Monessen Hearth CR, PF, 624DV(ST Fireplace installation, Check gas type, Installation items needed

Page 25

fireplace installation

Designer Series Gas Fireplaces

check gas type

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or conversion kit.

Installing gas piping to fireplace / burner system location

WARNING

A qualified installer or service person must connect appliance to gas supply. Follow all local codes.

CAUTION

For propane/LP units, never connect fireplace directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP supply.

installation items needed

Before installing fireplace and burner system, make sure you have the items listed below.

External regulator

Piping (check local codes)

Sealant (resistant to propane/LP gas)

 

(supplied by installer)

Test gauge connection*

Sediment trap (recommended)

Equipment shutoff valve*

Tee joint

Pipe wrench

approved flexible gas line with gas connector (if allowed by local codes — not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.

For propane/LP connections the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 35. Pointing the vent down protects it from freezing rain or sleet.

 

100 gal. (min)

External

Propane/LP

Supply Tank

Regulator

 

 

Vent Pointing

 

Down

 

FP1977

 

 

Use only new black iron or steel pipe. Internally

 

 

tinned copper or copper tubing can be used

 

CAUTION

per National Fuel Code, Section 2.6.3, providing

 

gas meets hydrogen sulfide limits, and where

 

 

 

 

permitted by local codes. Gas piping system

 

 

must be sized to provide minimum inlet

 

 

pressure (listed on data plate) at the maximum

 

 

flow rate (BTU/hr). Undue pressure loss will

 

 

occur if the pipe is too small.

 

 

 

When using copper of flex connectors use only fittings approved for gas connections. The gas control inlet is 3/8" NPT.

Figure 35 -

External Regulator with Vent Pointing Down (Propane/LP Only)

42D0200

25

Image 25
Contents Designer Series Direct Vent Gas Fireplace Designer Series Gas Fireplaces Owner InstallerCode Approval Important Safety Information and code approvalPlease Read the Following Carefully Never connect unit to private nonHigh Elevations Product featuresFireplace Dimensions Fireplace Framing Peninsula & Corner Framing SpecificationsPeninsula Framing Framing Fireplace See-through Framing SpecificationsClearances to combustibles ClearancesMantel clearances Finishing MaterialFireplace location Installation and Operating InstructionsSecurE fireplace to floor InstallationOptional top vent application Optional TOP Vent installationInstallation precautions VentING installationVenting Clearances 42D0200 Canadian Installations1 US Installations2 VentING installationGeneral Venting Information Termination Location Dimensions How To Use The Vent GraphFeet Top View Flat Installation Rear Wall Vent installationInstalling Horizontal Vent Cap Adhered to Horizontal termination configurationsExample Horizontal termination configurationBelow Grade Installations Vertical through-the-roof applications Flat ceiling installation Installation for vertical terminationConnect a section of pipe and extend up through the hole Installing gas piping to fireplace / burner system location Fireplace installationInstallation items needed Check gas typePropane/LP Natural GasLabel all wires before disconnecting when Electrical WiringServicing controls. Wiring errors can cause Remote Wall mounted Switch Electrical installationDo not connect wall switch to 110 V circuit Remote Wall Switch Electronic Pilot Ignition WiringOptional DC Remote Systems Glass Frame Removal Glass removalInstall logs and rock wool ember material in firebox LOG PlacementLog placement Install Top Log #6 Log placementVenting Height feet Grille Opening AIR Restrictor AdjustmentInitial lighting What to do if YOU Smell GASNever use an open flame to check for gas leak Never check for gas leak with open Approved leak testing methodFlame Lighting the burner Main burner switchPilot position Cleaning glass Cleaning and maintenanceFirebox cleaning Venting systemStanding Pilot Ignition TroubleshootingElectronic Ignition TroubleshootingYES Glass replacement and blower General troubleshootingOptional Blower accessory Blot Logs Replacement partsDescription Qty Natural Propane Replacement Parts are Available Through Your Retailer Fuel Conversion Kits Millivolt Natural Gas to LP Standing Pilot Millivolt ControlLP to Natural Gas Electronic Ignition Replacement PartsVent Components Replacement PartsDesigner Series Gas Fireplaces Designer Series Gas Fireplaces Designer Series Gas Fireplaces Carbon Monoxide Detector Requirements Five Year Warranty Lifetime WarrantyBasic Warranty If Warranty Service is NeededModel EnerGuide Ratings Fireplace Efficiency % Mhsc