Error Codes
The Rinnai water heater has the ability to check its own operation continuously. If a fault occurs, an error code will flash on the Display of the temperature controller. This assists with diagnosing the fault and may enable you to overcome a problem without a service call. Please identify the code displayed when inquiring about service.
Code | Fault |
| Remedy |
|
03 | Power interruption during |
| Turn off all hot water taps. Press ON/OFF twice. |
|
| Bath Fill (Water will not flow |
|
| |
| when power returns). |
|
|
|
10 | Air Supply or Exhaust |
| Ensure Rinnai approved venting materials are being used. |
|
| Blockage |
| Check that nothing is blocking the flue inlet or exhaust. |
|
|
|
| Check all vent components for proper connections. |
|
|
|
| Ensure vent length is within limits. |
|
|
|
| Ensure condensation collar was installed correctly. |
|
|
|
| Verify dip switches are set properly. |
|
|
|
| Check fan for blockage. |
|
|
|
| Burner Sensor Error (see code 31) |
|
|
|
| Check the fins in the heat exchanger. |
|
11 | No Ignition |
| Check that the gas is turned on at the water heater, gas meter, or cylinder. |
|
|
|
| Ensure gas type and pressure is correct. |
|
|
|
| Ensure gas line, meter, and/or regulator is sized properly. |
|
|
|
| Bleed all air from gas lines. |
|
|
|
| Verify dip switches are set properly. |
|
|
|
| Ensure appliance is properly grounded. |
|
|
|
| Disconnect EZConnect™ or MSA controls to isolate the problem. |
|
|
|
| Ensure igniter is operational. |
|
|
|
| Check igniter wiring harness for damage. |
|
|
|
| Check gas solenoid valves for open or short circuits. |
|
|
|
| Remove burner cover and ensure all burners are properly seated. |
|
|
|
| Remove burner plate and inspect burner surface for condensation or debris. |
|
|
|
|
| |
12 | Flame Failure |
| Check that the gas is turned on at the water heater and gas meter. Check for obstructions in | |
|
|
| the flue outlet. |
|
|
|
| Ensure gas line, meter, and/or regulator is sized properly. |
|
|
|
| Ensure gas type and pressure is correct. |
|
|
|
| Bleed all air from gas lines. |
|
|
|
| Ensure proper Rinnai venting material was installed. |
|
|
|
| Ensure condensation collar was installed properly. |
|
|
|
| Ensure vent length is within limits. |
|
|
|
| Verify dip switches are set properly. |
|
|
|
| Ensure appliance is properly grounded. |
|
|
|
| Disconnect keypad. |
|
|
|
| Disconnect EZConnect™ or MSA controls to isolate the problem. |
|
|
|
| Check power supply for loose connections. |
|
|
|
| Check power supply for proper voltage and voltage drops. |
|
|
|
| Ensure flame rod wire is connected. |
|
|
|
| Check flame rod for carbon |
|
|
|
| Disconnect and reconnect all wiring harnesses on unit and PC board. |
|
|
|
| Check for DC shorts at components. |
|
|
|
| Check gas solenoid valves for open or short circuits. |
|
|
|
| Remove burner plate and inspect burner surface for condensation or debris. |
|
|
|
| Check the ground wire for the PC board. |
|
14 | Thermal Fuse |
| Check gas type of unit and ensure it matches gas type being used. |
|
|
|
| Check for restrictions in air flow around unit and vent terminal. |
|
|
|
| Check for low water flow in a circulating system causing |
|
|
|
| Ensure dip switches are set to the proper position. |
|
|
|
| Check for foreign materials in combustion chamber and/or exhaust piping. |
|
|
|
| Check heat exchanger for cracks and/or separations. |
|
|
|
| Check heat exchanger surface for hot spots which indicate blockage due to scale |
|
|
|
| Refer to instructions in manual for flushing heat exchanger. |
|
|
|
| Measure resistance of safety circuit. |
|
|
|
| Ensure high fire and low fire manifold pressure is correct. |
|
|
|
| Check for improper conversion of product. |
|
|
|
|
|
|
|