Error Codes

Error Codes

The Rinnai water heater has the ability to check its own operation continuously. If a fault occurs, an error code will flash on the Display of the temperature controller. This assists with diagnosing the fault and may enable you to overcome a problem without a service call. Please identify the code displayed when inquiring about service.

Code

Fault

 

Remedy

 

03

Power interruption during

 

Turn off all hot water taps. Press ON/OFF twice.

 

 

Bath Fill (Water will not flow

 

 

 

when power returns).

 

 

 

10

Air Supply or Exhaust

 

Ensure Rinnai approved venting materials are being used.

 

 

Blockage

 

Check that nothing is blocking the flue inlet or exhaust.

 

 

 

 

Check all vent components for proper connections.

 

 

 

 

Ensure vent length is within limits.

 

 

 

 

Ensure condensation collar was installed correctly.

 

 

 

 

Verify dip switches are set properly.

 

 

 

 

Check fan for blockage.

 

 

 

 

Burner Sensor Error (see code 31)

 

 

 

 

Check the fins in the heat exchanger.

 

11

No Ignition

 

Check that the gas is turned on at the water heater, gas meter, or cylinder.

 

 

 

 

Ensure gas type and pressure is correct.

 

 

 

 

Ensure gas line, meter, and/or regulator is sized properly.

 

 

 

 

Bleed all air from gas lines.

 

 

 

 

Verify dip switches are set properly.

 

 

 

 

Ensure appliance is properly grounded.

 

 

 

 

Disconnect EZConnect™ or MSA controls to isolate the problem.

 

 

 

 

Ensure igniter is operational.

 

 

 

 

Check igniter wiring harness for damage.

 

 

 

 

Check gas solenoid valves for open or short circuits.

 

 

 

 

Remove burner cover and ensure all burners are properly seated.

 

 

 

 

Remove burner plate and inspect burner surface for condensation or debris.

 

 

 

 

 

12

Flame Failure

 

Check that the gas is turned on at the water heater and gas meter. Check for obstructions in

 

 

 

the flue outlet.

 

 

 

 

Ensure gas line, meter, and/or regulator is sized properly.

 

 

 

 

Ensure gas type and pressure is correct.

 

 

 

 

Bleed all air from gas lines.

 

 

 

 

Ensure proper Rinnai venting material was installed.

 

 

 

 

Ensure condensation collar was installed properly.

 

 

 

 

Ensure vent length is within limits.

 

 

 

 

Verify dip switches are set properly.

 

 

 

 

Ensure appliance is properly grounded.

 

 

 

 

Disconnect keypad.

 

 

 

 

Disconnect EZConnect™ or MSA controls to isolate the problem.

 

 

 

 

Check power supply for loose connections.

 

 

 

 

Check power supply for proper voltage and voltage drops.

 

 

 

 

Ensure flame rod wire is connected.

 

 

 

 

Check flame rod for carbon build-up.

 

 

 

 

Disconnect and reconnect all wiring harnesses on unit and PC board.

 

 

 

 

Check for DC shorts at components.

 

 

 

 

Check gas solenoid valves for open or short circuits.

 

 

 

 

Remove burner plate and inspect burner surface for condensation or debris.

 

 

 

 

Check the ground wire for the PC board.

 

14

Thermal Fuse

 

Check gas type of unit and ensure it matches gas type being used.

 

 

 

 

Check for restrictions in air flow around unit and vent terminal.

 

 

 

 

Check for low water flow in a circulating system causing short-cycling.

 

 

 

 

Ensure dip switches are set to the proper position.

 

 

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

 

 

Check heat exchanger for cracks and/or separations.

 

 

 

 

Check heat exchanger surface for hot spots which indicate blockage due to scale build-up.

 

 

 

 

Refer to instructions in manual for flushing heat exchanger.

 

 

 

 

Measure resistance of safety circuit.

 

 

 

 

Ensure high fire and low fire manifold pressure is correct.

 

 

 

 

Check for improper conversion of product.

