GAS LINE

REMINGTON QFP40 Direct Vent FIREPLACE

GAS LINE REQUIREMENTS

The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the requirements listed below. Ensure that a 1 1/4" allowance from base of unit is made for hard pipe installation, see page 16, Minimum Framing Dimen- sions.

The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.

The appliance must be isolated from the gas supply piping system by closing its equip- ment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).

Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.

Fuel

This unit is manufactured for use with natural gas. To convert to LP gas, Part #842-4470, LP Conversion Kit, is required and available through your dealer

Gas Line Connection

Amanual shutoff valve is installed in the unit. To access the shutoff valve, open the control panel access door and locate the red swing handle to the right of the control panel beneath the firebox.

Gas Inlet Pressure

All other gas appliances in the household must be turned “ON” to check Inlet Pressure, and;

Inlet pressure can only be checked with fireplace burner “ON”.

Input Pressure

Standard Minimum Maximum

Natural Gas

7" W.C.

4.5"W.C.

7"W.C.

 

 

 

 

Propane

11" W.C.

11"W.C.

14"W.C.

If the pressure is not sufficient, ensure: 1) the piping used is large enough, 2) the supply regulator is adequately adjusted, and 3) that the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

Page 46

250-4721 JUNE 2001

Image 46
Contents For Your Safety What to do if YOU Smell GASWelcome CongratulationsModel Name Serial Number Date Purchased Contents Troubleshooting Parts & Accessories Warranty Completing InstallationMaintenance OperationSafety Label Ratings PlateSTANDARDS/CLEARANCES Label Model Remington QFP40 Vented GAS Fireplace HeaterSafety Notices Safety Notices If YOU Smell GASSpecifications Heating SpecificationsMinimum Cabinet Dimensions Installation Terminology PreparationAN Overview Installation to Operation PreparationLP Conversion LP Conversion InstructionsConversion INSTRUCTIONS, FIG. BInstallation Minimum Framing DimensionsCorner Installations Raised Fireplace Raised Fireplace with Raised Hearth Hearth Requirements Mantel Requirements Combustible MantelsFascia Dimensions Acid Wash AlertInstallation Facing Requirements Rectangular FasciaFacing Over 1 25mm Thick Venting Installation PrecautionsSafety Precautions for the Installer General Venting InstructionsSimpson DURA-VENT Parts List Venting Installation Options & Guidelines Vertical Termination RuleOnly #HHW2Venting INSTALLATION, Installation Into a Class a Metal Chimney USA onlyInstallation Into a Masonry Chimney USA only HOW to USE Vent Graph Horizontal Termination Requirements Horizontal Installation Female Locking Lugs Male Locking LugsWall HHW2 Wood ScrewSiding Beneath Removed Venting Vertical Installation Instructions Using GS Series PipeVenting Minimum Clearance Cathedral Ceiling Installation Installation Into a Class a Metal Chimney USA only Installation Into AN Existing Masonry Chimney USA only Venting Venting GAS Line GAS Line RequirementsElectrical Copper White Wire BlackOptional Thermostat Installation Electrical ConnectionBrick Install Brick InstallationBrick INSTALLATION, Logset and Nugget Installation Logset InstallLOG Identification Logset and Nugget INSTALLATION, Nugget PlacementLeft Twig Glass Installing GlassInstalling Fascia FasciaLeak Test Leak TEST/START-UPInitial START-UP Normal Occurrences Lighting Lighting InstructionsDamper Adjustment AdjustmentsShutter Adjustment Adjusting the Blower SpeedHigh Altitude Operation Operation OperationControl Panel Maintenance MaintenanceYearly Servicing Procedures Glass Replacement Blower Replacement Electrical Schematic Troubleshooting TroublshootingTROUBLESHOOTING, Parts & Accessories PartsWarranty WarrantyDirect Vent Gas Fireplace