| FIELD |
|
| TITLE and EXPLANATION |
|
|
|
|
|
| |
|
|
|
| AC Loss Report Code | |
| *62 |
|
| ||
|
|
|
| Enter the appropriate report code. Timing of this report is random with up to a | |
|
|
|
| restores before the report goes out, there is no “AC RESTORE” report. | |
|
|
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. | |
|
|
|
| Low Bat Report Code | |
| *63 |
|
| ||
|
|
|
| Enter the appropriate report code; sent when a | |
|
|
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. | |
|
|
|
| Test Report Code | |
| *64 |
|
| ||
|
|
|
| Enter the appropriate report code, which is sent periodically to test that the communicator and phone | |
|
|
|
| lines are operational. Frequency of report is set in Scheduling mode (event 11) or by the following key | |
|
|
|
| commands: installer code + [#] + 0 + 0 = test report sent every 24 hours | |
|
|
|
| installer code + [#] + 0 + 1 = test report sent once per week | |
|
|
|
| installer code + [#] + 0 + 2 = test report sent every 28 days | |
|
|
|
| Each mode sets schedule 2 to the selected repeat option; first test report sent 12 hours after command. | |
|
|
|
| NOTE: Make sure the | |
|
|
|
| command to ensure that test reports are sent when expected. (see Setting the | |
|
|
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. | |
|
|
|
| Open Report Code | |
| *65 |
|
| ||
|
|
|
| Enter the appropriate report code, which is sent upon disarming of the system. | |
|
|
|
| UL: Required for UL commercial burglar alarm installations. | |
|
|
|
| Arm Away/Stay Report Code | |
| *66 |
|
| ||
|
|
|
| Enter appropriate report code. NOTE: “OPEN” reports not sent if associated closing report is not enabled. | |
|
|
|
| RF Trans. Low Batt. Report Code | |
| *67 |
|
| ||
|
|
|
| Enter the appropriate report code; sent when a wireless transmitter | |
|
|
|
| UL installations: must be enabled if wireless devices are used. | |
|
|
|
|
| |
| *68 |
|
| Cancel Report Code | |
|
|
|
| Enter the appropriate report code; sent upon disarming of the system after an alarm was reported. |
*69
Recent Closing Report
Similar to the Exit Error condition described in field *59, but occurs if any burglary zone is faulted within two minutes after the initial exit delay expires. Disarming the system within the two minutes stops the alarm sound and displays " ALARM CANCELED " or "CA" and the faulted zone number. No message is sent to the Central Monitoring Station.
If the system is not disarmed within two minutes, the alarm sound continues and a “recent closing” and a “zone alarm” message are sent to the Central Monitoring Station (after dial delay expires).
| *70 | Alarm Restore Report Code |
|
| Enter the appropriate report code; sent when an alarm zone is restored to its |
|
| |
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. |
|
| Trouble Restore Report Code |
| *71 | |
|
| Enter the appropriate report code, which is sent when a trouble in a zone is restored |
|
| UL: Required for UL commercial burglar alarm installations. |
|
| Bypass Restore Report Code |
| *72 | |
|
| Enter the appropriate report code, which is sent when a zone that has been bypassed is unbypassed. |
|
| UL: Required for UL commercial burglar alarm installations. |
|
| AC Restore Report Code |
| *73 | |
|
| Enter the appropriate report code; sent when AC power has been restored after an AC power outage. |
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. |
|
| Low Bat Restore Report Code |
| *74 | |
|
| Enter the appropriate report code; sent when a system |
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. |
| *75 | RF Xmtr Low Batt. Restore Code |
Enter the appropriate report code; sent when a trans. low battery is restored (new battery installed). UL installations: must be enabled if wireless devices are used. Required for UL commercial burglar alarm installations and required for residential fire alarm installations.