Lennox International Inc G24-200 installation instructions

Page 16
Manual background

COMMON VENTING USING TILE−LINED INTERIOR MASONRY CHIMNEY AND COMBINED VENT CONNECTOR

NOTE 1 − Refer to provided venting tables

MIN. LENGTH = AS SHORT AS PRACTICAL.

FOR MAX. LENGTH SEE NOTE 1

for installations in the USA and the vent-

 

INTERIOR TILE−LINED

ing tables in current CSA−B149.1 for

 

 

MASONRY CHIMNEY

installations in Canada.

 

 

JOIN HEAT SECTIONS

 

 

 

 

WITH A ’TEE−Y’

VENT

 

 

CONNECTOR

 

NOTE − The chimney must be

SEE NOTE 2

 

 

properly sized per provided vent-

 

 

 

 

ing tables and lined with a listed

Note 2 − Either single-walled or double-walled vent

metal lining system.

 

connector may be used. Refer to the capacity re-

PERMANENTLY SEALED

quirements as shown in the provided venting tables

FIREPLACE OPENING

for installations in USA and the venting tables in cur-

G24−200

rent CSA−B149.1 for installations in Canada.

FIGURE 10

General Venting Requirements

All G24−200 furnaces must be vented according to these instructions.

1 − Vent diameter recommendations and maximum al- lowable piping runs are found in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149.1 of the Natural Gas and Propane Installation Code for Canada.

2 − In no case should the vent or vent connector diameter be less than the diameter specified in the provided venting tables for the USA, and the appropriate vent- ing tables in the standards of CSA B149.1 of the Natu- ral Gas and Propane Installation Code for Canada.

3 − Single Appliance Vent − If the vertical vent or tile-lined chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to de- termine the minimum vent capacity and the vent connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, how- ever, shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood out- let area or flue collar area unless designed according to approved engineering methods.

4 − Multiple Appliance Vents − The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, flue collar area or drafthood outlet area unless designed according to engineering methods.

5 − The entire length of single wall metal vent connector shall be readily accessible for inspection, cleaning, and replacement.

6 − Single appliance venting configurations with zero lat- eral lengths, see tables 3 and 4, are assumed to have no elbows in the vent system. For all other vent config- urations, the vent system is assumed to have two 90_ elbows. For each additional 90_ elbow or equivalent (for example two 45_ elbows equal one 90_ elbow) be- yond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi- mum listed capacity).

7 − The common venting tables 5, 6, 7, and 8 were gener- ated using a maximum horizontal vent connector length of 1-1/2 feet (18 inches) for each inch of con- nector diameter as follows:

 

TABLE 2

 

 

 

Connector

 

Maximum Horizontal

Diameter

 

Connector Length

inches (mm)

 

feet (m)

 

 

 

3 (76)

 

4−1/2 (1.37)

 

 

 

4 (102)

 

6 (1.83)

 

 

 

5 (127)

 

7−1/2 (2.29)

 

 

 

6 (152)

 

9 (2.74)

 

 

 

7 (178)

 

10−1/2 (3.20)

8 − If the common vertical vent is offset, the maximum common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90_ elbows (0.80 x maximum common vent ca- pacity). The horizontal length of the offset shall not ex- ceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.

9 − The vent pipe should be as short as possible with the least number of elbows and angles to do the job. The vent connector should be routed to the vent using the shortest possible route.

Page 16

Image 16
Contents INSTALLATION INSTRUCTIONS G24-200 2P0805P504613M WHAT TO DO IF YOU SMELL GASG24−200 Unit Dimensions − inches mm PageG24−200 Filter Box Dimensions − inches mm SIDE VIEWBACK VIEW TOP VIEWG24−200 HEAT SECTION AND CABINET G24−200 Parts ArrangementPage G24−200 BLOWER SECTION G24−200 Parts Arrangement ContinuedPage G24−200 Gas Furnace SafetyShipping and Packing List setting General Combustion, Dilution & Ventilation AirCements and glues EQUIPMENT IN CONFINED SPACE ALL AIR FROM INSIDE Setting Equipment Return Air Plenum / Filter Box InstallationBOTTOM RETURN AIR FILTER BOX INSTALLATION PageBlower Motor / Drive Installation Duct SystemVenting Venting Using a Masonry Chimney Page Page SERVING A SINGLE CATEGORY I APPLIANCE PageSERVING A SINGLE CATEGORY I APPLIANCE PageVENT CONNECTOR CAPACITY SERVING TWO OR MORE CATEGORY I APPLIANCESSERVING TWO OR MORE CATEGORY I APPLIANCES COMMON VENT CAPACITYPage CARBON MONOXIDE POISONING HAZARD VENT TERMINATION CLEARANCES FOR INSTALLATIONS IN THE USA AND CANADAPage Horizontal Venting Gas Piping FIRE OR EXPLOSION HAZARD Electrical G24−200 FIELD WIRING DIAGRAM 120V SINGLE PH 60HZ Alternate make-upbox right side Alternate make-upG24-200FIELD WIRING DIAGRAM G24−200 FIELD WIRING DIAGRAM G UNITS − 460V 3PH 60HZJ UNITS − 575V 3PH 60HZ Alternate make-upFIGURE Page WIRING SCHEMATIC DIAGRAM FOR G24−200 P UNITS − 208/230V 1PH 60 HZY UNITS − 208/230V 3PH 60HZ G UNITS − 460V 3PH 60HZUnit Start−Up Heating Sequence of Operation Other Unit Adjustments and Operation Gas Pressure AdjustmentHigh Altitude Information Temperature Rise Setting blower CFM TABLE DRIVE KIT SPECIFICATIONS TABLE ACCESSORY AIR RESISTANCEPage Repair Parts List G24−200 Start−up and Performance Check ListTroubleshooting NORMAL HEATING MODEABNORMAL HEATING MODE Page3 − OFF NO POWER OR DETECTED FAULT NORMAL HEATING MODEABNORMAL HEATING MODE LED CODESPOWER ON THERMOSTAT CALLS FOR HEAT W1 ENERGIZED IS THE S10 S99 HIGH LIMIT CLOSED? YES COOLING SEQUENCE OF OPERATION FOR TWO CONDENSING UNITSFOR A SINGLE CONDENSING UNIT MANUAL FAN OPERATION