Raypak 0090B 0135B installation instructions Servicing Procedures, General Location of Controls

Page 22

4. SERVICING PROCEDURES

GENERAL LOCATION OF CONTROLS

CIRCULATOR

CONTROL BOX COMPONENT LOCATIONS MODELS 135 & 180

2-Staged Controller

Relay

Fast

Response Ignition Module

Temperature (Auto Ignition Only)

Sensor

Fig.#8195.1

VENT SENSOR

BYPASS VALVE

(MODELS 135 & 180 ONLY)

BYPASS LINE

TEMPERATURE

AND PRESSURE GAUGE

2-STAGED CONTROLLER

(MODEL 90 ONLY)

PRESSURE

RELIEF VALVE

RELAY

ADJUSTABLE

HIGH LIMIT

FIELD WIRING

COMPARTMENT

FAST RESPONSE TEMPERATURE SENSOR

IGNITION MODULE

(AUTO IGNITION ONLY)

TRANSFORMER

ROLL-OUT SENSOR

GAS VALVE

Fig.#8195.4

SEQUENCE OF OPERATION INTERMITTENT IGNITION DEVICE (IID)

Boilers equipped with the IID system will automatically light the pilot burner first and then the main burner, each time there is a call for heat from the room thermostat. Whenever the room thermostat is calling for heat, the circulator supplied with the boiler, will be energized and should be running. The ignition control module will also be energized to initiate the pilot ignition by opening the first main valve (pilot). At the same time, the electronic spark generator in the module produces a high voltage spark pulse output that lights the pilot burner. If the pilot burner does not light, the module will not energize the second main valve and the burners will not light. Ignition spark continues only until the timed trial for ignition period ends. Then, the module goes into safety shutdown or lockout. Lockout de-energizes the first main valve operator and closes the first main (pilot) valve in the gas control, stopping pilot gas flow. The ignition control system must be reset by setting the thermostat below room temperature for one minute or by turning off power to the module for one minute. When the pilot flame is established, flame rectification circuit is completed between the sensor and burner ground. The flame sensing circuit in the module detects the flame current, shuts off the spark generator and energizes the second main valve operator which opens the second main valve. This allows gas to flow to the burners where it is ignited by the pilot burner flame. When the thermostat is satisfied, the valve operators are de-energized shutting off the pilot and main burners, and also the circulator.

22

Image 22
Contents Operating Installation Instructions For Your SafetyContents Specifications and Dimensions General SpecificationsReceiving Equipment Mounting Base Installation ProceduresCode Requirements Clearance RequirementsModel Sq. In. of Free Area 0030, 0042 100 Venting ConnectionsCommon Vents Fig.#Vent Damper Installation LocationD80D General Wiring Diagram Installing the Vent Damper in Horizontal & Vertical VentsMounting Vent Damper Flair DamperGAS Supply Connections GAS PRESSURE-SPECIFICATIONSWater Connections & System Piping Typical Piping Single Zone PipingZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Circulators Multiple Zones with Zone ValvesElectrical Wiring Fig.#Wiring Diagram Standing Pilot 24 V 2 Stage Fig. # 2223eWiring Diagramintermittent Ignition Device IID Models 30, 42 Wiring Diagram Intermittent Ignition Device IID Fig. #2358Wiring Diagram Single Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut Off Device Control BOX Component Locations Models 135 Servicing ProceduresGeneral Location of Controls Sequence of Operation Intermittent Ignition Device IIDSTART-UP Procedures Filling the SystemLighting the Boiler What to do if YOU Smell GASHoneywell Pilot Robertshaw Pilot For Automatic Ignition ModelsSystem Shut Down Procedure To Turn OFF GAS to BoilerFor Automatic Ignition Systems Flame Failure Inspection Procedures BurnersSafe Shutdown Tests Limit Action Main Burner FlameMain Burner and Orifice Removal Raypak Tube Cleaning KITBurner Drawer Removal Repair SectionHeat Exchanger RE-ASSEMBLY Combustion Chamber RemovalTrouble Shooting Guide Important NoticePiping ADJUSTMENTS/REPLACEMENTS of Components Replacement Parts List RAYPAK, INCBypass valve supplied on sizes H-0135 and H-0180 only Page Venting