Gas Piping
NOTE − The flexible connector supplied with the unit must not be modified and must be installed between the two combination gas controls.
1 − Piping can be installed to enter either side of cabinet. Refer to figure 13.
a − Remove tee and 1/2 in. NPTx1/2 in. male brass fitting from left side gas valve.
b − Remove 1/2 in. elbow and nipple from right side gas valve and
c −
d − Install flexible connector (supplied with unit) be- tween gas valves and connect supply piping as shown.
NOTE − Flexible gas connector must be routed so that connector does NOT come in contact or interfere with any wiring.
2 − When connecting the gas supply, factors such as length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical ap- plications.
3 − The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumbwaiters or elevator shafts.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15 feet (4.57 m) upward toward the meter from the fur- nace. The piping must be supported at proper inter- vals [every 8 to 10 feet (2.44 to 3.01 m) using suitable hangers or straps. A drip leg should be installed in ver- tical pipe runs to the unit.
5 − In some localities, codes may require installation of a manual main
6 − A 1/8" N.P.T. plugged tap is located on gas valve for test gauge connection. See figure 20 for tap location.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro- leum gases.
LEFT SIDE GAS LINE INSTALLATION
MANUAL MAIN | FLEXIBLE CONNECTOR | ||||
|
|
|
|
| |
|
|
|
|
| SHIPPED WITH UNIT |
|
|
|
| 1/2 in. NPT X 1/2 in. MALE | AND FIELD INSTALLED |
|
|
|
|
| |
|
|
|
| BRASS FITTING |
|
|
|
|
| (Provided with flex connector) | 1/2 in. STREET |
|
|
|
| TEE | |
|
|
|
| ELBOW | |
|
|
|
| ||
|
|
|
| (3/4 in. X 1/2 in. X 1/2 in.) | |
|
|
|
|
|
| AUTOMATIC GAS VALVE |
DRIP LEG | (WITH MANUAL |
GROUND JOINT UNION
FIELD PROVIDED AND
INSTALLED
RIGHT SIDE GAS LINE INSTALLATION
(See item # 1 on previous page for installation instructions)
FLEXIBLE CONNECTOR |
|
| MANUAL MAIN | ||||||||
SHIPPED WITH UNIT |
|
|
|
|
|
|
|
|
|
|
|
AND FIELD INSTALLED |
|
|
|
|
|
|
|
|
|
|
|
| 1/2 in. NPT X 1/2 in. MALE |
| TEE | ||||||||
|
| BRASS FITTING |
|
|
|
|
| ||||
|
| (3/4 in. X 1/2 in. X 1/2in. ) | |||||||||
|
| (Provided with | |||||||||
|
|
|
|
|
|
|
|
|
| ||
1/2 in. STREET |
| flex connector) |
|
|
|
|
|
|
|
| |
ELBOW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AUTOMATIC GAS VALVE | DRIP LEG | ||
(WITH MANUAL | ||||
| ||||
|
|
| GROUND JOINT UNION | |
|
| FIELD PROVIDED AND |
| |
|
|
| ||
|
| INSTALLED |
|
FIGURE 13