Honeywell VISTA-10PSIA Various System Trouble Displays, Alpha Display, Meaning, Fixed Disp

Page 58

Installation Instructions

Panic Keys

There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station by pressing and holding the appropriate key for at least 2 seconds. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses. The Panic keys are identified by the system as follows:

Keys

Displayed as Zone

[A] (/1)

95

[B] (/#)

99

[C] (3/#)

96

IMPORTANT: For a Silent panic function (if programmed) to be of practical value, you must program a report code for the zone and the system must be connected to a central station.

Various System Trouble Displays

Alpha Display

Fixed Disp.

Meaning

ALARM CANCELED

CA

will appear if an exit or interior zone contained a fault during closing at the time

 

 

the Exit Delay ended (e.g., exit door left open), but the system was disarmed during

 

 

the Entry Delay time. The alarm sounder and keypad sound continuously, but stop

 

 

when the system is disarmed. No message will be transmitted to the central station.

EXIT ALARM

EA

will appear when the Exit Delay ends if an exit or interior zone contained a fault

 

 

during closing. The alarm sounder and keypad sound continuously until the system

 

 

is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central

 

 

station.

 

 

Also results if an alarm from an exit or interior zone occurs within 2 minutes after

 

 

the end of an Exit Delay.

CHECK

CHECK

indicates that a problem exists with the displayed zone(s) and requires attention.

ALARM 1xx

1xx

indicates that communication between control and a zone expander or wireless

FAULT 1xx

1xx

receiver is interrupted, where “xx” is the device address. Check the wiring and

CHECK 1xx

1xx

DIP switch settings on the units.

 

91

If field *199 is set to “1,” all ECP module problems are displayed as “91.”

 

 

If there are wireless sensors in the system, the Check condition may also be caused

 

 

by some change in the environment that prevents the receiver from receiving

 

 

signals from a particular sensor.

SYSTEM LO BAT

BAT

with no zone number indicates that the system's main standby battery is weak.

LO BAT

BAT

with a zone number and a once-per-minute beeping at the keypad indicates that a

 

 

low-battery condition exists in the wireless sensor displayed (zone “00” indicates a

 

 

wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display

 

 

may occur.

 

 

NOTE: Some wireless sensors use a non-replaceable long-life battery which requires

 

 

replacement of the entire unit at the end of battery life (e.g., 5802, 5802CP).

Busy-Standby

dl

If this remains displayed for more than 1 minute, the system is disabled.

Modem Comm

CC

The system is in communication with the central station for change of function or

 

 

status verification.

no display

no display

Power Failure

 

 

If there is no keypad display at all and the LEDs are unlit, operating power (AC and

 

 

battery) for the system has stopped and the system is inoperative.

 

 

If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word display

 

 

keypads) is displayed, the keypad is operating on battery power only.

 

 

If the battery standby capacity is used up during a prolonged AC power outage, the

 

 

control's power will shut down to minimize deep discharge of the battery.

Comm. Failure

FC

A communication failure has occurred.

Open Circuit

OC

The keypad is not receiving signals from the control and sees an open circuit.

Long Rng Trbl

bF

Backup LRR communication failure.

Bell Failure

70

Bell supervision failure.

RCVR Jam

90

RF jam detected.

KEYPAD LOW BAT

00 BAT

Wireless keypad low battery

Phone Okay

Cd

The dialer test has been successful (CID code 601).

Dialer Off

dO

The dialer is disabled.

Test in Progress

dd

Walk test mode is active(CID code 607).

Upload Completed

dC

The upload or download session was completed.

Upload Failed

dF

The upload or download session failed before completion.

