Horizontal Venting
This furnace design is certified by CSA international for horizontal venting through an outside wall, only with the use of two Field Controls Company Model
NOTE − Each heat section of the G24−200 unit re- quires its own sidewall venting kit. The two venting systems shall be completely separate starting at the outlet of each heat section and ending with the vent terminal of each Field Controls Venting Kit. (See fig- ure 12 for field wiring of the two sidewall horizontal venting kits.)
When horizontally vented, the minimum clearance for terminations from electric meters, gas meters, regula- tors and relief equipment is 4 ft. (1.2m) for US installa- tions. Refer to the current CSA−B149.1 for installations in Canada or with authorities having local jurisdiction.
At vent terminations, care must be taken to maintain pro- tective coatings over building materials (prolonged expo- sure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8 m) of a condensing unit be- cause the condensate can damage the painted coating.
WIRING FOR SIDEWALL VENTING KITS (Two kits are required − one for each heat section.)
FIELD INSTALLED WIRING
|
|
|
|
|
|
|
| 24 VAC |
|
| |
|
|
|
|
|
|
| THERMOSTAT |
| |||
|
|
|
|
| W1 | W2 | R | Y1 | Y2 | C | G |
| CK−43 CONTROL BOX |
|
|
|
|
|
|
|
| ||
|
|
|
| 2 | 5 |
|
|
|
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
|
| PRESSURE |
|
| 3 | 4 |
|
|
|
|
|
|
| SWITCH |
|
|
|
|
|
|
|
|
|
|
|
|
|
| RELAY |
|
|
|
|
|
| |
C | NO |
|
|
| W1 | W2 | R | Y1 | Y2 | C | G |
|
|
|
|
|
|
|
|
|
| ||
| L1 | N | M | T1 T2 T3 |
|
|
|
|
|
|
FACTORY INSTALLED WIRING
CK−43 CONTROL BOX
|
|
|
| 2 | 5 |
|
|
|
| 1 |
|
| PRESSURE |
|
| 3 | 4 |
| SWITCH |
|
|
|
|
|
|
|
| RELAY | |
C | NO |
|
|
|
|
| L1 | N | M | T1 T2 T3 |
M
SWG | TERMINAL STRIP FOR THERMOSTAT | ||
POWER | |||
CONNECTIONS IN FURNACE JUNCTION BOX | |||
VENTER | |||
|
|
MOTOR
M
SWG
POWER VENTER MOTOR
L1 L2
120VAC
FIGURE 12
Page 24