REMINGTON QFP40 Direct Vent FIREPLACE
HORIZONTAL TERMINATION REQUIREMENTS
A.*12” (30cm) minimum: Clearance above grade, veranda, porch, deck, or balcony.
B.*12” (30cm) minimum: Clearance to window or door that may be opened.
C.12” (30cm) minimum: Clearance to permanently closed window (recommended to prevent condensation on window.
D.18” (46cm) minimum: Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2’ (60cm) from the centerline of the terminal.
E.12” (30)cm) minimum: Clearance to unventilated soffit.
F.6” (15cm): Clearance to outside corner.
G.9” (23cm): Clearance to inside corner.
*Not to be installed above a meter/regulator (gas or electrical) assembly within 3’ (90cm) horizontally from the centerline of the meter/regulator.
H.*6’ (1.8m) minimum: Clearance to service regulator vent outlet.
I.*12” (30cm) minimum: Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance.
J.*6’ (1.8m) minimum: Clearance to a mechanical air supply air inlet.
K.*+7’ (2.1m) minimum: Clearance above paved sidewalk or a paved driveway located on public property.
L.*#12” (30 cm) minimum: Clearance under veranda, porch, deck, or balcony.
M.6” (15 cm) minimum: Clearance to adjacent building or deck.
N.6” (15 cm) minimum: Clearance to nearby building
+A vent shall not terminate directly above a sidewalk or paved driveway which is located between two
#Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*
*As specified in CGA B149 Installation Codes
Note: Local Codes or regulations may require different clearances.