Stovax PR0919 manual Site Requirements/Installation, Appliance Location, Safety Precautions, Edge

Page 14

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS/INSTALLATION

5.APPLIANCE LOCATION

5.1Please note this appliance has been specifically designed for stud work applications. There are two methods of installation, see Installation Instructions 3.2 Frame, 3.3

Edge

5.2This appliance must stand on a non-combustible hearth/ platform that is at least 12mm thick.

NOTE: It is recommended you construct the back panel of the fireplace from natural materials cut into three or more sections to prevent cracking. Resin-based materials may not be suitable. This appliance is an effective heat producer and attention must be paid to the construction and finish of the fireplace.

5.3A combustible shelf must be:

maximum 150mm in depth

minimum, 400mm high above the fire

A combustible side wall must be a minimum of 150mm from the appliance.

5.3This appliance can be installed with an up and out flue

(vertical wall - horizontal flue) or with a vertical flue with roof termination (see flue options, Section 2 Site Requirements).

IMPORTANT: REFER TO DATA BADGE AND TECHNICAL SPECIFICATION AT THE FRONT OF THE MANUAL TO ENSURE THE APPLIANCE IS CORRECTLY ADJUSTED FOR THE GAS TYPE AND CATEGORY APPLIED IN THE COUNTRY OF USE.

FOR DETAILS OF CHANGING BETWEEN GAS TYPES REFER TO SECTION 10, SERVICING, ‘REPLACING PARTS’.

1.SAFETY PRECAUTIONS

1.1For your own and other’s safety, you must install this stove according to local and national codes of practice. Failure to install the stove correctly could lead to prosecution:

Read these instructions before installing and using this stove.

1.2These instructions must be left intact with the user.

1.3Do not attempt to burn rubbish on this appliance.

1.4Keep all plastic bags away from young children.

1.5Do not place any object on or near to the appliance and allow adequate clearance above the appliance.

IF THE APPLIANCE IS EXTINGUISHED OR GOES OUT IN USE, WAIT 3 MINUTES BEFORE ATTEMPTING TO RELIGHT THE APPLIANCE.

2. installation of the appliance

THERE IS AN OPTIONAL DUCT KIT, CODE No. 8572

WHICH CAN BE FITTED AT THE SAME TIME AS THE APPLIANCE INSTALLATION.

2.1Remove the appliance from the carton and discard all unnecessary packaging. Ensure no components are thrown away when unpacking.

2.2To open the glass door, use the allen key provided:

• Release the two window locks

The lock needs to be moved from shut to open towards the outer edge of the glass door, Diagram 1

1

AR1860

2.3The gas supply enters the fire through a silicon panel on the floor under the access panel, Diagram 2:

• Slit with a sharp knife before bringing through the supply pipe, Diagram 3

14

Image 14
Contents Studio 8701BFCHEC Covering the Following ModelStudio 1 Balanced flue Studio 2 Balanced flue P8701BFCHECFail APPLIANCE COMMISSIONING CHECKLISTFLUE CHECK GAS CHECKGeneral MAN ModeUser Instructions Lighting the StudioTouch PAD Control Emergency Shut OFF Cleaning the StudioChanging the Studio Batteries All modelsFire will not Light Arrangement of Fuel BEDHOT SURFACES Covering the Following Models Installation InstructionsTechnical Specification Studio 1 BF Studio 2 BFStudio 1BF Studio 2BF Packing ChecklistQty Description Fixing Kit containing 850 1050 524 740 940 414 Steel Frame Dimensions Studio836 1036 510 740 940 414 12.5 SITE REQUIREMENTS Flue and Chimney RequirementsTOP Flue UP & OUT KIT Flue Options Studio 1 BFStudio 2 BF TOP Flue UP & OUT with Additional BendExtra Flue Lengths TOP Flue Vertical KIT 8524/8524ANTOP Flue Vertical Offset KIT 8530/8530AN GAS SupplyInstallation of the appliance SITE REQUIREMENTS/INSTALLATIONSafety Precautions Appliance LocationStud Work Installation Method 1 Frame InstallationStud Work Installation Wall plate Flue Assembly Stud Work Installation Method 2 EdgeMethod 1 Frame only Assembling the Appliance Add 10 mm to the outlet endThermostatic Remote Control Lighting the StudioInstallation Instructions Commissioning CommissioningServicing Instructions Servicing / Fault Finding ChartsSymptom Cause Remedy Servicing RequirementsIgnition Functional Check Flame Failure Functional CheckGeneral Replacing PartsWindow Frame Assembly Decorative FrameMaIN Burner Glass WindowBlack Enamelled Panels MaIN Control Assembly Ensure no stone pebbles fall into the pilot areaPilot Unit Assembly Ignition LeadControl BOX Magnetic safety valveGAS Valve Primary Aeration Plate Pressure and Leak Testing the ApplianceMain injector Changing between Gas TypesComponent ShoRt Spares ListStudio 1 BF Studio 2 BF Service Records Member of the Stovax Group