Rinnai RC80HPE, RC98HPE, RC80HPI, RC98HPI Manual - Rinnai Condensing Water Heaters, code

Page 14

Code

Fault

Remedy

 

 

 

16

Over Temperature

Check for restrictions in air flow around unit and vent terminal.

 

Warning

Check for low water flow in a circulating system causing short-cycling.

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

Check for clogged heat exchanger.

 

 

 

25

Condensate Trap Error

Condensate container is full.

 

 

Check condensate drain for blockage.

 

 

Replace condensate trap.

31

Burner Sensor Error

Measure resistance of sensor.

 

 

Replace sensor.

32

Outgoing Water

Check sensor wiring for damage.

 

Temperature Sensor

Measure resistance of sensor.

 

Fault

Clean sensor of scale build-up.

 

 

Replace sensor.

33

Heat Exchanger

Check sensor wiring for damage.

 

Outgoing Temperature

Measure resistance of sensor.

 

Sensor Fault

Clean sensor of scale build-up.

 

 

Replace sensor.

52

Modulating Solenoid

Check modulating gas solenoid valve wiring harness for loose or damaged terminals.

 

Valve Signal Abnormal

Measure resistance of valve coil.

61

Combustion Fan

Ensure fan will turn freely.

 

Failure

Check wiring harness to motor for damaged and/or loose connections.

 

 

Measure resistance of motor winding.

65

Water Flow Control

The water flow control valve has failed to close during the bath fill function. Immediately turn off

 

Fault

the water and discontinue the bath fill function. Contact a state qualified or licensed contractor to

 

 

service the appliance.

71

SV0, SV1, SV2, SV3

Replace the PC board.

 

and SV4 Solenoid

 

 

Valve Circuit Fault

 

72

Flame Sensing Device

Ensure flame rod is touching flame when unit fires.

 

Fault

Check all wiring to flame rod for damage.

 

 

Remove flame rod and check for carbon build-up; clean with sand paper.

 

 

Check inside burner chamber for any foreign material blocking flame at flame rod.

 

 

Measure micro amp output of sensor circuit with flame present.

 

 

Replace flame rod.

 

 

 

73

Burner Sensor Circuit

Check sensor wiring and PC board for damage.

 

Error

Replace sensor.

 

 

 

LC

Scale Build-up in Heat

Flush heat exchanger. Refer to instructions in manual.

 

Exchanger (when

Replace heat exchanger.

 

checking maintenance

NOTE: The LC code is the only error code that will allow the unit to keep running. The display will

 

code history, “00” is

alternate between the LC code and the temperature setting. The controller will continue to beep.

 

The LC code will reset if power is turned off and then on.

 

substituted for “LC”)

 

 

No

Nothing happens when

Clean inlet water supply filter.

code

water flow is activated.

On new installations ensure hot and cold water lines are not reversed.

 

 

Check for bleed over. Isolate unit from building by turning off hot water line to building. Isolate the

 

 

circulating system if present. Open your pressure relief valve; if water is flowing, there is bleed

 

 

over in your plumbing.

 

 

Ensure you have at least the minimum flow rate required to fire unit.

 

 

Ensure turbine spins freely.

 

 

Measure the resistance of the water flow control sensor.

 

 

Check for DC shorts at components.

 

 

 

