ADJUSTMENTS/REPLACEMENTS OF COMPONENTS

DANGER - SHOCK HAZARD

Make sure electrical power to the boiler is disconnect- ed to avoid potential serious injury or damage to com- ponents.

1.Gas Valve Replacement

a)Shut off electrical power and gas supply to the boiler.

b)Remove gas piping to gas valve inlet.

c)Disconnect wiring connections, pilot tubing (when equipped).

d)Remove screws (2) holding the burner tray.

e)Slide burner tray out.

f)Remove gas valve bracket screws and bracket.

g)Unscrew gas valve from gas pipe.

h)Reverse above procedure to re-install.

2.Pilot Burner Cleaning or Replacement (Standing Pilot)

a)Shut off electrical power and gas supply to the boiler.

b)Disconnect gas piping to gas valve.

c)Disconnect wiring connections to gas valve.

d)Remove screws (2) holding the burner tray.

e)Slide burner tray out.

f)Remove screw holding pilot lighter tube.

g)Remove screws (2) holding pilot bracket on the burner tray.

h)Disconnect thermocouple and pilot tubing from the gas valve.

i)Remove pilot burner from pilot bracket.

j)Remove pilot orifice and blow away lint or dirt. Clean with wire or small brush.

NOTE: Make sure pilot orifice is clear, but do not enlarge the hole.

k) Reverse above procedure to re-install.

HONEYWELL PILOT

ROBERTSHAW PILOT

PILOT

PILOT

AIR

OPENING

ORIFICE

ORIFICE

Fig.# 8045.2

Fig.# 8102.1

3.Flame Roll-out Switch Replacement

a)Shut off electrical power to the boiler.

b)Remove wiring connections to switch.

c)Remove screws (2) holding the switch.

d)Reverse above procedure to re-install.

4.Vent Thermal Switch Replacement

a)Shut off electrical power to the boiler.

b)Remove wiring connections to switch.

c)Remove the screws (2).

d)Reverse above procedure to re-install.

5.Ignition Module Replacement

a)Shut off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring connections to module.

d)Remove screws (2) holding module.

e)Reverse above procedure to re-install.

6.Transformer Replacement

a)Shut off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring connections from trans- former leads.

d)Remove screws (2) holding transformer.

e)Reverse above procedure to re-install.

7.Pump Relay Replacement

a)Shut off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring to the relay.

d)Remove screws (2) holding relay.

e)Reverse above procedure to re-install.

8.Adjustable High Limit Control

a)Shut off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)The control is factory set at 180°F. To reset to another setting, use a small screw driver

and turn dial clockwise

to lower the

temperature or counter-clockwise

to

raise the setting.

 

 

d)To replace the limit control, disconnect the wir- ing connections.

e)Remove screws (2) holding the limit control.

f)Remove upper access panel.

g)Remove the wedge or retaining clip holding the sensing bulb in the control well in the in/out header.

h)Pull out the sensing bulb carefully from the control well.

i)Remove the limit control with capillary from unit.

33

Image 33
Contents For Your Safety Operating Installation InstructionsContents General Specifications Specifications and DimensionsReceiving Equipment Code Requirements Installation ProceduresMounting Base Clearance RequirementsVenting Connections Model Sq. In. of Free Area 0030, 0042 100Fig.# Common VentsLocation Vent Damper InstallationInstalling the Vent Damper in Horizontal & Vertical Vents D80D General Wiring DiagramMounting Flair Damper Vent DamperGAS PRESSURE-SPECIFICATIONS GAS Supply ConnectionsWater Connections & System Piping Single Zone Piping Typical PipingZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Zone Valves Multiple Zones with CirculatorsFig.# Electrical WiringFig. # 2223e Wiring Diagram Standing Pilot 24 V 2 StageWiring Diagramintermittent Ignition Device IID Models 30, 42 Fig. #2358 Wiring Diagram Intermittent Ignition Device IIDWiring Diagram Single Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut Off Device General Location of Controls Servicing ProceduresControl BOX Component Locations Models 135 Sequence of Operation Intermittent Ignition Device IIDFilling the System START-UP ProceduresWhat to do if YOU Smell GAS Lighting the BoilerFor Automatic Ignition Models Honeywell Pilot Robertshaw PilotTo Turn OFF GAS to Boiler System Shut Down ProcedureFor Automatic Ignition Systems Safe Shutdown Tests Limit Action Inspection Procedures BurnersFlame Failure Main Burner FlameBurner Drawer Removal Raypak Tube Cleaning KITMain Burner and Orifice Removal Repair SectionCombustion Chamber Removal Heat Exchanger RE-ASSEMBLYImportant Notice Trouble Shooting GuidePiping ADJUSTMENTS/REPLACEMENTS of Components RAYPAK, INC Replacement Parts ListBypass valve supplied on sizes H-0135 and H-0180 only Page Venting