INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
1. Flue and Chimney Requirements
Note: This appliance must only be installed with the flue supplied.
You must adhere to the following:
1.1The flue must be sited in accordance with BS5440: Part 1 (latest edition). See Diagram 1.
1.2Fit a guard to protect people from any terminal less than 2 metres above any access such as level ground, a balcony or above a flat roof.
1.3All vertical and horizontal flues must be securely fixed and fire precautions followed in accordance with local and national codes of practice.
1.4A restrictor may be required. Refer to Technical Specifications on page 12.
1.5Two types of flue terminals are available, horizontal and vertical. To measure for a horizontal terminal:
•Decide on the terminal position
•Measure the height from the top of the appliance to the centre of the required outlet.
For minimum and maximum flue dimensions see Diagram 1A / 1B.
•Allow enough room either above or to the side of the appliance to assemble the flue on top
•Assemble a horizontal flue in the following order:
-Vertical section
-90° elbow
-Horizontal plus terminal
•Support the opening of a masonry installation with a lintel.
1.7Only the horizontal terminal section can be reduced in size.
1
UK Dimensions
11