automatic address example from unset address No miscablingSetup completes Status returns to the usual stop status Manual setting from remote controllerTo know the position of indoor unit body by address Push button if the unit stopsPush and buttons simultaneously for 4 seconds or more Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1100AT-E 111Be sure to mount the propeller fan Case of RAV-SM1400AT-E112 113 114 Exploded Views and Parts ListPart Description Location115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor