Rinnai RC80HPI, RC98HPE Space Heating, Temperature Setting, Pumps, Replacement, Iron Components

Page 37
Space Heating

Space Heating

If the water heater is to be used for both water (potable) heating and space heating then the following apply.

The piping and components connected to the water heater shall be suitable for use with potable water.

Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water.

The water heater shall not be connected to any heating system or components previously used with a nonpotable water heating appliance.

When the system requires water for space heating at temperatures higher than required for other uses, a means such as a mixing valve shall be installed to temper the water for other uses in order to reduce the scald hazard potential.

Space heating applications are considered commercial applications for warranty purposes.

Temperature Setting

When using this appliance to provide domestic hot water it is recommended that the domestic hot water temperature be reduced to acceptable temperatures in accordance with local codes. In the absence of local codes it is recommended that the domestic hot water temperature be set to 140º F (60º C) or lower in accordance with UPC 501.6 by using mixing valves or the temperature controller for the water heater.

Pumps

Only use pumps of brass or stainless steel construction. Do not use pumps of iron construction as they will oxidize and clog the inlet filter on the appliance.

Pumps circulating water through the water heater must be sized to overcome the pressure loss through the water heater, the heating system, and any additional plumbing pressure losses. The pressure drop curve based on the water heater model is provided in this manual.

Replacement

When replacing an existing space heating application’s water heating source (boiler, tank water heater, tankless water heater, etc.) with Rinnai water heaters, ensure that the water heaters are sized to adequately provide the necessary BTU input for the desired space heating application. Rinnai water heaters are designed to maintain a constant outlet temperature and will supply only the necessary amount of BTU’s to maintain that temperature. Depending on the application the maximum BTU rating of the unit may not be achieved. Contact Rinnai’s Applications Engineering Department for assistance at (800) 621-9419 ext. 4490.

Iron Components

Do not use Rinnai water heaters directly for space heating applications involving iron radiators or applications with any iron components. Iron components may oxidize creating rust that will clog the inlet filter of the Rinnai water heater.

Manual - Rinnai Condensing Water Heaters

37

Image 37
Contents Direct Vent Tankless Water Heater Operation and Installation ManualANS Z21.10.3 Consumer Safety Information Table of ContentsError Codes Technical DataRC80HPi SpecificationsRC98HPi RC98HPeSafety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features DANGERDescription of Operation Features Available on Temperature ControllersOperating Instructions In Use Indicator Temperature Display Temperature MC-502RC-1US-S* WirelessPriority Indicator Priority Button ON/OFF Button IndicatorPriority Button and Indicator ON/OFF Button In Use Indicator Temperature Display Clock CallBC-100V-1US MC-100V-1USTemperature Controller Settings How to Set the TemperatureRC80HPi RC80HPeTemperature Controller Settings Setting the Sound Volume Voice PromptRe-settingthe Maximum Temperature MCC-91Temperature ControllerSetting the Water Volume Using the Water Smart / Bath Fill FunctionOverview Setting the Clock Setting Controller to MuteUsing the Water Smart / Bath Fill Function Filling the TubCleaning MaintenanceVent System MotorsFault Error CodesCode Remedycode Manual - Rinnai Condensing Water HeatersAccessing Operating Information Trouble Shooting for Common IssuesWater Quality I don’t have any hot water when I open the tapH2 H1 Circulating Pump Flushing the Heat Exchanger Error Code LC orWater Heater General Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGas Piping Electrical ConnectionGeneral Instructions Gas Piping Pipe Sizing Procedure - ExampleGas Input of Rinnai water heater BTU / HR Cubic Feet per Hour CFH =General Instructions Water PipingPressure Relief Valve Freeze ProtectionFreeze Protection Piping Condensate drain line Recommended Piping for Basic InstallationCondensate drain For this application Recommended Piping for Circulation Systems3 years on heat exchanger 3 year on parts Optional Piping for Circulation SystemsManual - Rinnai Condensing Water Heaters For this applicationIntake / Exhaust Guidelines Venting InstructionsCondensate Vent Products Maximum Vent LengthREU-KA2530FFUD-US RC98HPiAREA WHERE B TERMINAL IS NOT PERMITTTED Flue Terminal Clearances ANS Z21.10.3 CSACanadian Installations US InstallationsINSIDE CORNER IN S ID E C O R N E R Additional Clearances RC80HPe, RC98HPeDispose of condensate per local codes Flue Installation RC80HPi, RC98HPiDispose of condensate per local codes Securing Manual - Rinnai Condensing Water HeatersConnecting Multiple Water Heaters High Altitude InstallationsGuidelines Configurations Temperature Controller InstallationLocation Cable Lengths and Size Temperature Controller Installation securing screw wiring hole securing screw Mounting the Controller Outline of RemoteOperating Instructions FOR YOUR SAFETY READ BEFORE OPERATINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEPressure Drop Curve Technical DataOutlet Flow Data Pressure Loss psiTemperature Setting Space HeatingReplacement PumpsRC80HPi, RC98HPi DimensionsRC80HPi, RC80HPe RC80HPe, RC98HPeTWIN THERMISTOR Ladder DiagramLimited Warranty Warranty InformationConsumer Support How do I get service? Limited Warranty ContinuedWhat is not covered? What will Rinnai do?ou lappel 1-866-RINNAI1 Manuel dinstallation et dutilisationComportements et pratiques de sécurité Instructions dutilisationRéglage de température Chaud BrûlureRC80HPi Options de température sans contrôleur à distanceRC80HPe RC98HPiCORRECT VUE DE FACE EntretienINCORRECT VUE DE FACE NettoyageInstallation Instructions Instructions généralesNutilisez pas de matériaux de substitution Manuel - Rinnai Condensing Water HeatersFixation du chauffe-eau Écartements par rapport à lappareilRC80HPe, RC98HPe Tuyauterie de gaz Installations à haute altitudeInstructions générales Qualité de leau Tuyauterie deauInstructions générales Soupape de sûretéLégende Tuyauterie recommandée pour installation de baseCondensate Vidange condensat drain Consignes pour aspiration/évacuation Instructions de ventilationCondensat Longueur maximum de ventilation RC80HPi ................. REU-KA2530FFUD Produits de ventilationRC98HPi ................. REU-KA3237FFUD Rinnai/UbbinkInstallations aux USA Installations au CanadaENTÉE DALIMENTATION EN AIR TERMINAISON DE VENTILATIONVis de fixation INSTRUCTIONS DE MISE EN MARCHE Instructions dutilisationCOMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL FERMÉECLOSE OUVERTOPENCONTACT DE Diagramme en escalierFUSIBLE 7 A DÉTECTION DE GELInformations sur la garantie Support à la clientèleGarantie limitée Manuel - Rinnai Condensing Water Heaters Garantie limitéeQue fait Rinnai pour exercer la garantie ? Quest-cequi nest pas couvert ?U290-665X01 Rinnai’s other fine products