Lennox International Inc G24-200 installation instructions Horizontal Venting

Page 24
Horizontal Venting

Horizontal Venting

This furnace design is certified by CSA international for horizontal venting through an outside wall, only with the use of two Field Controls Company Model SWG-4L side- wall venting kits, available from any Lennox Dealer Service Center. No other Field brand venting kits or any other manufacturer’s venting kits are acceptable. Horizontal venting of this furnace without the use of the above stated kits is prohibited.

NOTE − Each heat section of the G24−200 unit re- quires its own sidewall venting kit. The two venting systems shall be completely separate starting at the outlet of each heat section and ending with the vent terminal of each Field Controls Venting Kit. (See fig- ure 12 for field wiring of the two sidewall horizontal venting kits.)

When horizontally vented, the minimum clearance for terminations from electric meters, gas meters, regula- tors and relief equipment is 4 ft. (1.2m) for US installa- tions. Refer to the current CSA−B149.1 for installations in Canada or with authorities having local jurisdiction.

At vent terminations, care must be taken to maintain pro- tective coatings over building materials (prolonged expo- sure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8 m) of a condensing unit be- cause the condensate can damage the painted coating.

WIRING FOR SIDEWALL VENTING KITS (Two kits are required − one for each heat section.)

FIELD INSTALLED WIRING

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

W1

W2

R

Y1

Y2

C

G

 

CK−43 CONTROL BOX

 

 

 

 

 

 

 

 

 

 

 

 

2

5

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

PRESSURE

 

 

3

4

 

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY

 

 

 

 

 

 

C

NO

 

 

 

W1

W2

R

Y1

Y2

C

G

 

 

 

 

 

 

 

 

 

 

 

L1

N

M

T1 T2 T3

 

 

 

 

 

 

FACTORY INSTALLED WIRING

CK−43 CONTROL BOX

 

 

 

 

2

5

 

 

 

 

1

 

 

PRESSURE

 

 

3

4

 

SWITCH

 

 

 

 

 

 

 

 

RELAY

C

NO

 

 

 

 

 

L1

N

M

T1 T2 T3

M

SWG

TERMINAL STRIP FOR THERMOSTAT

POWER

CONNECTIONS IN FURNACE JUNCTION BOX

VENTER

 

 

MOTOR

M

SWG

POWER VENTER MOTOR

L1 L2

120VAC

FIGURE 12

Page 24

Image 24
Contents INSTALLATION INSTRUCTIONS G24-200 2P0805P504613M WHAT TO DO IF YOU SMELL GASG24−200 Unit Dimensions − inches mm PageG24−200 Filter Box Dimensions − inches mm SIDE VIEWBACK VIEW TOP VIEWG24−200 Parts Arrangement G24−200 HEAT SECTION AND CABINETPage G24−200 Parts Arrangement Continued G24−200 BLOWER SECTIONPage Safety G24−200 Gas FurnaceShipping and Packing List setting General Combustion, Dilution & Ventilation AirCements and glues EQUIPMENT IN CONFINED SPACE ALL AIR FROM INSIDE Setting Equipment Return Air Plenum / Filter Box InstallationBOTTOM RETURN AIR FILTER BOX INSTALLATION PageBlower Motor / Drive Installation Duct SystemVenting Venting Using a Masonry Chimney Page Page SERVING A SINGLE CATEGORY I APPLIANCE PageSERVING A SINGLE CATEGORY I APPLIANCE PageVENT CONNECTOR CAPACITY SERVING TWO OR MORE CATEGORY I APPLIANCESSERVING TWO OR MORE CATEGORY I APPLIANCES COMMON VENT CAPACITYPage CARBON MONOXIDE POISONING HAZARD FOR INSTALLATIONS IN THE USA AND CANADA VENT TERMINATION CLEARANCESPage Horizontal Venting Gas Piping FIRE OR EXPLOSION HAZARD Electrical G24−200 FIELD WIRING DIAGRAM 120V SINGLE PH 60HZ Alternate make-upbox right side Alternate make-upG24-200FIELD WIRING DIAGRAM G24−200 FIELD WIRING DIAGRAM G UNITS − 460V 3PH 60HZJ UNITS − 575V 3PH 60HZ Alternate make-upFIGURE Page WIRING SCHEMATIC DIAGRAM FOR G24−200 P UNITS − 208/230V 1PH 60 HZY UNITS − 208/230V 3PH 60HZ G UNITS − 460V 3PH 60HZUnit Start−Up Heating Sequence of Operation Gas Pressure Adjustment Other Unit Adjustments and OperationHigh Altitude Information Temperature Rise Setting blower CFM TABLE ACCESSORY AIR RESISTANCE TABLE DRIVE KIT SPECIFICATIONSPage Repair Parts List G24−200 Start−up and Performance Check ListTroubleshooting NORMAL HEATING MODEABNORMAL HEATING MODE Page3 − OFF NO POWER OR DETECTED FAULT NORMAL HEATING MODEABNORMAL HEATING MODE LED CODESPOWER ON THERMOSTAT CALLS FOR HEAT W1 ENERGIZED IS THE S10 S99 HIGH LIMIT CLOSED? YES COOLING SEQUENCE OF OPERATION FOR TWO CONDENSING UNITSFOR A SINGLE CONDENSING UNIT MANUAL FAN OPERATION