Monessen Hearth 624DV(ST, PF, CR, CL)NVC/PVC manual Horizontal termination configurations, Adhered to

Page 19

ventING installation

Designer Series Gas Fireplaces

Horizontal termination configurations

40

 

 

 

Since it is very important that the venting system maintain its bal-

38

 

 

 

ance between the combustion air intake and the flue gas exhaust,

36

 

 

 

certain limitations as to vent configurations apply and must be strictly

34

 

Dimensions in

adhered to.

 

32

 

 

 

 

Feet

 

 

 

 

The Vent Graph, showing the relationship between vertical and horizontal

30

 

 

 

 

 

side wall venting, will help to determine the various dimensions allowable.

28

 

 

 

Figure 22

 

26

 

 

 

Minimum clearance between vent pipes and combustible materials is

 

 

 

24

 

 

 

3" on top and 1" from bottom and sides unless otherwise noted.

22

 

 

 

 

 

 

 

 

When vent termination exits through foundations less than 20" below siding

20

 

 

 

outcrop, the vent pipe must flush up with the siding.

 

18

 

 

 

It is best to locate the fireplace in such a way that minimizes the number

16

 

 

 

of offsets and horizontal vent length.

 

14

 

 

eg: A

The horizontal vent run refers to the total length of vent pipe from the

12

 

 

 

 

 

flue collar of the fireplace (or the top of he Transition Elbow) to the

10

 

 

 

face of the outer wall.

 

8

 

 

 

The maximum number of 90° elbows per side wall instal-

 

6

 

 

 

lation is three (3). Figure 23

20"

4

 

 

 

If a 90° elbow is fitted directly on top of the fireplace flange

 

2

 

 

 

the maximum horizontal vent run before the termination

 

2

4

6

8 10 1214 16 1820

or a vertical rise is 36” (914 mm). Figure 24

 

Horizontal Dimension From the Outside Face of the

 

 

Figure 22 - Wall to the Center of the Fireplace Vent Flange

 

Rear Wall Venting Graph

 

 

 

3 x 90°

Elbows

3 x 90°

Elbows

FP1176

Figure 23 -

Maximum Three (3) 90° Elbows Per Installation

36"

(914 mm)

Max.

FP1177

Figure 24 -

Maximum Horizontal Run with No Rise

42D0200

19

Image 19
Contents Designer Series Direct Vent Gas Fireplace Designer Series Gas Fireplaces Owner InstallerNever connect unit to private non Important Safety Information and code approvalCode Approval Please Read the Following CarefullyHigh Elevations Product featuresFireplace Dimensions Fireplace Framing Peninsula & Corner Framing SpecificationsPeninsula Framing Framing Fireplace See-through Framing SpecificationsFinishing Material ClearancesClearances to combustibles Mantel clearancesFireplace location Installation and Operating InstructionsSecurE fireplace to floor InstallationOptional top vent application Optional TOP Vent installationInstallation precautions VentING installationVenting Clearances 42D0200 Canadian Installations1 US Installations2 VentING installationGeneral Venting Information Termination Location Dimensions How To Use The Vent GraphFeet Top View Flat Installation Rear Wall Vent installationInstalling Horizontal Vent Cap Adhered to Horizontal termination configurationsExample Horizontal termination configurationBelow Grade Installations Vertical through-the-roof applications Flat ceiling installation Installation for vertical terminationConnect a section of pipe and extend up through the hole Check gas type Fireplace installationInstalling gas piping to fireplace / burner system location Installation items neededPropane/LP Natural GasLabel all wires before disconnecting when Electrical WiringServicing controls. Wiring errors can cause Remote Wall mounted Switch Electrical installationDo not connect wall switch to 110 V circuit Remote Wall Switch Electronic Pilot Ignition WiringOptional DC Remote Systems Glass Frame Removal Glass removalInstall logs and rock wool ember material in firebox LOG PlacementLog placement Install Top Log #6 Log placementVenting Height feet Grille Opening AIR Restrictor AdjustmentInitial lighting What to do if YOU Smell GASNever use an open flame to check for gas leak Never check for gas leak with open Approved leak testing methodFlame Lighting the burner Main burner switchPilot position Venting system Cleaning and maintenanceCleaning glass Firebox cleaningStanding Pilot Ignition TroubleshootingElectronic Ignition TroubleshootingYES Glass replacement and blower General troubleshootingOptional Blower accessory Blot Logs Replacement partsDescription Qty Natural Propane Replacement Parts are Available Through Your Retailer Fuel Conversion Kits Millivolt Natural Gas to LP Standing Pilot Millivolt ControlLP to Natural Gas Electronic Ignition Replacement PartsVent Components Replacement PartsDesigner Series Gas Fireplaces Designer Series Gas Fireplaces Designer Series Gas Fireplaces Carbon Monoxide Detector Requirements If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyModel EnerGuide Ratings Fireplace Efficiency % Mhsc