Home Automation OmniPro II Important Notes, Freeze Alarms, Indoor and Outdoor Temperature, Page

Page 42

Downstairs

2=HEAT

0=OFF

1=ON

Downstairs

#=STAT

3=COOL

9=TIME

ENTER TIME

 

MINUTES (1-99)

#=H/M/S

Downstairs

FOR 15M

0=OFF

1=ON

The current status of a temperature zone may be displayed by selecting ' # ' (STAT) key from the main temperature menu. The status display differs depending on the temperature zone type.

When you are finished, press the ' * ' key twice to return to the top-level display.

IMPORTANT NOTES:

¾There is a 3-minute minimum on and off time for PESMs designed to prevent short cycling your HVAC compressor. If the PESM has just turned the HVAC system on or off, it will wait 3 minutes before changing it, even though the display does change.

¾If you change the Heat or Cool setback temperature on the PESM, the system will insure that there is always at least four degrees Fahrenheit difference between the Heat and Cool temperatures by altering the other setback temperature as necessary.

¾PESMs are NOT affected by All On or All Off commands.

Freeze Alarms

Thermostats and PESMs can also be used to report potential freeze conditions before damage to pipes and appliances can occur. An alarm is activated when any Thermostat or PESM detects a temperature below 40 degrees. The alarm will not clear until the temperature exceeds 45 degrees.

When the alarm is initiated, the console beeper will be turned on and an alarm dial-out sequence will be initiated after the normal dial-out delay. Both voice and digital communicator dial-outs may be used. The voice dial-out will follow the Dial Order as specified in Set Up Dial. The digital communicator will report the Freeze Alarm Code to the Central Station.

The sounder is not activated for freeze alarms (this feature must be activated by your installer).

Indoor and Outdoor Temperature

The Model 31A00-1 Temperature Sensor is used for sensing temperatures from 0º F - 120º F and 31A00-7 Extended Range Temperature Sensor is used for sensing temperatures from -40º F - 120º F. It features a new, high accuracy temperature sensor that doesn’t need calibration.

The temperature can be used to activate programs for controlling temperatures indoors and in attics, garages, greenhouses, basements, wine cellars, coolers, and freezers. The temperature can be displayed on the console or spoken over the telephone. It can also report, log, alert, or generate an alarm if the temperature reaches freeze conditions or if the temperature goes above the high setpoint or drops below the low setpoint programmed in the system.

Outdoor temperature zones have a High and Low temperature associated with them that can be used for control purposes. An example of this is to program the system to turn on the bathroom heat if the outdoor temp goes below 45 degrees. High and Low temperatures are changed the same way as a PESM.

When a temperature sensor is selected from the list of temperature devices, you may set a “Low” and “High” setpoint for activating programs or alarms. Enter the desired temperature then press the ' # ' key.

