Rinnai RC80HPE, RC98HPE, RC80HPI Venting Instructions, Intake / Exhaust Guidelines, Condensate

Page 26
Venting Instructions

Venting Instructions

Intake / Exhaust Guidelines

Refer to the specific instructions on your vent product for

 

additional installation requirements.

This water heater is a direct vent water heater and therefore is certified and listed with the vent system. You must use vent components that are certified and listed with the water heater model.

Do not combine vent components from different manufacturers.

The vent system must vent directly to the outside of the building and use outside air for combustion.

Venting should be as direct as possible with a minimum number of pipe fittings.

Avoid dips or sags in horizontal vent runs by installing supports per the vent manufacturer’s instructions.

Support horizontal vent runs every four feet and all vertical vent runs every six feet or in accordance with local codes.

Vent diameter must not be reduced.

Do not connect the venting system with an existing vent or chimney.

Do not common vent with the vent pipe of any other water heater or appliance.

Vent connections must be firmly pressed together so that the gaskets form an air tight seal.

Refer to the instructions of the vent system manufacturer for component assembly instructions.

If the vent system is to be enclosed, it is suggested that the design of the enclosure shall permit inspection of the vent system. The design of such enclosure shall be deemed acceptable by the installer or the local inspector.

Condensate

The Rinnai RC80HPi and RC98HPi condensing tankless water heaters are factory equipped with a condensate trap and drain line.

Use only vent that is approved and identified as acceptable for condensing appliances.

Do not use aluminum, PVC, CPVC, ABS or galvanized material to vent this appliance.

Slope the venting toward the appliance according to the vent manufacturers installation instructions.

All condensate must drain and dispose of per local codes.

If the condensate drain gets blocked, an error code will display on the controller. If this occurs, the condensate drain must be cleaned.

The condensate trap will automatically prime (self- prime) during operation of the unit as condensate forms. Condensate draining from the unit indicates that the trap is full and that there is no blockage in the condensate drain. It is not necessary to add water to the condensate trap.

Use only PVC or CPVC pipe for the condensate drain line.

The drain pipe (along its entire length) must be at least the same diameter as the drain line, (1/2 inch NPT).

The condensate trap must be primed before operation to prevent exhaust gases from entering the building

The drain pipe should be as short as possible and have a downward pitch.

The end of the drain pipe should be open to the atmosphere. The end should not be under water or other substances.

Do not connect the drain pipe directly to the rain sewer.

Do not connect the condensate drain line with an air conditioning evaporator coil drain.

To minimize freezing of the condensate, run the condensate drain line through an interior wall or between insulation and an interior wall.

26

Manual - Rinnai Condensing Water Heaters

Image 26
Contents ANS Z21.10.3 Operation and Installation ManualDirect Vent Tankless Water Heater Error Codes Table of ContentsConsumer Safety Information Technical DataRC98HPi SpecificationsRC80HPi RC98HPeSafety Behavior and Practices Safety Features Consumer Safety InformationSafety Definitions DANGEROperating Instructions Features Available on Temperature ControllersDescription of Operation Priority Indicator Priority Button ON/OFF Button MC-502RC-1US-S* WirelessIn Use Indicator Temperature Display Temperature IndicatorBC-100V-1US In Use Indicator Temperature Display Clock CallPriority Button and Indicator ON/OFF Button MC-100V-1USRC80HPi How to Set the TemperatureTemperature Controller Settings RC80HPeRe-settingthe Maximum Temperature Setting the Sound Volume Voice PromptTemperature Controller Settings MCC-91Temperature ControllerOverview Using the Water Smart / Bath Fill FunctionSetting the Water Volume Using the Water Smart / Bath Fill Function Setting Controller to MuteSetting the Clock Filling the TubVent System MaintenanceCleaning MotorsCode Error CodesFault RemedyManual - Rinnai Condensing Water Heaters codeWater Quality Trouble Shooting for Common IssuesAccessing Operating Information I don’t have any hot water when I open the tapWater Heater Flushing the Heat Exchanger Error Code LC orH2 H1 Circulating Pump Installation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGeneral Instructions Electrical ConnectionGas Piping Gas Input of Rinnai water heater BTU / HR Pipe Sizing Procedure - ExampleGas Piping Cubic Feet per Hour CFH =Pressure Relief Valve Water PipingGeneral Instructions Freeze ProtectionFreeze Protection Piping Condensate drain Recommended Piping for Basic InstallationCondensate drain line Recommended Piping for Circulation Systems For this applicationManual - Rinnai Condensing Water Heaters Optional Piping for Circulation Systems3 years on heat exchanger 3 year on parts For this applicationCondensate Venting InstructionsIntake / Exhaust Guidelines REU-KA2530FFUD-US Maximum Vent LengthVent Products RC98HPiCanadian Installations Flue Terminal Clearances ANS Z21.10.3 CSAAREA WHERE B TERMINAL IS NOT PERMITTTED US InstallationsINSIDE CORNER Additional Clearances RC80HPe, RC98HPe IN S ID E C O R N E RDispose of condensate per local codes Securing Flue Installation RC80HPi, RC98HPiDispose of condensate per local codes Manual - Rinnai Condensing Water HeatersGuidelines High Altitude InstallationsConnecting Multiple Water Heaters Location Temperature Controller InstallationConfigurations Cable Lengths and SizeMounting the Controller securing screw wiring hole securing screwTemperature Controller Installation Outline of RemoteOPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATINGOperating Instructions TO TURN OFF GAS TO APPLIANCEOutlet Flow Data Technical DataPressure Drop Curve Pressure Loss psiReplacement Space HeatingTemperature Setting PumpsRC80HPi, RC80HPe DimensionsRC80HPi, RC98HPi RC80HPe, RC98HPeLadder Diagram TWIN THERMISTORConsumer Support Warranty InformationLimited Warranty What is not covered? Limited Warranty ContinuedHow do I get service? What will Rinnai do?Manuel dinstallation et dutilisation ou lappel 1-866-RINNAI1Réglage de température Instructions dutilisationComportements et pratiques de sécurité Chaud BrûlureRC80HPe Options de température sans contrôleur à distanceRC80HPi RC98HPiINCORRECT VUE DE FACE EntretienCORRECT VUE DE FACE NettoyageNutilisez pas de matériaux de substitution Instructions généralesInstallation Instructions Manuel - Rinnai Condensing Water HeatersRC80HPe, RC98HPe Écartements par rapport à lappareilFixation du chauffe-eau Instructions générales Installations à haute altitudeTuyauterie de gaz Instructions générales Tuyauterie deauQualité de leau Soupape de sûretéCondensate Vidange condensat drain Tuyauterie recommandée pour installation de baseLégende Condensat Instructions de ventilationConsignes pour aspiration/évacuation Longueur maximum de ventilation RC98HPi ................. REU-KA3237FFUD Produits de ventilationRC80HPi ................. REU-KA2530FFUD Rinnai/UbbinkENTÉE DALIMENTATION EN AIR TERMINAISON DE Installations au CanadaInstallations aux USA VENTILATIONVis de fixation COMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL Instructions dutilisationINSTRUCTIONS DE MISE EN MARCHE FERMÉECLOSE OUVERTOPENFUSIBLE 7 A Diagramme en escalierCONTACT DE DÉTECTION DE GELGarantie limitée Support à la clientèleInformations sur la garantie Que fait Rinnai pour exercer la garantie ? Garantie limitéeManuel - Rinnai Condensing Water Heaters Quest-cequi nest pas couvert ?Rinnai’s other fine products U290-665X01