Installing and connecting the drain hose of the indoor unit
When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65 mm hole drilled in the wall, check the followings:
Wall |
|
|
|
Indoor unit |
|
|
|
Drain hose |
|
|
|
| The drain hose must NOT | The end of the drain hose | The drain hose must not |
| slant upwards. | must NOT be placed under | be bent. |
|
| water. |
|
|
|
| After completing the |
|
|
| installation of the drain |
|
|
| hose, pour water into |
|
|
| the drain pan to check |
5cm |
|
| whether the hose is well |
less | Ditch |
| drained. |
Keep a clearance of at least | Do not place the end of the |
|
|
5 cm between the end of the | drain hose in a hollow. |
|
|
drain hose and the ground. |
|
|
|
1) Correct connection | 2) Incorrect connection |
|
Drain hose | Pipe |
|
|
|
|
|
|
|
|
| Drain hose | Pipe |
• Don’t tie drain hose to the assembly pipe which may lead to water leakage.
Drain hose installation
1.If necessary, connect the 2 meter extension drain hose to the drain hose.
2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.
3.Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.
• If you do not use the other drain hose hole, block it with a rubber stopper.
4.When extending the Drain Hose, hold the end of Drain Hose and Extended Hose, rotate and insert the drain hose into Extended hose for 40~45 mm. Make sure the two hoses are firmly connected, there is no water leakage.
Drain hose hole |
5.Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the each side of connection by 20 mm .
English-46
A3050 MG Model
2014/4/2 9:49:56