HEATING SEQUENCE OF OPERATION WITH
NORMAL HEATING MODE | ABNORMAL HEATING MODE |
IS THE S10 (S99) HIGH LIMIT CLOSED?
YES
HAS ROOM AIR TEMPERATURE CONTINUED
TO DROP BELOW THE THERMOSTAT"S
W2 SET POINT?
NO
DETERMINE WHY
RELAYS MAINTAIN BLOWER OPERATION.
YES
POWER FROM W2
ENERGIZES K19 RELAY
GAS VALVE ENERGIZED (HIGH HEAT)
AFTER APPROXIMATELY 3 SEC.
IS W2 DEMAND SATISFIED?
YES
CLOSE
NO
IS W1 DEMAND SATISFIED?
YES |
A3 (A12) LED OFF |
GAS VALVE CLOSES. |
B6 (B15) COMBUSTION |
AIR BLOWER OFF. |
B3 SYSTEM BLOWERS OFF |
AFTER 150 SEC DELAY. |
NOTE − IF ECONOMIZER INSTALLED, ECONOMIZER OPERATES WHEN BLOWER POWERED.
LED CODES
1 − ON NORMAL OPERATION WITH THERMOSTAT CALLING FOR HEAT. 2 − 0.5 SEC ON AND 2.5 SECS OFF IN IGNITION RETRY PERIOD.
3 − OFF NO POWER OR DETECTED FAULT.
Page 41