Page 34

Image 42
Contents HOME AUTOMATION, INC Control & Security SystemDocument Number 20R00-2Rev. January Copyright 2001-2006Home Automation, Inc All Rights ReservedSECURITY SYSTEM OPERATION INTRODUCTIONOVERALL DESCRIPTION ContentsCONTROL TELEPHONE CONTROL SETUP CANADIAN INDUSTRY CANADA NOTICE UNDERWRITERS LABORATORIES REQUIREMENTSFEDERAL COMMUNICATION COMMISSION NOTICE APPENDIX A - DIAL OUT PLANNERPage INTRODUCTION Underwriters Laboratories UL ListingPage 1- OFF OVERALL DESCRIPTIONConsole Operation 2- DAY6- UP ARROW Normal Top-LevelDisplayDisplay Menus 7- CONSOLE LEDTrouble Beeps Error BeepsMain Menu To silence the beeper, press the * keyAreas OmniPro II MaintenanceCancel Confirmation Beep0 = OFF SECURITY SYSTEM OPERATIONArming the Security System 1 = DAY3 = AWAY Using Shortcut Keys2 = NIGHT 4 = VACATIONBypassing Zones 9 = RESTOREQuick Arm Restoring ZonesBurglar Alarm Activated What To Do When You Come HomeWhat Happens When the Alarm is Activated #=GOTOEmergency Keys Fire Alarm ActivatedGas Alarm Activated PageAlarm Cancel Duress Code Entered or Duress Alarm ActivatedAlarm Reset Police EmergencyMaster Code Trouble IndicationsCodes PageArea Arming Panic SwitchesDuress Code Manager CodeGOTO Area PageTesting Your System PageAbout UPB Control CommandsCONTROL PageHAI Lighting Control HLC Format When set to UPB, the OmniPro II controller canRoom Controller LED Indicators About RoomsAbout House Controllers About CentraLiteAbout Lutron RadioRA PageHouse Codes About ALCAbout ALC Module TypesModule / Output Unit Numbers Unit NumbersOmniPro II Unit Numbers PageControlling Units Configuring Lighting Scenes in an HLC RoomScrolling Through Names Controlling a Room of HLC LightingControlling CentraLite Units StepOperation PageControlling RadioRA Units Controlling ALC or X-10UnitsPage Controlling Compose Units Ramp Command ALCScene Command Compose PageInternal Flags Timed CommandsStatus of a Unit PageAll Lights On Controlling OutputsAll On / Off All OffScene On Command Scene CommandsScene Set Command Leviton Scene ControlUPB Links Scene Off CommandSetting a Link Lighting Scenes Activating and Deactivating LinksENTER BUTTON Executing Phantom ButtonsExecuting CentraLite Scenes PHANTOM BUTTON 1 0=OFF 1=ONLeave for Work Button ButtonsTemperature Control Dinner for Two ButtonHAI RC-SeriesThermostats PageProgrammable Energy Saver Modules PESMs PageThe following control actions are allowed on PESMs PageIndoor and Outdoor Temperature Freeze AlarmsIMPORTANT NOTES PageOutdoor Temperature Temperature AlarmsHumidity Temperature Control of AppliancesStatus Configuring HLC DevicesConfiguring HLC Devices using an Omni Console PageStep Operation Setup Mode for HLC DevicesStep Operation Step OperationRING - RINGING ONHK - ON HOOKOFFHK - OFF HOOK DEAD - DEAD PHONE LINETHROUGH PageEvent Log Show EventsPage Play Memo Message MessagesRecord Memo Message Clear Text MessagesClear Message Show MessageLog Message Say MessageMSGNAME Send Message Pro-LinkSERIAL PORT ENTER MESSAGEIn-HousePhones TELEPHONE CONTROLTelephone Interface Remote PhonesMain Menu Phone Access Denied - Remote LockoutAlternate Method Page3 - Button 1 - Control2 - Security 4 - All6 - Status When an HAI Communicating Thermostat is enteredWhen a Programmable Energy Saver PESM is entered 7 - EventsPlaying and Recording a Message When the HAI Two-WayAudio Module is being used8 - Message Paging and ListeningPlaying and Recording the Address 9 - Good-ByePanic Button over the Phone # # # # # # PageVoice Dialer Emergency Dial-OutDigital Dialer How the OmniPro II Voice Dialer WorksEntering the Code PC AccessWhat You Hear - If Your OmniPro II Calls You PageOmniPro II Ethernet Connections Connecting to Network via PC AccessBuilt-InEthernet Port PageLocal Network Dynamic DNSPage i.e Local / Wide Area Networki.e PageAccess Areas SETUPSet Up Codes Authority LevelTIME Set Up TimeDuress Code Page2 = Show Programs Advanced Control Programming ACP1 = Add Programs PageMenu PageEdit Programs 3 = Delete All ProgramsPage Edit Programs When Times ProgramsPage Control Unit / Switch Press Event Buttons Button and Event ProgramsPage OmniPro Corresponding Switch TableSwitch UPB 6-ButtonKeypadUPB Link Event Buttons Zone Event ButtonsAll On/Off Event Buttons PageMiscellaneous Event Buttons Alarm Event ButtonsX-10Event Buttons PageSwitch Press Event Buttons CentraLite Message Event Buttons Pro-LinkPage Edit Program Command Program Control CommandsPage Program Button Commands Unit Toggle CommandProgram Security Commands Program All On / All Off CommandsProgram Temperature Commands Program Video CommandsProgram Message Commands Program Energy CostProgram Security Mode Conditions Edit Program ConditionProgram Control Conditions Program Zone ConditionsProgram Time Clock Conditions Program Other ConditionsPage Remote Commands Set Up DialTelephone Access Answer Outside CallDial Order Dial Out NumberDial Out Numbers PageExit Delay Set Up ArmingEntry Delay Audible Exit DelayEnable Auto Bypass Set up MiscellaneousEnable Quick Arm All On For AlarmHouse Codes 1-16Format Enable Freeze AlarmFlash For Alarm FORMATHouse Codes 1-16All On Time ClocksPage Daylight Savings Latitude, Longitude, and Time ZoneZONE NAME PageNUMBER Controller IP AddressController Port Number DESCRIPTIONSet Up Names Encryption KeyPage SET UP VOICE 1=CTRL 2=ZONE 3=BTTN ↓ Set Up VoiceSet Up Address 4=CODE 5=TEMP 6=AREA 8=MSG↑UNDERWRITERS LABORATORIES REQUIREMENTS FIRE ESCAPE PLANNINGPage FEDERAL COMMUNICATION COMMISSION NOTICE PageCANADIAN INDUSTRY CANADA NOTICE IF YOU HAVE TROUBLE WITH YOUR PHONESPage APPENDIX A - DIAL OUT PLANNER OmniPro II Voice Dial-OutPlannerPage INSTRUCTIONS TO CALLED PARTY PageCODE CHAR APPENDIX B - TEXT DESCRIPTION CHARACTER CODESCODE CHAR CODE CHARDESCRIPTION APPENDIX C - VOICE DESCRIPTION CODESCODE CODECODE CODEDESCRIPTION DESCRIPTIONCODE CODEDESCRIPTION DESCRIPTIONDESCRIPTION NOTES ON CUSTOM PHRASESCODE CODEPage NOTE TO INSTALLER HAI New Orleans, LA U S A