Rinnai 24e user manual Temperature Controls General

Page 15

TEMPERATURE CONTROLS - GENERAL

When deciding on the best position for the temperature controls, the following points should be taken into account.

Fit the controls out of reach of children (suggested height from the floor 1.5m.)

Avoid positions where the controllers will become hot. Do not fit them near stoves or ovens, or above radiators or heaters.

If possible, avoid exposure to direct sunlight or positions where bright lights will make the digital display difficult to read.

Position away from areas where the controller will be prone to splashing by cooking products such as oils and fats.

The temperature controllers are water resistant, however they should be positioned away from areas where direct or persistent splashing could occur.

Refer to the I.E.E electrical wiring regulations current edition for location requirements in shower and bath areas.

The cables to the temperature controller carry only 12VDC (extra low voltage.)

When using more than one temperature controller the signal cable should be run in parallel. That is, from controller to controller to heater, or from each controller to the heater. Do not wire the controllers in series.

The installation in every application will vary, therefore the temperature controller cable has been provided so that you may cut the length accordingly and fit the spade connectors, ensuring a good connection.

Cables are simply ‘piggy-backed’ at the water heater or at the primary temperature controller. Polarity is not important when connecting the cables, either colour wire can be connected to either terminal at both the heater or primary temperature controller. If more cable is needed any cable with similar specification to the cable supplied with the controller can be used. Maximum length is 50 metres.

15

Image 15
Contents Infinity 24e Definition of Commercial Use Rinnai UK WarrantyStandard Use Definition of Standard UseContents Unpacking Rinnai Water Heater Important Information Installation InstructionsAppliance Location Installation Instructions PositioningGas Connection Installation Instructions ConnectionsWater Supply Water ConnectionFlue Requirements Positioning Dimensions Infinity 24e Technical DetailsOperating Noise Level is Very LOW Features and BenefitsImportant Information OFF Turn On by opening the hot water tap Operation Without RemotesTemperature Controls General Universal Temperature Controller Temperature Controls InstallationConnecting One or Two Controllers Connecting Three ControllersConnecting Four Controllers Temperature Controls Temperature Controls Operating Adjusting Temperature Using 1 Universal Temperature ControllerBathroom temperatures should be no more than 500C Using 2 or more Universal Temperature ControllersSwitching the system on Using hot waterStep Using 4 Universal Temperature ControllersUsing High Temperature Display Controllers To turn off your hot water system Additional safety featuresTemperature Controls Information Testing GAS Pressure Setting Mbar Propane 1.7 mbarPropane Mbar DIP Switch Setting Dip Switch Positions ExplainedDip Switches Explained Temperatures Remotes Connected Code Fault Remedy Displayed Error MessagesInstallations with circulation pumps With temperature controller fittedWithout temperature controller fitted Standard system Restarting the Rinnai Water HeaterWiring Diagram Diagnostic Points Electrical Supply…………………………….…………..……………….230V AC 50Hz 1ph SpecificationPage Service Contact Commissioning Check List