Toshiba RAV-SM1101BT-E, RAV-SM1400AT-E, RAV-SM1100AT-E P03 error/1E error, H01 error/1F error

Page 67

[P03 error]/[1E error]

Is protective control such as

NO

Are connections of

NO

 

 

discharge temprelease control normal?

 

cable/connector normal?

 

 

YES

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Is charged refrigerant amount normal?

 

YES

 

 

 

YES

Is not abnormal overload?

 

 

 

NO

 

 

 

 

 

NO

Are characteristics of

 

TD sensor resistance value normal?

 

Correct the cabling and connection of connector.

Check parts. Defect Replace

Check and correct the charged refrigerant amount.

Improve and delete the cause

Replace TD sensor.

YES

* Refer to Characteristics-4.

Check CDB.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

[H01 error]/[1F error]

Is power voltage normal?

YES

Is not abnormal overload?

NO

Is the circuit detected by current sensor normal?

YES

NO

YES

NO

Improve power line.

Improve and delete the cause.

Check and correct circuit cables.

Check IPDU.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

65

Image 67
Contents Split Type Contents Indoor Unit SpecificationsConcealed Duct Type RAV-SM1101BT-E RAV-SM1401BT-E RAV-SM560AT-E RAV-SM800AT-E Outdoor UnitRAV-SM1100AT-E RAV-SM1400AT-E Cooling Heating Operation Characteristic CurveCooling Capacity Variation Ratio According to TemperatureHeating AIR Ducting Work Static Pressure Characteristics of Each ModelRAV-SM1101BT-E Round duct RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-E DimensionConstruction Views External Views Indoor Unit Concealed Duct TypeRAV-SM560AT-E RAV-SM800AT-E RAV-SM1100AT-E / SM1400AT-E Outdoor unit Systematic Refrigerating Cycle DiagramIndoor Unit/Outdoor Unit Indoor unitRAV-SM801BT-E RAV-SM1001BT-E Second rps Fan Indoor Outdoor StrainerColor Wiring DiagramIdentification MCC-813 Color IdentificationFor P.C. Board MCC-1359MCC-1398 MCC-1438Parts name Type Specifications Specifications of Electrical PartsRAV-SM1100AT-E Piping Materials and Joints Used Safety During Installation/ServicingRefrigerant Piping Installation Refrigerant R410ANominal diameter Processing of Piping Materials1 Thicknesses of annealed copper pipes Thickness mm Outer diameter mm R410A R22Diameter Flare tool for Conventional flare toolR410A clutch type Clutch type Wing nut type R22 clutch type Clutch type Wing nut typeWrenches available on the market Nm kgfcmRequired Tools ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingMaterials for Brazing Brazing of PipesFlux Never use gas other than Nitrogen gas BrazingIndoor Unit Control Main Sub master remote controller Weekly timerIndoor Control Circuit Outline of specifications Remarks Control SpecificationsRemote controller Outline of control Command Operation Heating AutoHeat Control temp C Operation Prohibited Case of wired remote controllerLast push priority CenterTa˚C Normal control RAV-SM561BT-E / SM801BT-E / SM1101BT Indoor Print Circuit BoardMCC-1402 SM1401BT-EFunction Connector Pin Specifications Remarks Indoor P.C. Board Optional Connector SpecificationsPulse Modulating Valve PMV control Discharge temperature release controlOutdoor Control Outline of Main ControlsMAX Heating operation Outdoor fan control Object SM560Allocations of fan tap revolutions Cooling operationCurrent release value shift control Short intermittent operation preventive controlHigh-pressure suppression TE control For SM800 Over-current preventive controlStart of heating operation Defrost controlPrint Circuit Board Outdoor ControlsMCC-813 RAV-SM560AT-E Viewed from parts of P.C board MCC-1398 RAV-SM800AT-E / SM1100AT-E / SM1400AT-E Before troubleshooting TroubleshootingSummary of Troubleshooting Wired remote controller typeError mode detected by indoor unit Check Code ListDiagnostic function Cause of operation Error mode detected by outdoor unitTimer Ready Wired remote Controller Check code Error mode detected by remote controller or network adapterIpdu side Error Mode Detected by LED on Outdoor P.C. BoardSW800 LED display in bit 1, bit 2, bit 3, bit 4 OFF CDB sideCheck code SW800 LED display in bit 1, bit 2, bit 3 OFFType a New Check Code/Present Check Code Central Control Side Troubleshooting Procedure for Each Check CodeE01 error/*99 error E09 error/*99 errorE04 error/04 error L09 error/46 error E10 error/CF errorE18 error/97 error *99 error E08, L03, L07, L08 error/ *96 error 99 errorL30 error/B6 error L20 error/98 errorB7 error Central controller F10 error 0C error P10 error/Ob errorP12 error/11 error Single phase P22 error/1A errorRAV-SM1100AT-E, SM1400AT-E F02 error/0d error P19 error/08 errorP26 error/14 error F01 error/0F errorH03 error/17 error P29 error/16 errorF04 error/19 error F06 error/18 errorF08 error/1b error H02 error/1d error L29 error/1C errorH01 error/1F error P03 error/1E errorP04 error/21 error Error Central controller F29 error / 12 error E03 error Master indoor unitP31 error Sub indoor unit TD sensor Caracteristics-4 TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1Caracteristics-3 20 TE, TO, TS sensorCase Replacement of Service Indoor P.C. BoardMinimum requirements for item code R1 Readout of the setup data from EepromR2 Replacement of service P.C. board ContentsR3 Writing of the setup contents to Eeprom Type Item code Memorandum for setup contents Item code table ExampleIndoor unit capacity Item code Wired remote controller Setup AT Local Site and OthersTest Run Setup on Remote Controller Setup to Select FunctionDescription At shipment Item No. DN table Selection of functionSetup method Cabling and Setting of Remote Controller ControlOperation Contents Monitor Function of Remote Controller SwitchProcedure System example Calling of error historyGroup control operation RequirementNetwork Adapter Microcomputer Block DiagramNetwork Address Setup Switch SW01 LED Display SpecificationNetwork cable connection Communication Cable SpecificationsCommunication circuit Communication cable specifications Cable ConnectionProcedure Set the network address while the unit stops How to Set an Address NumberHow to set from the remote controller at indoor unit side How to set by the switch on the network adapter P.C. boardNetwork address No. setup table SW01 Requirement in ServiceAddress No Contents Remarks Address Setup Address SetupAddress setup procedure Automatic address example from unset address No miscabling Address Setup & Group ControlSystem configuration Only turning on source power supply Automatic completionSetup completes Status returns to the usual stop status Manual setting from remote controllerTo know the position of indoor unit body by address Push button if the unit stopsPush and buttons simultaneously for 4 seconds or more Detachments Part name Procedure RemarksNo. Part name Procedure Remarks † Drain pump Remove the drain pan and float switch Attachment DetachmentPart name Procedure RemarksRequirement Part name ProcedureConnection with the power terminal Take off fixed screw for the valve mounting ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement 100101 102 103 104 Product 105106 107 108 109 110 Case of RAV-SM1400AT-E 111Case of RAV-SM1100AT-E Be sure to mount the propeller fan112 113 Location Exploded Views and Parts List114 Part Description115 904 901, 902, 903 35, 36, 37RAV-SM1001BT-E / SM1401BT-E 116RAV-SM561BT-E / SM801BT-E / SM1001BT-E / SM1401BT-E 117118 Inverter119 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704120 21,22 16,17121 706122 Inverter 26,27 23,24 28,29123 TH Sensor