Raypak 0090B 0135B Mounting, Installing the Vent Damper in Horizontal & Vertical Vents

Page 8

MOUNTING

On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent.

The vent damper is set up for a continuous pilot system. If the vent damper is installed on an Intermittent Pilot or Hot Surface Ignition equipped system, the energy savings of the vent damper can be improved by plugging the hole in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.

Hole in Vent Damper Blade

Closed Position

Fig. #8994

DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazardous condition.

HORIZONTAL INSTALLATION

 

FLOW >

 

NO

 

 

YES

YES

TO BOILER

VENT DAMPER

TO CHIMNEY

 

 

 

 

NO

1K

1K1

VERTICAL

INSTALLATION

TO CHIMNEY

VENT

DAMPER

AT BOILER

DRAFT

HOOD

INSTALL VENT

DAMPER WITH ACTUATOR TO SIDES OF VENT ONLY. DO NOT MOUNT ABOVE OR BELOW VENT.

ACTUATOR MAY BE INSTALLED IN ANY POSITION ON VERTICAL PIPE.

 

D80

 

 

 

MOTOR

 

 

N.C.

 

 

 

END

 

 

1K2

SWITCH N.O.

C.

 

 

 

 

1K3

 

 

4

3

2

1

INSTALLING THE VENT DAMPER IN HORIZONTAL & VERTICAL VENTS.

CABLE

Fig. #152323

D80D GENERAL WIRING DIAGRAM

INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED. IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON MONOXIDE POISONING, COULD RESULT.

8

Image 8
Contents Operating Installation Instructions For Your SafetyContents Receiving Equipment General SpecificationsSpecifications and Dimensions Installation Procedures Code RequirementsMounting Base Clearance RequirementsModel Sq. In. of Free Area 0030, 0042 100 Venting ConnectionsCommon Vents Fig.#Vent Damper Installation LocationMounting Installing the Vent Damper in Horizontal & Vertical VentsD80D General Wiring Diagram Vent Damper Flair DamperWater Connections & System Piping GAS PRESSURE-SPECIFICATIONSGAS Supply Connections Typical Piping Single Zone PipingZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Circulators Multiple Zones with Zone ValvesElectrical Wiring Fig.#Wiring Diagram Standing Pilot 24 V 2 Stage Fig. # 2223eWiring Diagramintermittent Ignition Device IID Models 30, 42 Wiring Diagram Intermittent Ignition Device IID Fig. #2358Wiring Diagram Single Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut Off Device Servicing Procedures General Location of ControlsControl BOX Component Locations Models 135 Sequence of Operation Intermittent Ignition Device IIDSTART-UP Procedures Filling the SystemLighting the Boiler What to do if YOU Smell GASHoneywell Pilot Robertshaw Pilot For Automatic Ignition ModelsSystem Shut Down Procedure To Turn OFF GAS to BoilerFor Automatic Ignition Systems Inspection Procedures Burners Safe Shutdown Tests Limit ActionFlame Failure Main Burner FlameRaypak Tube Cleaning KIT Burner Drawer RemovalMain Burner and Orifice Removal Repair SectionHeat Exchanger RE-ASSEMBLY Combustion Chamber RemovalTrouble Shooting Guide Important NoticePiping ADJUSTMENTS/REPLACEMENTS of Components Replacement Parts List RAYPAK, INCBypass valve supplied on sizes H-0135 and H-0180 only Page Venting