6-6

Image 58
Contents Ademco VISTA-10P Ademco VISTA-10PSIA Recommendations for Proper Protection Table Of Contents Testing the System Menu Mode ProgrammingSystem Communication and Operation Functions Features and Installation HighlightsCapabilities Compatible DevicesImportant Installation Highlights Installer Please Read Cabinet and Lock Mounting and Wiring the ControlMounting the PC Board Alone no RF Receiver Mounting Board with RF Receiver Mounting the PC Board and RF ReceiverKeypad Addresses Wiring to KeypadsSupplementary Power optional Size MA or less 100 mA 300 mA 500 mA 600 mAWire Run Chart Wiring the AC TransformerBackup Battery Distance from control Wire SizeEarth Ground AC Power Outlet GroundMetal Cold Water Pipe Smoke Detectors Hardwire ZonesWire Smoke Detectors Normally Open Zones/ Normally Open Eolr ZonesInstalling a 5800TM Module Installing the RF ReceiverRF Receiver No. of Zones Installing a Keyswitch Installing the TransmittersTransmitter Battery Life Connecting Relay Modules Keyswitch Wiring ConnectionsOn-Board Triggers On-Board Trigger Connector with 4-Wire CablePhone Line/Phone Module Connections Phone Module Problems Long Range Radio ConnectionsAudio Alarm Verification Connections AAV, listen-In RJ31XAbout Programming To enable keypadsProgramming Overview KeypadsFunction Keys Wireless Receiver, Transmitters, and Wireless Keys keyfobsPager Programming Output DevicesZone Type Definitions Configurable No Alarm ResponseKeyswitch Monitor ZoneExiting the Programming Mode Menu Mode Programming ∗56, *57, ∗58, ∗79, ∗80, ∗81, ∗82Loading Factory Defaults/Initializing for Download Task ProcedureReports as†† Enabled By… Table of Device AddressesAbout Data Field Programming System Setup FieldsData Field Programming Programming Data FieldsZone Sounds & Timing Dialer Programming System Status Report Codes Trouble Restore Report Code Cancel Report CodeAlarm Restore Report Code Bypass Restore Report CodeMiscellaneous System Fields Option Selection Event Log EnablesEvent Log Full Report Code No. of Reports In Armed Period per Zone Swinger SuppressionPager Programming Fields Configurable Zone Type Options Configurable Zone Type Programming FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesKeypad Programming Fields Installation Instructions Zone Programming Overview ∗56 and ∗58 Menu Modes Menu Mode ProgrammingZone Programming Procedure SET to CONFIRM? 0 = no 1 = YESInput S/N Input Type RF TransInput S/N L Xmit to ConfirmCompleting Zone Programming ∗58 Expert Programming Mode ProceduresProgram ALPHA? 0 = no 1 = YES RC in L Wireless Key Programming TemplatesTemplate ? Input S/N AXXX-XXXX Wireless Key Predefined Default TemplatesWireless Key Transmitter Xmit to Confirm Press to Skip∗79 Menu Mode Output Device Programming Overview *79/*80 Menu ModeMenu Mode Output Device Mapping Output Device programming involvesOutput Definition Components Menu Mode Defining Output Functions∗80 Menu Mode Prompt EntryE P Trig Zone List Programming Zone List Overview ∗81 Menu ModeMenu Mode List No Used for…Press the desired function key, A-D Function Key Programming Overview ∗57 Menu ModeProgramming Function Keys Is no longer available to be used as an endProgramming Zone Descriptors Menu mode ∗82 About Descriptor Programming Overview ∗82 Menu ModeWhen defining descriptors ZN 01 Back Door ZN 01 Back D OORZN 01 Back Door Custom?Character Ascii Chart For Adding Custom Words For Entering Zone DescriptorsProgramming Installer and User Schedules System Operation section= group number Installation Instructions System Communication Overview System Communication and OperationReport Code Formats Where Code for Type +1/4+1 Report Standard ExpandedCode Definition Ademco Contact IDMaximum User Security Codes Setting the Real-Time ClockLevel User No Functions Voice Keypads Keypad CommandsKeypad Functions Function DescriptionMeaning Various System Trouble DisplaysAlpha Display Keys Displayed as ZoneChecking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportPhone Modules Specifications & AccessoriesRelay Module Long Range RadioCompatible 5800 Series Transmitters Table Series Transmitter Input Loop IdentificationModel Product Input Type Description 5827 Wireless Keypad Can be used to turn the burglary protection on and offInstallation Instructions Industry Canada Industrie CanadaFederal Communications Commission FCC Part FCC PartUL Notices SIA Quick Reference GuideLimitations and Warranty Limitations of this Alarm System10-2 Index 10-4 Summary of Connections Limited Warranty K0735V3 10/04 Rev. B