Monessen Hearth PF, CR, CL)NVC/PVC, 624DV(ST manual How To Use The Vent Graph, Dimensions, Feet

Page 16

Designer Series Gas Fireplaces

ventING installation

termination clearances for buildings with combustible and noncombustible exteriors

G G=6" (152mm)

V

Inside Corner

G

V

G = Combustible 24"(610mm) Noncombustible 18"(457mm)

V

F F=6" (152mm)

Outside Corner

H

V

J

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

 

D

C

C

 

V

E

C = Maximum depth of 48" (1219mm) for alcove location

D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)

E = Clearance from corner in alcove location

Combustible - 6" (152mm) Noncombustible - 2" (51mm)

Balcony with No Side Wall

Balcony with Perpendicular

 

 

 

Alcove Location

 

 

Figure 14 -

Side Wall

 

40

 

 

 

 

 

Allowable Venting Chart

 

 

38

 

 

 

 

 

How To Use The Vent Graph

 

 

36

 

 

 

 

Vertical

 

 

34

 

Dimensions in

 

The Vent Graph should be read in conjunction with the following

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

Feet

 

 

vent installation instructions to determine the relationship between

 

30

 

 

 

Dimension

 

 

 

 

 

ing through the outer wall. Using this dimension on the Sidewall

 

 

 

 

 

 

 

 

 

 

 

the vertical and horizontal dimensions of the vent system.

 

28

 

 

 

 

 

1. Determine the height of the center of the horizontal vent pipe exit-

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Graph below, locate the point intersecting with the slanted

 

24

 

 

 

HorizontalVentPipe

From theFloorofUnit

 

12

 

 

 

Example: If the vertical dimension from the floor of the fireplace

 

 

 

 

graph line.

 

 

22

 

 

 

 

 

2. From the point of this intersection, draw a vertical line to the

 

20

 

 

 

 

 

bottom of the graph.

 

 

18

 

 

 

 

 

 

 

16

 

 

 

 

 

3. Select the indicated dimension, and position the fireplace in

 

 

 

 

 

 

 

14

 

 

 

 

 

accordance with same.

 

 

 

 

eg: A

 

 

 

 

 

 

 

 

 

is 11' (3.4 m) the horizontal run to the face of the outer wall must

 

10

 

 

 

 

to

 

8

 

 

 

 

the

not exceed 14' (4.3 m).

 

 

 

 

 

 

Example: If the vertical dimension from the floor of the unit is

 

6

 

 

 

 

Center

7’ (2.14m), the horizontal run to the face of the outer wall must

20"

4

 

 

 

 

not exceed 8Z\x' (2.6 m).

 

 

2

 

 

 

 

of

 

 

 

 

 

 

 

 

Sidewall Vent Graph showing the relationship between vertical and

 

2

4

6

8 10 1214 16 1820

 

the

horizontal dimensions for a Direct Vent flue system.

 

 

 

 

 

Horizontal Dimension From the Outside Face of the

 

 

 

Figure 15 - Wall to the Center of the Fireplace Vent Flange

 

Rear Wall Venting Graph

 

 

 

 

 

16

42D0200

Image 16
Contents Designer Series Direct Vent Gas Fireplace Designer Series Gas Fireplaces Installer OwnerImportant Safety Information and code approval Code ApprovalPlease Read the Following Carefully Never connect unit to private nonProduct features High ElevationsFireplace Dimensions Fireplace Framing Peninsula & Corner Framing SpecificationsPeninsula Framing See-through Framing Specifications Framing FireplaceClearances Clearances to combustiblesMantel clearances Finishing MaterialInstallation and Operating Instructions Fireplace locationInstallation SecurE fireplace to floorOptional TOP Vent installation Optional top vent applicationInstallation precautions VentING installationVenting Clearances 42D0200 Canadian Installations1 US Installations2 VentING installationGeneral Venting Information Termination Location Dimensions How To Use The Vent GraphFeet Rear Wall Vent installation Top View Flat InstallationInstalling Horizontal Vent Cap Horizontal termination configurations Adhered toHorizontal termination configuration ExampleBelow Grade Installations Vertical through-the-roof applications Installation for vertical termination Flat ceiling installationConnect a section of pipe and extend up through the hole Fireplace installation Installing gas piping to fireplace / burner system locationInstallation items needed Check gas typeNatural Gas Propane/LPLabel all wires before disconnecting when Electrical WiringServicing controls. Wiring errors can cause Remote Wall mounted Switch Electrical installationDo not connect wall switch to 110 V circuit Remote Wall Switch Electronic Pilot Ignition WiringOptional DC Remote Systems Glass removal Glass Frame RemovalLOG Placement Install logs and rock wool ember material in fireboxLog placement Log placement Install Top Log #6AIR Restrictor Adjustment Venting Height feet Grille OpeningInitial lighting What to do if YOU Smell GASNever use an open flame to check for gas leak Never check for gas leak with open Approved leak testing methodFlame Lighting the burner Main burner switchPilot position Cleaning and maintenance Cleaning glassFirebox cleaning Venting systemTroubleshooting Standing Pilot IgnitionElectronic Ignition TroubleshootingYES Glass replacement and blower General troubleshootingOptional Blower accessory Blot Logs Replacement partsDescription Qty Natural Propane Replacement Parts are Available Through Your Retailer Fuel Conversion Kits Millivolt Natural Gas to LP Standing Pilot Millivolt ControlLP to Natural Gas Replacement Parts Electronic IgnitionReplacement Parts Vent ComponentsDesigner Series Gas Fireplaces Designer Series Gas Fireplaces Designer Series Gas Fireplaces Carbon Monoxide Detector Requirements Lifetime Warranty Five Year WarrantyBasic Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %