Code | Fault | Remedy |
|
|
|
16 | Over Temperature | Check for restrictions in air flow around unit and vent terminal. |
| Warning | Check for low water flow in a circulating system causing |
|
| Check for foreign materials in combustion chamber and/or exhaust piping. |
|
| Check for clogged heat exchanger. |
|
|
|
25 | Condensate Trap Error | Condensate container is full. |
|
| Check condensate drain for blockage. |
|
| Replace condensate trap. |
31 | Burner Sensor Error | Measure resistance of sensor. |
|
| Replace sensor. |
32 | Outgoing Water | Check sensor wiring for damage. |
| Temperature Sensor | Measure resistance of sensor. |
| Fault | Clean sensor of scale |
|
| Replace sensor. |
33 | Heat Exchanger | Check sensor wiring for damage. |
| Outgoing Temperature | Measure resistance of sensor. |
| Sensor Fault | Clean sensor of scale |
|
| Replace sensor. |
52 | Modulating Solenoid | Check modulating gas solenoid valve wiring harness for loose or damaged terminals. |
| Valve Signal Abnormal | Measure resistance of valve coil. |
61 | Combustion Fan | Ensure fan will turn freely. |
| Failure | Check wiring harness to motor for damaged and/or loose connections. |
|
| Measure resistance of motor winding. |
65 | Water Flow Control | The water flow control valve has failed to close during the bath fill function. Immediately turn off |
| Fault | the water and discontinue the bath fill function. Contact a state qualified or licensed contractor to |
|
| service the appliance. |
71 | SV0, SV1, SV2, SV3 | Replace the PC board. |
| and SV4 Solenoid |
|
| Valve Circuit Fault |
|
72 | Flame Sensing Device | Ensure flame rod is touching flame when unit fires. |
| Fault | Check all wiring to flame rod for damage. |
|
| Remove flame rod and check for carbon |
|
| Check inside burner chamber for any foreign material blocking flame at flame rod. |
|
| Measure micro amp output of sensor circuit with flame present. |
|
| Replace flame rod. |
|
|
|
73 | Burner Sensor Circuit | Check sensor wiring and PC board for damage. |
| Error | Replace sensor. |
|
|
|
LC | Scale | Flush heat exchanger. Refer to instructions in manual. |
| Exchanger (when | Replace heat exchanger. |
| checking maintenance | NOTE: The LC code is the only error code that will allow the unit to keep running. The display will |
| code history, “00” is | alternate between the LC code and the temperature setting. The controller will continue to beep. |
| The LC code will reset if power is turned off and then on. | |
| substituted for “LC”) | |
|
| |
No | Nothing happens when | Clean inlet water supply filter. |
code | water flow is activated. | On new installations ensure hot and cold water lines are not reversed. |
|
| Check for bleed over. Isolate unit from building by turning off hot water line to building. Isolate the |
|
| circulating system if present. Open your pressure relief valve; if water is flowing, there is bleed |
|
| over in your plumbing. |
|
| Ensure you have at least the minimum flow rate required to fire unit. |
|
| Ensure turbine spins freely. |
|
| Measure the resistance of the water flow control sensor. |
|
| Check for DC shorts at components. |
|
|
|
14 | Manual - Rinnai Condensing Water Heaters |