When “Status Tracking” is enabled (this is the default setting), OmniPro II keeps track of the exact status of each unit even when a lighting scene is initiated by the Room Controller. Room Controllers also keep track of when individual switches in a room are turned on and off. When all of the lighting loads in a room are turned off, the “Off” indicator is illuminated. If any of the lighting loads in a room are turned on at an HAI UPB™ Wall Switch or Dimmer, the “On” indicator will illuminate and the “Off” indicator is turned off. Likewise, if the “On” indicator or one of the scene indicators is illuminated, and then all of the lighting loads are turned off at HAI UPB™ Wall Switches, the “Off” indicator will illuminate and any others are turned off.

About House Controllers

The HAI UPB™ 8-Button House Controller allows for controlling all 8 rooms of lighting where HAI UPB™ Wall Switches, Dimmers, and Modules have been installed. It can also be configured as a general purpose 8 button keypad controller used to trigger 8 different macro programs in the OmniPro II controller or to toggle between two different actions (i.e. turn lighting load on...turn lighting load off) each time a pushbutton is pressed.

When used to control rooms of lighting in the HLC structure, each button on the House Controller is used to toggle all of the lights in the respective room on and off. When the room is turned on, the LED indicator behind the respective button is illuminated and all of the lights in the room are turned on. When the room is turned off, the LED indicator behind the respective button is turned off and all of the lights in the room are turned off. If a lighting load in the respective room is turned on, the LED indicator behind the button is illuminated. When all lighting loads in the respective room are turned off, the LED indicator behind the button is turned off.

When used to control rooms of lighting in the HLC structure, each House Controller controls 8 consecutive rooms (i.e. Room 1-8, Room 9-16, Room 17-24, and Room 25-31). To configure a House Controller to control a group of 8 rooms, it must be set to the last unit number in one of the respective rooms. For example, a House Controller set to Unit 8, 16, 24, 32, 40, 48, 56, or 64 is configured to control rooms 1-8. This allows you to have up to 8 House Controllers throughout the house that control rooms 1-8.

Within the HLC structure, House Controllers can also be configured as a general purpose 8 button keypad controller that is used to trigger 8 different macro programs in the OmniPro II. When configuring a House Controller as a general purpose 8 button keypad controller, it must be set to a unit number between the first and last unit number in a room (i.e. 2-7, 10-15, 18-23, 26-31, 34-39, etc.). When configured as a general purpose 8 button keypad controller, programs must be created in the OmniPro II controller for the LED indicator behind each button to function.

About CentraLite

CentraLite is a centralized lighting control system that uses hardwired lighting control technology to control lighting loads, fans, and mechanical low voltage relays.

CentraLite lighting scenes are used to control groups of lights which are preset to turn on to various levels of dimming.

When set to CentraLite, the OmniPro II controller can:

¾Send commands (on, off, and level) to individual loads and relays

¾Receive status (on and off) from individual loads and relays

¾Execute scene commands (on and off) to control of up to 255 CentraLite lighting scenes

¾Receive commands when buttons are pressed on a CentraLite keypad (up to 127)

About Lutron RadioRA

Lutron RadioRA uses wireless communication technology to control lighting. Each Switch or Dimmer controls one Zone, or area, of lighting in a RadioRA system. Accessory Switches and Dimmers are used to control the lights locally from up to 9 additional locations. Master controls provide control and monitoring for all the lights in a RadioRA system.

Phantom Buttons are “virtual” buttons in the RS232 Interface. Though there are no physical buttons that represent these Phantom Buttons, they work very similarly to buttons on RadioRA Master Controls. Phantom Buttons are intended to give the RS232 Interface control over multiple RadioRA Switches and Dimmers with one command. To control more than one device at one time, Phantom Buttons are recommended.