14

Manual - Rinnai Condensing Water Heaters

Image 14
Contents ANS Z21.10.3 Operation and Installation ManualDirect Vent Tankless Water Heater Error Codes Table of ContentsConsumer Safety Information Technical DataRC98HPi SpecificationsRC80HPi RC98HPeSafety Behavior and Practices Safety Features Consumer Safety InformationSafety Definitions DANGEROperating Instructions Features Available on Temperature ControllersDescription of Operation Priority Indicator Priority Button ON/OFF Button MC-502RC-1US-S* WirelessIn Use Indicator Temperature Display Temperature IndicatorBC-100V-1US In Use Indicator Temperature Display Clock CallPriority Button and Indicator ON/OFF Button MC-100V-1USRC80HPi How to Set the TemperatureTemperature Controller Settings RC80HPeRe-settingthe Maximum Temperature Setting the Sound Volume Voice PromptTemperature Controller Settings MCC-91Temperature ControllerOverview Using the Water Smart / Bath Fill FunctionSetting the Water Volume Using the Water Smart / Bath Fill Function Setting Controller to MuteSetting the Clock Filling the TubVent System MaintenanceCleaning MotorsCode Error CodesFault RemedyManual - Rinnai Condensing Water Heaters codeWater Quality Trouble Shooting for Common IssuesAccessing Operating Information I don’t have any hot water when I open the tapWater Heater Flushing the Heat Exchanger Error Code LC orH2 H1 Circulating Pump Installation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGeneral Instructions Electrical ConnectionGas Piping Gas Input of Rinnai water heater BTU / HR Pipe Sizing Procedure - ExampleGas Piping Cubic Feet per Hour CFH =Pressure Relief Valve Water PipingGeneral Instructions Freeze ProtectionFreeze Protection Piping Condensate drain Recommended Piping for Basic InstallationCondensate drain line Recommended Piping for Circulation Systems For this applicationManual - Rinnai Condensing Water Heaters Optional Piping for Circulation Systems3 years on heat exchanger 3 year on parts For this applicationCondensate Venting InstructionsIntake / Exhaust Guidelines REU-KA2530FFUD-US Maximum Vent LengthVent Products RC98HPiCanadian Installations Flue Terminal Clearances ANS Z21.10.3 CSAAREA WHERE B TERMINAL IS NOT PERMITTTED US InstallationsINSIDE CORNER Additional Clearances RC80HPe, RC98HPe IN S ID E C O R N E RDispose of condensate per local codes Securing Flue Installation RC80HPi, RC98HPiDispose of condensate per local codes Manual - Rinnai Condensing Water HeatersGuidelines High Altitude InstallationsConnecting Multiple Water Heaters Location Temperature Controller InstallationConfigurations Cable Lengths and SizeMounting the Controller securing screw wiring hole securing screwTemperature Controller Installation Outline of RemoteOPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATINGOperating Instructions TO TURN OFF GAS TO APPLIANCEOutlet Flow Data Technical DataPressure Drop Curve Pressure Loss psiReplacement Space HeatingTemperature Setting PumpsRC80HPi, RC80HPe DimensionsRC80HPi, RC98HPi RC80HPe, RC98HPeLadder Diagram TWIN THERMISTORConsumer Support Warranty InformationLimited Warranty What is not covered? Limited Warranty ContinuedHow do I get service? What will Rinnai do?Manuel dinstallation et dutilisation ou lappel 1-866-RINNAI1Réglage de température Instructions dutilisationComportements et pratiques de sécurité Chaud BrûlureRC80HPe Options de température sans contrôleur à distanceRC80HPi RC98HPiINCORRECT VUE DE FACE EntretienCORRECT VUE DE FACE NettoyageNutilisez pas de matériaux de substitution Instructions généralesInstallation Instructions Manuel - Rinnai Condensing Water HeatersRC80HPe, RC98HPe Écartements par rapport à lappareilFixation du chauffe-eau Instructions générales Installations à haute altitudeTuyauterie de gaz Instructions générales Tuyauterie deauQualité de leau Soupape de sûretéCondensate Vidange condensat drain Tuyauterie recommandée pour installation de baseLégende Condensat Instructions de ventilationConsignes pour aspiration/évacuation Longueur maximum de ventilation RC98HPi ................. REU-KA3237FFUD Produits de ventilationRC80HPi ................. REU-KA2530FFUD Rinnai/UbbinkENTÉE DALIMENTATION EN AIR TERMINAISON DE Installations au CanadaInstallations aux USA VENTILATIONVis de fixation COMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL Instructions dutilisationINSTRUCTIONS DE MISE EN MARCHE FERMÉECLOSE OUVERTOPENFUSIBLE 7 A Diagramme en escalierCONTACT DE DÉTECTION DE GELGarantie limitée Support à la clientèleInformations sur la garantie Que fait Rinnai pour exercer la garantie ? Garantie limitéeManuel - Rinnai Condensing Water Heaters Quest-cequi nest pas couvert ?Rinnai’s other fine products U290-665X01