Remington QFP40 manual Installation Into a Class a Metal Chimney USA only

Page 42

VENTING

REMINGTON QFP40 Direct Vent FIREPLACE

VERTICAL INSTALLATION INSTRUCTIONS (CONT.)

INSTALLATION INTO A CLASS A METAL CHIMNEY (USA ONLY)

NOTE: Have the existing installation inspected by a qualified chimney sweep or profes- sional installer prior to converting to direct vent. The existing chimney system must be in serviceable condition and functionally sound and clean.

Step 1. Remove existing chimney cap.

Step 2. Measure the distance from the top of the chimney to the bottom of the ceiling support box, add 3" (76mm) to this measurement, and cut a section of 4" (102mm) flex pipe to that length (the flex should be extended to its nominal length).

Step 3. Connect the end of the flex pipe section to the underside of the top adapter (SDV #985K, 986K or 987K), using three sheet metal screws (Figure 19).

Step 4. Pass the flex pipe down through the center of the chimney system, and center the top adapter on the top of the chimney pipe. Drill four 1/8" (3.3mm) diameter holes through the top adapter, and into the chimney top. Ensure that you are drilling into the metal on the chimney. Twist lock the high wind termination cap (SDV #991) onto the top adapter (Figures 20 and 21).

Step 5. Pull the flex pipe down through the ceiling support box, until it protrudes approxi- mately 3" (76mm). Connect the flex pipe to the retro connector (SDV #909B), and attach with sheet metal screws.

Step 6. Push the flex pipe back up into the ceiling support box, center the retro connec- tor, and attach it to the support box with sheet metal screws.

Step 7. The connection between the appliance and the retro connector may be com- pleted with sections of direct vent pipe.

FIG. 19

FIG. 20

FIG. 21

 

TOP

TERMINATION

 

ADAPTER

 

CAP

 

 

FLEX

DRILL (4) 1/8”

SHEET

METAL

PIPE

DIAMETER

SCREWS

 

 

HOLES

SHEET

 

METAL

 

 

SCREWS

 

 

Page 42

250-4721 JUNE 2001

Image 42
Contents For Your Safety What to do if YOU Smell GASWelcome CongratulationsModel Name Serial Number Date Purchased Contents Troubleshooting Parts & Accessories Warranty Completing InstallationMaintenance OperationSafety Label Ratings PlateSTANDARDS/CLEARANCES Label Model Remington QFP40 Vented GAS Fireplace HeaterSafety Notices Safety Notices If YOU Smell GASSpecifications Heating SpecificationsMinimum Cabinet Dimensions Installation Terminology PreparationAN Overview Installation to Operation PreparationLP Conversion LP Conversion InstructionsConversion INSTRUCTIONS, FIG. BInstallation Minimum Framing DimensionsCorner Installations Raised Fireplace Raised Fireplace with Raised Hearth Hearth Requirements Mantel Requirements Combustible MantelsFascia Dimensions Acid Wash AlertInstallation Facing Requirements Rectangular FasciaFacing Over 1 25mm Thick Venting Installation PrecautionsSafety Precautions for the Installer General Venting InstructionsSimpson DURA-VENT Parts List Venting Installation Options & Guidelines Vertical Termination RuleOnly #HHW2Venting INSTALLATION, Installation Into a Class a Metal Chimney USA onlyInstallation Into a Masonry Chimney USA only HOW to USE Vent Graph Horizontal Termination Requirements Horizontal Installation Female Locking Lugs Male Locking LugsWall Wood Screw HHW2Siding Beneath Removed Venting Vertical Installation Instructions Using GS Series PipeVenting Minimum Clearance Cathedral Ceiling Installation Installation Into a Class a Metal Chimney USA only Installation Into AN Existing Masonry Chimney USA only Venting Venting GAS Line GAS Line RequirementsElectrical Copper White Wire BlackOptional Thermostat Installation Electrical ConnectionBrick Install Brick InstallationBrick INSTALLATION, Logset Install Logset and Nugget InstallationLOG Identification Logset and Nugget INSTALLATION, Nugget PlacementLeft Twig Glass Installing GlassInstalling Fascia FasciaLeak TEST/START-UP Leak TestInitial START-UP Normal Occurrences Lighting Lighting InstructionsDamper Adjustment AdjustmentsShutter Adjustment Adjusting the Blower SpeedHigh Altitude Operation Operation OperationControl Panel Maintenance MaintenanceYearly Servicing Procedures Glass Replacement Blower Replacement Electrical Schematic Troubleshooting TroublshootingTROUBLESHOOTING, Parts & Accessories PartsWarranty WarrantyDirect Vent Gas Fireplace