ELECTRICAL CONNECTION

Make sure the household breaker is shut off prior to working on any electrical lines.

This appliance, when installed, must be electrically grounded in acordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.

The electrical line must be at least 14 gauge and supply 120 Volts at 60 Hz (2 Amps)

COPPER

WHITE

WIRE

BLACK

Remove the junction box cover at the right rear corner of the fireplace near the base.

Feed the electrical line through the strain relief (use insulated Romex type wire).

Remove the wires from the junction box. Expose approximately 1/2” of metal wire from each line of the electrical line. Use wire nuts to secure the wires together. Connect copper ground wire to grounding screw as shown in fig- ure above, connect the white wire to the common wire (usually white), and the black wire to the hot wire (usually black).

Push the wire connections into the junction box. Replace the cover plate. Tighten the strain relief onto the outer insulation of the electrical line to se- cure.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring er- rors can cause improper and dangerous operation. Verify proper opera- tion after servicing.

OPTIONAL THERMOSTAT INSTALLATION

A remote control or wall switch may be wired to the TH and TPTH thermostat terminals. See Parts and Accessories on page 66 to order through your dealer.

ELECTRICAL

250-4721 JUNE 2001

Page 47

Image 47
Contents What to do if YOU Smell GAS For Your SafetyCongratulations WelcomeModel Name Serial Number Date Purchased Contents Operation Completing InstallationMaintenance Troubleshooting Parts & Accessories WarrantyRatings Plate Safety LabelModel Remington QFP40 Vented GAS Fireplace Heater STANDARDS/CLEARANCES LabelSafety Notices If YOU Smell GAS Safety NoticesHeating Specifications SpecificationsMinimum Cabinet Dimensions Preparation Installation TerminologyPreparation AN Overview Installation to OperationLP Conversion Instructions LP ConversionFIG. B Conversion INSTRUCTIONS,Minimum Framing Dimensions InstallationCorner Installations Raised Fireplace Raised Fireplace with Raised Hearth Hearth Requirements Combustible Mantels Mantel RequirementsAcid Wash Alert Fascia DimensionsInstallation Rectangular Fascia Facing RequirementsFacing Over 1 25mm Thick General Venting Instructions Installation PrecautionsSafety Precautions for the Installer VentingSimpson DURA-VENT Parts List Vertical Termination Rule Venting Installation Options & Guidelines#HHW2 OnlyInstallation Into a Class a Metal Chimney USA only Venting INSTALLATION,Installation Into a Masonry Chimney USA only HOW to USE Vent Graph Horizontal Termination Requirements Female Locking Lugs Male Locking Lugs Horizontal InstallationWall Siding Beneath Removed Wood ScrewHHW2 Venting Using GS Series Pipe Vertical Installation InstructionsVenting Minimum Clearance Cathedral Ceiling Installation Installation Into a Class a Metal Chimney USA only Installation Into AN Existing Masonry Chimney USA only Venting Venting GAS Line Requirements GAS LineElectrical Connection Copper White Wire BlackOptional Thermostat Installation ElectricalBrick Installation Brick InstallBrick INSTALLATION, LOG Identification Logset InstallLogset and Nugget Installation Nugget Placement Logset and Nugget INSTALLATION,Left Twig Fascia Installing GlassInstalling Fascia GlassInitial START-UP Normal Occurrences Leak TEST/START-UPLeak Test Lighting Instructions LightingAdjusting the Blower Speed AdjustmentsShutter Adjustment Damper AdjustmentHigh Altitude Operation Control Panel OperationOperation Maintenance MaintenanceYearly Servicing Procedures Glass Replacement Blower Replacement Electrical Schematic Troublshooting TroubleshootingTROUBLESHOOTING, Parts Parts & AccessoriesWarranty WarrantyDirect Vent Gas Fireplace