Monessen Hearth CR, PF, CL)NVC/PVC, 624DV(ST manual Below Grade Installations

Page 21

ventING installation

Designer Series Gas Fireplaces

Below Grade Installations

When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178 mm) below grade level. The 7" (178 mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.

If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. Refer to the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".

1.Establish vent hole through the wall. Refer to Page 18, Figure 17

2.Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approxi- mately 4" below snorkel. Figure 28

3.Install vent system.

4.Ensure a watertight seal is made around the vent pipe coming through the wall.

5.Slide the snorkel into the vent pipes and secure to the wall.

6.Level the soil so as to maintain a 4" clearance below snor- kel. Figure 28

WARNING

Do not back fill around snorkel.

A clearance of at least 4” must be maintained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2" sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. Figure 28

 

Screws

Firestop

 

 

Minimum

 

4" Clearance

 

Ground

24"

Window Well

 

Minimum

Gravel

 

 

Drain

 

Foundation Wall

Foundation

Recess

Watertight Seal Around Pipe

Snorkel

Wall Screws

Sheet Metal

Screws

FP1965

Figure 28 -

Below Grade Installation

FP1966

Figure 29 -

Snorkel Installation, Recessed Foundation

42D0200

21

Image 21
Contents Designer Series Direct Vent Gas Fireplace Designer Series Gas Fireplaces Owner InstallerCode Approval Important Safety Information and code approvalPlease Read the Following Carefully Never connect unit to private nonHigh Elevations Product featuresFireplace Dimensions Peninsula & Corner Framing Specifications Fireplace FramingPeninsula Framing Framing Fireplace See-through Framing SpecificationsClearances to combustibles ClearancesMantel clearances Finishing MaterialFireplace location Installation and Operating InstructionsSecurE fireplace to floor InstallationOptional top vent application Optional TOP Vent installationVentING installation Installation precautionsVenting Clearances 42D0200 VentING installation Canadian Installations1 US Installations2General Venting Information Termination Location How To Use The Vent Graph DimensionsFeet Top View Flat Installation Rear Wall Vent installationInstalling Horizontal Vent Cap Adhered to Horizontal termination configurationsExample Horizontal termination configurationBelow Grade Installations Vertical through-the-roof applications Flat ceiling installation Installation for vertical terminationConnect a section of pipe and extend up through the hole Installing gas piping to fireplace / burner system location Fireplace installationInstallation items needed Check gas typePropane/LP Natural GasElectrical Wiring Label all wires before disconnecting whenServicing controls. Wiring errors can cause Electrical installation Remote Wall mounted SwitchDo not connect wall switch to 110 V circuit Electronic Pilot Ignition Wiring Remote Wall SwitchOptional DC Remote Systems Glass Frame Removal Glass removalInstall logs and rock wool ember material in firebox LOG PlacementLog placement Install Top Log #6 Log placementVenting Height feet Grille Opening AIR Restrictor AdjustmentWhat to do if YOU Smell GAS Initial lightingNever use an open flame to check for gas leak Approved leak testing method Never check for gas leak with openFlame Main burner switch Lighting the burnerPilot position Cleaning glass Cleaning and maintenanceFirebox cleaning Venting systemStanding Pilot Ignition TroubleshootingTroubleshooting Electronic IgnitionYES General troubleshooting Glass replacement and blowerOptional Blower accessory Blot Replacement parts LogsDescription Qty Natural Propane Replacement Parts are Available Through Your Retailer Standing Pilot Millivolt Control Fuel Conversion Kits Millivolt Natural Gas to LPLP to Natural Gas Electronic Ignition Replacement PartsVent Components Replacement PartsDesigner Series Gas Fireplaces Designer Series Gas Fireplaces Designer Series Gas Fireplaces Carbon Monoxide Detector Requirements Five Year Warranty Lifetime WarrantyBasic Warranty If Warranty Service is NeededModel EnerGuide Ratings Fireplace Efficiency % Mhsc