Rinnai RC98HPE, RC80HPI Gas Piping, Pipe Sizing Procedure - Example, Cubic Feet per Hour CFH =

Page 20
Pipe Sizing Procedure - Example

Gas Piping

Pipe Sizing Procedure - Example

The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas type, the pressure drop in the system, the gas pressure supplied, and gas line type. For gas pipe sizing in the United States, refer to the National Fuel Gas Code, NFPA 54. For Canadian gas pipe sizing, refer to the Natural Gas and Propane Installation Code CAN/CSA B149.1. The below information is provided as an example. The appropriate table from the applicable code must be used.

1.Determine the cubic feet per hour of gas required by dividing the gas input (on the rating plate) by the heating value of the gas (available from the local gas company). The gas input needs to include all gas products at the location and the maximum BTU usage at full load when all gas products are in use.

Gas Input of Rinnai water heater (BTU / HR)

Cubic Feet per Hour (CFH) =

Heating Value of Gas (BTU / FT 3 )

2.Use the table for your gas type to find the pipe size required for your cubic feet per hour of gas and your pipe length.

Example: The heating value of propane gas for your location is 2516 BTU / FT 3. The gas input of the R94LSi is 190,000 BTU/HR. Additional appliances at the location require 75,000 BTU/HR.

Therefore the cubic feet per hour = (190,000+75,000) / 2516 = 105.3 FT 3/ HR.

If the pipe length is 100 ft then the 3/4 inch pipe size capable of supplying 197 FT 3/ HR of propane gas will be adequate.

Length

 

Pipe Size (inches)

 

3/4

1

1 1/4

1 1/2

 

10

273

514

1060

1580

20

188

353

726

1090

30

151

284

583

873

40

129

243

499

747

50

114

215

442

662

60

104

195

400

600

70

95

179

368

552

80

89

167

343

514

 

 

 

 

 

90

83

157

322

482

 

 

 

 

 

100

79

148

304

455

 

 

 

 

 

125

70

131

269

403

 

 

 

 

 

150

63

119

244

366

 

 

 

 

 

175

58

109

224

336

 

 

 

 

 

200

54

102

209

313

 

 

 

 

 

Length

 

Pipe Size (inches)

 

 

 

 

 

1/2

3/4

1

1 1/4

 

 

 

 

 

 

10

291

608

1150

2350

 

 

 

 

 

20

200

418

787

1620

 

 

 

 

 

30

160

336

632

1300

 

 

 

 

 

40

137

287

541

1110

 

 

 

 

 

50

122

255

480

985

 

 

 

 

 

60

110

231

434

892

 

 

 

 

 

80

101

212

400

821

 

 

 

 

 

100

94

197

372

763

 

 

 

 

 

125

89

185

349

716

 

 

 

 

 

150

84

175

330

677

 

 

 

 

 

175

74

155

292

600

 

 

 

 

 

200

67

140

265

543

 

 

 

 

 

