Rinnai RC98HPE, RC80HPI Maintenance, Cleaning, Vent System, Motors, Temperature Controller

Page 12
Maintenance

Maintenance

Repairs and maintenance should be performed by a qualified service technician. The appliance should be inspected annually by a qualified service technician. Verify proper operation after servicing.

Cleaning

It is imperative that control compartments, burners, and circulating air passageways of the appliance be kept clean.

Clean as follows:

1.Turn off and disconnect electrical power. Allow to cool.

2.Remove and clean the water inlet filter.

3.Remove the front panel by removing 4 screws.

4.Use pressurized air to remove dust from the main burner, heat exchanger, and fan blades. Do not use a wet cloth or spray cleaners on the burner. Do not use volatile substances such as benzene and thinners. They may ignite or fade the paint.

5.Use soft dry cloth to wipe cabinet.

Vent System

The vent system should be inspected at least annually for blockages or damage.

Motors

Motors are permanently lubricated and do not need periodic lubrication. Keep fan and motor free of dust and dirt by cleaning annually.

Temperature Controller

Use a soft damp cloth to clean the temperature controller. Do not use solvents.

Lime / Scale Build-up

If you receive Error Code “LC”, refer to the procedure, Flushing the Heat Exchanger. Refer to the section on Water Quality to see if your water needs to be treated or conditioned. (When checking maintenance code history, “00” is substituted for “LC”.)

Snow Accumulation

Keep the area around flue terminal free of snow and ice. The appliance will not function properly if the intake air or exhaust is impeded (blocked or partially blocked) by obstructions.

Visual Inspection of Flame

The burner must flame evenly over the entire surface when operating correctly. The flame must burn with a clear, blue, stable flame. See the parts breakdown of the burner for the location of the view ports.

The flame pattern should be as shown in the figures below.

12

Manual - Rinnai Condensing Water Heaters

Image 12
Contents Operation and Installation Manual Direct Vent Tankless Water HeaterANS Z21.10.3 Table of Contents Consumer Safety InformationError Codes Technical DataSpecifications RC80HPiRC98HPi RC98HPeConsumer Safety Information Safety DefinitionsSafety Behavior and Practices Safety Features DANGERFeatures Available on Temperature Controllers Description of OperationOperating Instructions MC-502RC-1US-S* Wireless In Use Indicator Temperature Display TemperaturePriority Indicator Priority Button ON/OFF Button IndicatorIn Use Indicator Temperature Display Clock Call Priority Button and Indicator ON/OFF ButtonBC-100V-1US MC-100V-1USHow to Set the Temperature Temperature Controller SettingsRC80HPi RC80HPeSetting the Sound Volume Voice Prompt Temperature Controller SettingsRe-settingthe Maximum Temperature MCC-91Temperature ControllerUsing the Water Smart / Bath Fill Function Setting the Water VolumeOverview Setting Controller to Mute Setting the ClockUsing the Water Smart / Bath Fill Function Filling the TubMaintenance CleaningVent System MotorsError Codes FaultCode RemedyManual - Rinnai Condensing Water Heaters codeTrouble Shooting for Common Issues Accessing Operating InformationWater Quality I don’t have any hot water when I open the tapFlushing the Heat Exchanger Error Code LC or H2 H1 Circulating PumpWater Heater Installation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterElectrical Connection Gas PipingGeneral Instructions Pipe Sizing Procedure - Example Gas PipingGas Input of Rinnai water heater BTU / HR Cubic Feet per Hour CFH =Water Piping General InstructionsPressure Relief Valve Freeze ProtectionFreeze Protection Piping Recommended Piping for Basic Installation Condensate drain lineCondensate drain Recommended Piping for Circulation Systems For this applicationOptional Piping for Circulation Systems 3 years on heat exchanger 3 year on partsManual - Rinnai Condensing Water Heaters For this applicationVenting Instructions Intake / Exhaust GuidelinesCondensate Maximum Vent Length Vent ProductsREU-KA2530FFUD-US RC98HPiFlue Terminal Clearances ANS Z21.10.3 CSA AREA WHERE B TERMINAL IS NOT PERMITTTEDCanadian Installations US InstallationsINSIDE CORNER Additional Clearances RC80HPe, RC98HPe IN S ID E C O R N E RFlue Installation RC80HPi, RC98HPi Dispose of condensate per local codesDispose of condensate per local codes Securing Manual - Rinnai Condensing Water HeatersHigh Altitude Installations Connecting Multiple Water HeatersGuidelines Temperature Controller Installation ConfigurationsLocation Cable Lengths and Sizesecuring screw wiring hole securing screw Temperature Controller InstallationMounting the Controller Outline of RemoteFOR YOUR SAFETY READ BEFORE OPERATING Operating InstructionsOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCETechnical Data Pressure Drop CurveOutlet Flow Data Pressure Loss psiSpace Heating Temperature SettingReplacement PumpsDimensions RC80HPi, RC98HPiRC80HPi, RC80HPe RC80HPe, RC98HPeLadder Diagram TWIN THERMISTORWarranty Information Limited WarrantyConsumer Support Limited Warranty Continued How do I get service?What is not covered? What will Rinnai do?Manuel dinstallation et dutilisation ou lappel 1-866-RINNAI1Instructions dutilisation Comportements et pratiques de sécuritéRéglage de température Chaud BrûlureOptions de température sans contrôleur à distance RC80HPiRC80HPe RC98HPiEntretien CORRECT VUE DE FACEINCORRECT VUE DE FACE NettoyageInstructions générales Installation InstructionsNutilisez pas de matériaux de substitution Manuel - Rinnai Condensing Water HeatersÉcartements par rapport à lappareil Fixation du chauffe-eauRC80HPe, RC98HPe Installations à haute altitude Tuyauterie de gazInstructions générales Tuyauterie deau Qualité de leauInstructions générales Soupape de sûretéTuyauterie recommandée pour installation de base LégendeCondensate Vidange condensat drain Instructions de ventilation Consignes pour aspiration/évacuationCondensat Longueur maximum de ventilation Produits de ventilation RC80HPi ................. REU-KA2530FFUDRC98HPi ................. REU-KA3237FFUD Rinnai/UbbinkInstallations au Canada Installations aux USAENTÉE DALIMENTATION EN AIR TERMINAISON DE VENTILATIONVis de fixation Instructions dutilisation INSTRUCTIONS DE MISE EN MARCHECOMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL FERMÉECLOSE OUVERTOPENDiagramme en escalier CONTACT DEFUSIBLE 7 A DÉTECTION DE GELSupport à la clientèle Informations sur la garantieGarantie limitée Garantie limitée Manuel - Rinnai Condensing Water HeatersQue fait Rinnai pour exercer la garantie ? Quest-cequi nest pas couvert ?Rinnai’s other fine products U290-665X01