Lennox International Inc G24-200 installation instructions setting

Page 7

For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are lo- cated no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical dam- age by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149.1 standard.

The furnace must be adjusted to obtain a temperature rise range and within the allowable external static pressure on furnaces with a duct system as listed on unit nameplate.

Installation in parking structures must be in accordance with the Standard for Parking Structures (ANSI/NFPA No. 88A−1991). Installation in repair garages must be in accor- dance with the Standard for Repair Garages (ANSI/NFPA No. 88B−1991).

The G24−200 furnace must be installed so that electrical components are protected from water.

When the furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually oper- ated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full T" or

" setting.

When installed, the furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following address:

National Fire Protection Association 1 Battery March Park

Quincy, MA 02269

In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.

Never test for gas leaks with an open flame. Check all con- nections with a commercially available soap solution made specifically for leak detection.

NOTE − Furnace must be adjusted to obtain a tempera- ture rise (high and low fire) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit operation.

Field wiring connection must meet or exceed specifications of type T wire and withstand a maximum temperature rise of 180°F (82°C).

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space con- taining the furnace, return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside space containing furnace.

NOTE − This furnace is designed for a minimum continu- ous return air temperature of 60°F (16°C) or an intermit- tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.

Use of this unit as a construction heater or air conditioner is not recommended during any phase of construction. Very low return air temperatures, harmful vapors and op- eration of the unit with clogged or misplaced filters will damage the unit.

If this unit has been used for heating or cooling of buildings or structures under construction, the following conditions must be met or the warranty will be void:

SThe vent hood must be installed per these installation instructions.

SA room thermostat must control the unit. The use of fixed jumpers that will provide continuous heating or cooling is not allowed.

SA pre−filter must be installed at the entry to the return air duct.

SThe return air duct must be provided and sealed to the unit.

SReturn air temperature range between 55°F (13°C) and 80°F (27°C) must be maintained.

SAir filters must be replaced and pre−filters must be re- moved upon construction completion.

SThe input rate and temperature rise must be set per the unit rating plate.

SThe heat exchanger, components, duct system, air fil- ters and evaporator coil must be thoroughly cleaned following final construction clean−up.

SThe unit operating conditions (including airflow, cool- ing operation, ignition, input rate, temperature rise and venting) must be verified according to these installa- tion instructions.

NOTE − The Commonwealth of Massachusetts stipu- lates these additional requirements:

SGas units shall be installed by a licensed plumber or gas fitter only.

SThe gas cock must be

The Lennox G24−200 furnace may be installed in alcoves, closets, basements, garages and utility rooms.

Page 7

Image 7
Contents WHAT TO DO IF YOU SMELL GAS INSTALLATION INSTRUCTIONS G24-2002P0805 P504613MPage G24−200 Unit Dimensions − inches mmTOP VIEW G24−200 Filter Box Dimensions − inches mmSIDE VIEW BACK VIEWG24−200 HEAT SECTION AND CABINET G24−200 Parts ArrangementPage G24−200 BLOWER SECTION G24−200 Parts Arrangement ContinuedPage G24−200 Gas Furnace SafetyShipping and Packing List setting Combustion, Dilution & Ventilation Air GeneralCements and glues EQUIPMENT IN CONFINED SPACE ALL AIR FROM INSIDE Return Air Plenum / Filter Box Installation Setting EquipmentPage BOTTOM RETURN AIR FILTER BOX INSTALLATIONDuct System Blower Motor / Drive InstallationVenting Venting Using a Masonry Chimney Page Page Page SERVING A SINGLE CATEGORY I APPLIANCEPage SERVING A SINGLE CATEGORY I APPLIANCECOMMON VENT CAPACITY VENT CONNECTOR CAPACITYSERVING TWO OR MORE CATEGORY I APPLIANCES SERVING TWO OR MORE CATEGORY I APPLIANCESPage CARBON MONOXIDE POISONING HAZARD VENT TERMINATION CLEARANCES FOR INSTALLATIONS IN THE USA AND CANADAPage Horizontal Venting Gas Piping FIRE OR EXPLOSION HAZARD Electrical Alternate make-up G24−200 FIELD WIRING DIAGRAM 120V SINGLE PH 60HZAlternate make-up box right sideG24-200FIELD WIRING DIAGRAM Alternate make-up G24−200 FIELD WIRING DIAGRAMG UNITS − 460V 3PH 60HZ J UNITS − 575V 3PH 60HZFIGURE Page G UNITS − 460V 3PH 60HZ WIRING SCHEMATIC DIAGRAM FOR G24−200P UNITS − 208/230V 1PH 60 HZ Y UNITS − 208/230V 3PH 60HZUnit Start−Up Heating Sequence of Operation Other Unit Adjustments and Operation Gas Pressure AdjustmentHigh Altitude Information Temperature Rise Setting blower CFM TABLE DRIVE KIT SPECIFICATIONS TABLE ACCESSORY AIR RESISTANCEPage G24−200 Start−up and Performance Check List Repair Parts ListPage TroubleshootingNORMAL HEATING MODE ABNORMAL HEATING MODELED CODES 3 − OFF NO POWER OR DETECTED FAULTNORMAL HEATING MODE ABNORMAL HEATING MODEPOWER ON THERMOSTAT CALLS FOR HEAT W1 ENERGIZED IS THE S10 S99 HIGH LIMIT CLOSED? YES MANUAL FAN OPERATION COOLING SEQUENCE OF OPERATIONFOR TWO CONDENSING UNITS FOR A SINGLE CONDENSING UNIT