 

 

 

 

 

 

 

 

Manual - Rinnai Condensing Water Heaters

13

Image 13
Contents Direct Vent Tankless Water Heater Operation and Installation ManualANS Z21.10.3 Consumer Safety Information Table of ContentsError Codes Technical DataRC80HPi SpecificationsRC98HPi RC98HPeSafety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features DANGERDescription of Operation Features Available on Temperature ControllersOperating Instructions In Use Indicator Temperature Display Temperature MC-502RC-1US-S* WirelessPriority Indicator Priority Button ON/OFF Button IndicatorPriority Button and Indicator ON/OFF Button In Use Indicator Temperature Display Clock CallBC-100V-1US MC-100V-1USTemperature Controller Settings How to Set the TemperatureRC80HPi RC80HPeTemperature Controller Settings Setting the Sound Volume Voice PromptRe-settingthe Maximum Temperature MCC-91Temperature Controller Setting the Water Volume Using the Water Smart / Bath Fill Function Overview Setting the Clock Setting Controller to MuteUsing the Water Smart / Bath Fill Function Filling the TubCleaning MaintenanceVent System MotorsFault Error CodesCode Remedycode Manual - Rinnai Condensing Water HeatersAccessing Operating Information Trouble Shooting for Common IssuesWater Quality I don’t have any hot water when I open the tapH2 H1 Circulating Pump Flushing the Heat Exchanger Error Code LC orWater Heater General Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGas Piping Electrical ConnectionGeneral Instructions Gas Piping Pipe Sizing Procedure - ExampleGas Input of Rinnai water heater BTU / HR Cubic Feet per Hour CFH =General Instructions Water PipingPressure Relief Valve Freeze ProtectionFreeze Protection Piping Condensate drain line Recommended Piping for Basic InstallationCondensate drain For this application Recommended Piping for Circulation Systems3 years on heat exchanger 3 year on parts Optional Piping for Circulation SystemsManual - Rinnai Condensing Water Heaters For this applicationIntake / Exhaust Guidelines Venting InstructionsCondensate Vent Products Maximum Vent LengthREU-KA2530FFUD-US RC98HPiAREA WHERE B TERMINAL IS NOT PERMITTTED Flue Terminal Clearances ANS Z21.10.3 CSACanadian Installations US InstallationsINSIDE CORNER IN S ID E C O R N E R Additional Clearances RC80HPe, RC98HPeDispose of condensate per local codes Flue Installation RC80HPi, RC98HPiDispose of condensate per local codes Securing Manual - Rinnai Condensing Water HeatersConnecting Multiple Water Heaters High Altitude InstallationsGuidelines Configurations Temperature Controller InstallationLocation Cable Lengths and SizeTemperature Controller Installation securing screw wiring hole securing screwMounting the Controller Outline of RemoteOperating Instructions FOR YOUR SAFETY READ BEFORE OPERATINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEPressure Drop Curve Technical DataOutlet Flow Data Pressure Loss psiTemperature Setting Space HeatingReplacement PumpsRC80HPi, RC98HPi DimensionsRC80HPi, RC80HPe RC80HPe, RC98HPeTWIN THERMISTOR Ladder DiagramLimited Warranty Warranty InformationConsumer Support How do I get service? Limited Warranty ContinuedWhat is not covered? What will Rinnai do?ou lappel 1-866-RINNAI1 Manuel dinstallation et dutilisationComportements et pratiques de sécurité Instructions dutilisationRéglage de température Chaud BrûlureRC80HPi Options de température sans contrôleur à distanceRC80HPe RC98HPiCORRECT VUE DE FACE EntretienINCORRECT VUE DE FACE NettoyageInstallation Instructions Instructions généralesNutilisez pas de matériaux de substitution Manuel - Rinnai Condensing Water HeatersFixation du chauffe-eau Écartements par rapport à lappareilRC80HPe, RC98HPe Tuyauterie de gaz Installations à haute altitudeInstructions générales Qualité de leau Tuyauterie deauInstructions générales Soupape de sûretéLégende Tuyauterie recommandée pour installation de baseCondensate Vidange condensat drain Consignes pour aspiration/évacuation Instructions de ventilationCondensat Longueur maximum de ventilation RC80HPi ................. REU-KA2530FFUD Produits de ventilationRC98HPi ................. REU-KA3237FFUD Rinnai/UbbinkInstallations aux USA Installations au CanadaENTÉE DALIMENTATION EN AIR TERMINAISON DE VENTILATIONVis de fixation INSTRUCTIONS DE MISE EN MARCHE Instructions dutilisationCOMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL FERMÉECLOSE OUVERTOPENCONTACT DE Diagramme en escalierFUSIBLE 7 A DÉTECTION DE GELInformations sur la garantie Support à la clientèleGarantie limitée Manuel - Rinnai Condensing Water Heaters Garantie limitéeQue fait Rinnai pour exercer la garantie ? Quest-cequi nest pas couvert ?U290-665X01 Rinnai’s other fine products