Monessen Hearth CR, PF, CL)NVC/PVC manual Rear Wall Vent installation, Top View Flat Installation

Page 17

Venting installation

Designer Series Gas Fireplaces

Rear Wall Vent installation

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance

The maximum horizontal distance between the rear of the appliance and the outside face of the rear wall is 20" (508 m). Figure 16

Only one 45° elbow is allowed in these installations.

20"

(508 mm)

9Z\x"

(241 mm)

Top View Flat

Installation

11Z\x"

(292 mm)

Figure 16 -

Rear Vent Application, Maximum

Horizontal Distance

1.Locate and cut the vent opening in the wall. For combustible walls first frame in opening. Combustible Walls: Cut a 11Z\x"H x 9Z\x" W (292 x 241 mm) hole through the exterior wall and frame as shown. Figure 17

Noncombustible Walls: Hole opening should be 7Z\x" (190 mm) in diameter.

2.Rigid vent pipes and fittings have special twist-lock connections. Assemble the desired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor.

Twist-lock Procedure: The female ends of the pipes and fittings have three locking lugs (indentations). These lugs will slide straight into matching slots on the male end of adjacent pipes and fittings. Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. Figure 18

3.Attach vent pipe assembly to the fireplace. Set fire- place in front of its permanent location to insure mini- mum clearances. Mark the wall for a 11Z\x"H x 9Z\x"W (292 x 241 mm) rectangle hole (for noncombustible material such as masonry block or concrete, a 7Z\x" [190 mm] diameter hole is acceptable). Figure 17. The center of the hole should line up with the center line of the horizontal rigid vent pipe end. Be sure to allow for minimum rise. Cut a 11Z\x"x9Z\x" rectangle hole through combustible exterior wall (7Z\x" diameter hole if noncombustible). Frame as necessary. Allow 1/4" minimum rise per foot. Figure 17

7Z\x"

(190 mm)

FP1954

Figure 17 -

Vent Opening Requirements

Female Locking

Lugs

Note: Horizontal runs of vent must be supported every three (3) feet (914 mm). Use wall straps for this purpose.

Male Slots

FP1953

Figure 18 -

Rigid Vent Pipe Connections

42D0200

17

Image 17
Contents Designer Series Direct Vent Gas Fireplace Designer Series Gas Fireplaces Owner InstallerCode Approval Important Safety Information and code approvalPlease Read the Following Carefully Never connect unit to private nonHigh Elevations Product featuresFireplace Dimensions Peninsula Framing Peninsula & Corner Framing SpecificationsFireplace Framing Framing Fireplace See-through Framing SpecificationsClearances to combustibles ClearancesMantel clearances Finishing MaterialFireplace location Installation and Operating InstructionsSecurE fireplace to floor InstallationOptional top vent application Optional TOP Vent installationVenting Clearances VentING installationInstallation precautions 42D0200 General Venting Information Termination Location VentING installationCanadian Installations1 US Installations2 Feet How To Use The Vent GraphDimensions Top View Flat Installation Rear Wall Vent installationInstalling Horizontal Vent Cap Adhered to Horizontal termination configurationsExample Horizontal termination configurationBelow Grade Installations Vertical through-the-roof applications Flat ceiling installation Installation for vertical terminationConnect a section of pipe and extend up through the hole Installing gas piping to fireplace / burner system location Fireplace installationInstallation items needed Check gas typePropane/LP Natural GasServicing controls. Wiring errors can cause Electrical WiringLabel all wires before disconnecting when Do not connect wall switch to 110 V circuit Electrical installationRemote Wall mounted Switch Optional DC Remote Systems Electronic Pilot Ignition WiringRemote Wall Switch Glass Frame Removal Glass removalInstall logs and rock wool ember material in firebox LOG PlacementLog placement Install Top Log #6 Log placementVenting Height feet Grille Opening AIR Restrictor AdjustmentNever use an open flame to check for gas leak What to do if YOU Smell GASInitial lighting Flame Approved leak testing methodNever check for gas leak with open Pilot position Main burner switchLighting the burner Cleaning glass Cleaning and maintenanceFirebox cleaning Venting systemStanding Pilot Ignition TroubleshootingYES TroubleshootingElectronic Ignition Optional Blower accessory Blot General troubleshootingGlass replacement and blower Description Qty Natural Propane Replacement partsLogs Replacement Parts are Available Through Your Retailer LP to Natural Gas Standing Pilot Millivolt ControlFuel Conversion Kits Millivolt Natural Gas to LP Electronic Ignition Replacement PartsVent Components Replacement PartsDesigner Series Gas Fireplaces Designer Series Gas Fireplaces Designer Series Gas Fireplaces Carbon Monoxide Detector Requirements Five Year Warranty Lifetime WarrantyBasic Warranty If Warranty Service is NeededModel EnerGuide Ratings Fireplace Efficiency % Mhsc