20

Manual - Rinnai Condensing Water Heaters

Image 20
Contents ANS Z21.10.3 Operation and Installation ManualDirect Vent Tankless Water Heater Table of Contents Consumer Safety InformationError Codes Technical DataSpecifications RC80HPiRC98HPi RC98HPeConsumer Safety Information Safety DefinitionsSafety Behavior and Practices Safety Features DANGEROperating Instructions Features Available on Temperature ControllersDescription of Operation MC-502RC-1US-S* Wireless In Use Indicator Temperature Display TemperaturePriority Indicator Priority Button ON/OFF Button IndicatorIn Use Indicator Temperature Display Clock Call Priority Button and Indicator ON/OFF ButtonBC-100V-1US MC-100V-1USHow to Set the Temperature Temperature Controller SettingsRC80HPi RC80HPeSetting the Sound Volume Voice Prompt Temperature Controller SettingsRe-settingthe Maximum Temperature MCC-91Temperature ControllerOverview Using the Water Smart / Bath Fill FunctionSetting the Water Volume Setting Controller to Mute Setting the ClockUsing the Water Smart / Bath Fill Function Filling the TubMaintenance CleaningVent System MotorsError Codes FaultCode RemedyManual - Rinnai Condensing Water Heaters codeTrouble Shooting for Common Issues Accessing Operating InformationWater Quality I don’t have any hot water when I open the tapWater Heater Flushing the Heat Exchanger Error Code LC orH2 H1 Circulating Pump Installation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGeneral Instructions Electrical ConnectionGas Piping Pipe Sizing Procedure - Example Gas PipingGas Input of Rinnai water heater BTU / HR Cubic Feet per Hour CFH =Water Piping General InstructionsPressure Relief Valve Freeze ProtectionFreeze Protection Piping Condensate drain Recommended Piping for Basic InstallationCondensate drain line Recommended Piping for Circulation Systems For this applicationOptional Piping for Circulation Systems 3 years on heat exchanger 3 year on partsManual - Rinnai Condensing Water Heaters For this applicationCondensate Venting InstructionsIntake / Exhaust Guidelines Maximum Vent Length Vent ProductsREU-KA2530FFUD-US RC98HPiFlue Terminal Clearances ANS Z21.10.3 CSA AREA WHERE B TERMINAL IS NOT PERMITTTEDCanadian Installations US InstallationsINSIDE CORNER Additional Clearances RC80HPe, RC98HPe IN S ID E C O R N E RFlue Installation RC80HPi, RC98HPi Dispose of condensate per local codesDispose of condensate per local codes Securing Manual - Rinnai Condensing Water HeatersGuidelines High Altitude InstallationsConnecting Multiple Water Heaters Temperature Controller Installation ConfigurationsLocation Cable Lengths and Sizesecuring screw wiring hole securing screw Temperature Controller InstallationMounting the Controller Outline of RemoteFOR YOUR SAFETY READ BEFORE OPERATING Operating InstructionsOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCETechnical Data Pressure Drop CurveOutlet Flow Data Pressure Loss psiSpace Heating Temperature SettingReplacement PumpsDimensions RC80HPi, RC98HPiRC80HPi, RC80HPe RC80HPe, RC98HPeLadder Diagram TWIN THERMISTORConsumer Support Warranty InformationLimited Warranty Limited Warranty Continued How do I get service?What is not covered? What will Rinnai do?Manuel dinstallation et dutilisation ou lappel 1-866-RINNAI1Instructions dutilisation Comportements et pratiques de sécuritéRéglage de température Chaud BrûlureOptions de température sans contrôleur à distance RC80HPiRC80HPe RC98HPiEntretien CORRECT VUE DE FACEINCORRECT VUE DE FACE NettoyageInstructions générales Installation InstructionsNutilisez pas de matériaux de substitution Manuel - Rinnai Condensing Water HeatersRC80HPe, RC98HPe Écartements par rapport à lappareilFixation du chauffe-eau Instructions générales Installations à haute altitudeTuyauterie de gaz Tuyauterie deau Qualité de leauInstructions générales Soupape de sûretéCondensate Vidange condensat drain Tuyauterie recommandée pour installation de baseLégende Condensat Instructions de ventilationConsignes pour aspiration/évacuation Longueur maximum de ventilation Produits de ventilation RC80HPi ................. REU-KA2530FFUDRC98HPi ................. REU-KA3237FFUD Rinnai/UbbinkInstallations au Canada Installations aux USAENTÉE DALIMENTATION EN AIR TERMINAISON DE VENTILATIONVis de fixation Instructions dutilisation INSTRUCTIONS DE MISE EN MARCHECOMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL FERMÉECLOSE OUVERTOPENDiagramme en escalier CONTACT DEFUSIBLE 7 A DÉTECTION DE GELGarantie limitée Support à la clientèleInformations sur la garantie Garantie limitée Manuel - Rinnai Condensing Water HeatersQue fait Rinnai pour exercer la garantie ? Quest-cequi nest pas couvert ?Rinnai’s other fine products U290-665X01