Designer Series Gas Fireplaces | ventING installation |
termination clearances for buildings with combustible and noncombustible exteriors
G G=6" (152mm)
V
Inside Corner
G
V
G = Combustible 24"(610mm) Noncombustible 18"(457mm)
V
F F=6" (152mm)
Outside Corner
H |
V |
J |
Combustible & |
Noncombustible |
H = 24" (610mm) |
J = 20" (508mm) |
| D |
C | C |
|
V
E
C = Maximum depth of 48" (1219mm) for alcove location
D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in alcove location
Combustible - 6" (152mm) Noncombustible - 2" (51mm)
Balcony with No Side Wall | Balcony with Perpendicular |
|
|
| Alcove Location |
|
| ||
Figure 14 - | Side Wall |
| 40 |
|
|
|
|
| |
Allowable Venting Chart |
|
| 38 |
|
|
|
|
| |
How To Use The Vent Graph |
|
| 36 |
|
|
|
| Vertical | |
|
| 34 |
| Dimensions in |
| ||||
The Vent Graph should be read in conjunction with the following |
|
|
| ||||||
|
|
|
| ||||||
| 32 |
|
|
| |||||
|
|
| Feet |
|
| ||||
vent installation instructions to determine the relationship between |
| 30 |
|
|
| Dimension | |||
|
|
|
|
| |||||
ing through the outer wall. Using this dimension on the Sidewall |
|
|
|
|
| ||||
|
|
|
|
|
| ||||
the vertical and horizontal dimensions of the vent system. |
| 28 |
|
|
|
|
| ||
1. Determine the height of the center of the horizontal vent pipe exit- |
|
|
|
|
|
| |||
| 26 |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
Vent Graph below, locate the point intersecting with the slanted |
| 24 |
|
|
| HorizontalVentPipe | From theFloorofUnit | ||
| 12 |
|
|
| |||||
Example: If the vertical dimension from the floor of the fireplace |
|
|
|
| |||||
graph line. |
|
| 22 |
|
|
|
|
| |
2. From the point of this intersection, draw a vertical line to the |
| 20 |
|
|
|
|
| ||
bottom of the graph. |
|
| 18 |
|
|
|
|
| |
|
| 16 |
|
|
|
|
| ||
3. Select the indicated dimension, and position the fireplace in |
|
|
|
|
|
| |||
| 14 |
|
|
|
|
| |||
accordance with same. |
|
|
|
| eg: A |
|
| ||
|
|
|
|
|
|
| |||
is 11' (3.4 m) the horizontal run to the face of the outer wall must |
| 10 |
|
|
|
| to | ||
| 8 |
|
|
|
| the | |||
not exceed 14' (4.3 m). |
|
|
|
|
|
| |||
Example: If the vertical dimension from the floor of the unit is |
| 6 |
|
|
|
| Center | ||
7’ (2.14m), the horizontal run to the face of the outer wall must | 20" | 4 |
|
|
|
| |||
not exceed 8Z\x' (2.6 m). |
|
| 2 |
|
|
|
| of | |
|
|
|
|
|
|
|
| ||
Sidewall Vent Graph showing the relationship between vertical and |
| 2 | 4 | 6 | 8 10 1214 16 1820 |
| the | ||
horizontal dimensions for a Direct Vent flue system. |
|
| |||||||
|
|
| |||||||
Horizontal Dimension From the Outside Face of the | |||||||||
|
| ||||||||
| Figure 15 - Wall to the Center of the Fireplace Vent Flange | ||||||||
| Rear Wall Venting Graph |
|
|
|
|
|
16 | 42D0200 |