MOUNTING
On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent.
The vent damper is set up for a continuous pilot system. If the vent damper is installed on an Intermittent Pilot or Hot Surface Ignition equipped system, the energy savings of the vent damper can be improved by plugging the hole in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.
Hole in Vent Damper Blade
Closed Position
Fig. #8994
DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazardous condition.
HORIZONTAL INSTALLATION
| FLOW > |
| NO |
|
| YES | YES |
TO BOILER | VENT DAMPER | TO CHIMNEY |
|
|
|
| NO |
1K |
1K1 |
VERTICAL
INSTALLATION
TO CHIMNEY
VENT
DAMPER
AT BOILER
DRAFT
HOOD
INSTALL VENT
DAMPER WITH ACTUATOR TO SIDES OF VENT ONLY. DO NOT MOUNT ABOVE OR BELOW VENT.
ACTUATOR MAY BE INSTALLED IN ANY POSITION ON VERTICAL PIPE.
| D80 |
|
|
| MOTOR |
|
|
N.C. |
|
|
|
END |
|
| 1K2 |
SWITCH N.O. | C. |
| |
|
| ||
| 1K3 |
|
|
4 | 3 | 2 | 1 |
INSTALLING THE VENT DAMPER IN HORIZONTAL & VERTICAL VENTS.
CABLE
Fig. #152323
D80D GENERAL WIRING DIAGRAM
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED. IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON MONOXIDE POISONING, COULD RESULT.