Page 18

Image 26
Contents Document Number 20R00-2Rev. January HOME AUTOMATION, INCControl & Security System Copyright 2001-2006Home Automation, Inc All Rights ReservedSECURITY SYSTEM OPERATION INTRODUCTIONOVERALL DESCRIPTION ContentsCONTROL TELEPHONE CONTROL SETUP CANADIAN INDUSTRY CANADA NOTICE UNDERWRITERS LABORATORIES REQUIREMENTSFEDERAL COMMUNICATION COMMISSION NOTICE APPENDIX A - DIAL OUT PLANNERPage Page INTRODUCTIONUnderwriters Laboratories UL Listing 1- OFF OVERALL DESCRIPTIONConsole Operation 2- DAY6- UP ARROW Normal Top-LevelDisplayDisplay Menus 7- CONSOLE LEDTrouble Beeps Error BeepsMain Menu To silence the beeper, press the * keyAreas OmniPro II MaintenanceCancel Confirmation Beep0 = OFF SECURITY SYSTEM OPERATIONArming the Security System 1 = DAY3 = AWAY Using Shortcut Keys2 = NIGHT 4 = VACATIONBypassing Zones 9 = RESTOREQuick Arm Restoring ZonesBurglar Alarm Activated What To Do When You Come HomeWhat Happens When the Alarm is Activated #=GOTOEmergency Keys Fire Alarm ActivatedGas Alarm Activated PageAlarm Cancel Duress Code Entered or Duress Alarm ActivatedAlarm Reset Police EmergencyMaster Code Trouble IndicationsCodes PageArea Arming Panic SwitchesDuress Code Manager CodeGOTO Area PageTesting Your System PageAbout UPB Control CommandsCONTROL PageHAI Lighting Control HLC Format When set to UPB, the OmniPro II controller canRoom Controller LED Indicators About RoomsAbout House Controllers About CentraLiteAbout Lutron RadioRA PageHouse Codes About ALCAbout ALC Module TypesModule / Output Unit Numbers Unit NumbersOmniPro II Unit Numbers PageControlling Units Configuring Lighting Scenes in an HLC RoomScrolling Through Names Controlling a Room of HLC LightingControlling CentraLite Units StepOperation PagePage Controlling RadioRA UnitsControlling ALC or X-10Units Controlling Compose Units Ramp Command ALCScene Command Compose PageInternal Flags Timed CommandsStatus of a Unit PageAll Lights On Controlling OutputsAll On / Off All OffScene On Command Scene CommandsScene Set Command Leviton Scene ControlUPB Links Scene Off CommandSetting a Link Lighting Scenes Activating and Deactivating LinksENTER BUTTON Executing Phantom ButtonsExecuting CentraLite Scenes PHANTOM BUTTON 1 0=OFF 1=ONLeave for Work Button ButtonsTemperature Control Dinner for Two ButtonHAI RC-SeriesThermostats PageProgrammable Energy Saver Modules PESMs PageThe following control actions are allowed on PESMs PageIndoor and Outdoor Temperature Freeze AlarmsIMPORTANT NOTES PageOutdoor Temperature Temperature AlarmsHumidity Temperature Control of AppliancesStatus Configuring HLC DevicesConfiguring HLC Devices using an Omni Console PageStep Operation Setup Mode for HLC DevicesStep Operation Step OperationRING - RINGING ONHK - ON HOOKOFFHK - OFF HOOK DEAD - DEAD PHONE LINETHROUGH PagePage Event LogShow Events Play Memo Message MessagesRecord Memo Message Clear Text MessagesClear Message Show MessageLog Message Say MessageMSGNAME Send Message Pro-LinkSERIAL PORT ENTER MESSAGEIn-HousePhones TELEPHONE CONTROLTelephone Interface Remote PhonesMain Menu Phone Access Denied - Remote LockoutAlternate Method Page3 - Button 1 - Control2 - Security 4 - All6 - Status When an HAI Communicating Thermostat is enteredWhen a Programmable Energy Saver PESM is entered 7 - EventsPlaying and Recording a Message When the HAI Two-WayAudio Module is being used8 - Message Paging and ListeningPlaying and Recording the Address 9 - Good-ByePanic Button over the Phone # # # # # # PageVoice Dialer Emergency Dial-OutDigital Dialer How the OmniPro II Voice Dialer WorksEntering the Code PC AccessWhat You Hear - If Your OmniPro II Calls You PageOmniPro II Ethernet Connections Connecting to Network via PC AccessBuilt-InEthernet Port PagePage Local NetworkDynamic DNS i.e Local / Wide Area Networki.e PageAccess Areas SETUPSet Up Codes Authority LevelTIME Set Up TimeDuress Code Page2 = Show Programs Advanced Control Programming ACP1 = Add Programs PageMenu PagePage Edit Programs3 = Delete All Programs Page Edit Programs WhenTimes Programs Page Control Unit / Switch Press Event ButtonsButton and Event Programs OmniPro Corresponding Switch TableSwitch UPB 6-ButtonKeypadUPB Link Event Buttons Zone Event ButtonsAll On/Off Event Buttons PageMiscellaneous Event Buttons Alarm Event ButtonsX-10Event Buttons PagePage Switch Press Event Buttons CentraLiteMessage Event Buttons Pro-Link Page Edit Program CommandProgram Control Commands Program Button Commands Unit Toggle CommandProgram Security Commands Program All On / All Off CommandsProgram Temperature Commands Program Video CommandsProgram Message Commands Program Energy CostProgram Security Mode Conditions Edit Program ConditionProgram Control Conditions Program Zone ConditionsPage Program Time Clock ConditionsProgram Other Conditions Remote Commands Set Up DialTelephone Access Answer Outside CallDial Order Dial Out NumberDial Out Numbers PageExit Delay Set Up ArmingEntry Delay Audible Exit DelayEnable Auto Bypass Set up MiscellaneousEnable Quick Arm All On For AlarmHouse Codes 1-16Format Enable Freeze AlarmFlash For Alarm FORMATPage House Codes 1-16All OnTime Clocks Daylight Savings Latitude, Longitude, and Time ZoneZONE NAME PageNUMBER Controller IP AddressController Port Number DESCRIPTIONPage Set Up NamesEncryption Key SET UP VOICE 1=CTRL 2=ZONE 3=BTTN ↓ Set Up VoiceSet Up Address 4=CODE 5=TEMP 6=AREA 8=MSG↑Page UNDERWRITERS LABORATORIES REQUIREMENTSFIRE ESCAPE PLANNING FEDERAL COMMUNICATION COMMISSION NOTICE PagePage CANADIAN INDUSTRY CANADA NOTICEIF YOU HAVE TROUBLE WITH YOUR PHONES Page APPENDIX A - DIAL OUT PLANNEROmniPro II Voice Dial-OutPlanner INSTRUCTIONS TO CALLED PARTY PageCODE CHAR APPENDIX B - TEXT DESCRIPTION CHARACTER CODESCODE CHAR CODE CHARDESCRIPTION APPENDIX C - VOICE DESCRIPTION CODESCODE CODECODE CODEDESCRIPTION DESCRIPTIONCODE CODEDESCRIPTION DESCRIPTIONDESCRIPTION NOTES ON CUSTOM PHRASESCODE CODEPage NOTE TO INSTALLER HAI New Orleans, LA U S A