Installation Instructions
*55 |
| Dynamic Signaling Priority |
|
| UL Installations: For UL Commercial Burglary installations that use a DACT and LRR, the DACT must be programmed |
|
| for priority (option “0”). |
|
| Intended for use with Long Range Radio reporting (field ∗29 OUTPUT TO LONG RANGE RADIO must |
|
| be enabled). |
|
| Select the initial reporting destination for messages as follows: |
|
| Primary Dialer First selected (0): |
|
| • If acknowledged before delay expires (see ∗54), then message will not be sent to LRR. |
|
| • If not acknowledged before delay expires, message is sent to both the Primary Phone No. and LRR. |
Long Range Radio First selected (1):
•If acknowledged before delay expires, then message will not be sent to the primary dialer.
•If not acknowledged before delay expires, then message is sent to both Primary Phone No. and LRR.
| *56 | Zone Programming Menu Mode |
|
| Use this menu mode to program zone information. See Zone Programming section for procedures. |
|
| |
|
| Function Key Menu Mode |
| *57 | |
|
| Use this menu mode to program keypad function keys. See Function Key section for procedures. |
|
| Expert Zone Programming Menu Mode |
| *58 | |
|
| This menu mode can be used to quickly program zone information, but is recommended only for those |
already familiar with *56 menu mode. See Zone Programming section for procedures.
System Status Report Codes
Zone report codes are programmed using interactive ✱56 or ✱58 Zone Programming modes, while system status
An entry of 0 in the first box disables a report. Entering 0 in the second box advance to the next field.
Expanded or 4+2 Format: Enter codes in both boxes (first and second digits) for
| FIELD |
|
| TITLE and EXPLANATION |
| ||||||||
|
|
|
| Exit Error Report Code |
| ||||||||
| *59 |
|
|
| |||||||||
|
|
|
| After arming the system, entry/exit and interior zones remaining open after exit delay expires cause an |
| ||||||||
|
|
|
| alarm sound at the keypad and external sounder (keypad also displays “EXIT ALARM”), and entry |
| ||||||||
|
|
|
| delay begins. Disarming before the end of the entry delay stops alarm sounding and no message is sent |
| ||||||||
|
|
|
| to the central station. The keypad displays “CA” |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| If the system is not disarmed before entry delay expires, an “EXIT ALARM” message ( |
|
|
| ||||||
|
|
|
| also zone alarm message) will be sent to the central station if Exit Error Report Code is enabled. The |
| ||||||||
|
|
|
| keypad will display “EA” |
| ||||||||
|
|
|
| continues until the system is disarmed (or timeout occurs). |
| ||||||||
|
|
|
| An Exit Alarm condition will also result if a fault occurs in an exit or interior zone within 2 minutes |
| ||||||||
|
|
|
| following the end of the exit delay, and an “EXIT ALARM” message will be sent to the central station |
| ||||||||
|
|
|
| (except for | , see field *69 Recent Closing report). |
| |||||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
| [1] Always enabled. Also see field *69. |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| *60 | Trouble Report Code |
|
| Enter the appropriate report code, which is sent if a zone has a trouble condition. |
|
| |
|
| UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. |
|
| Bypass Report Code |
| *61 | |
|
| Enter the appropriate report code, which is sent when a zone is manually bypassed. |
UL: Required for UL commercial burglar alarm installations.