Honeywell VISTA-10P Output Device Programming Overview *79/*80 Menu Mode, ∗79 Menu Mode

Page 42

Installation Instructions

Output Device Programming Overview (*79/*80 Menu Mode)

Output Devices: The system supports up to 4 relays plus 2 built-in trigger outputs. These “output devices” are assigned to system-wide output numbers (01-04, 17, 18). Relays are identified by the relay module’s device address and the relay position on the module (i.e. the physical relay number, 1-4, on the module). Built-in triggers are identified by the output number, 17 for Trigger 1 and/or 18 for Trigger 2.Use *79 Menu Mode to assign output numbers and map them to device addresses.

Output Functions: The system also provides up to 12 installer-defined output functions, which can be assigned to any of the physical outputs. Therefore, the action of any one of the outputs can be based on as many of these functions as desired. This lets a single relay perform many functions. Use *80 Menu Mode to define output functions.

Relays are not recommended for life safety applications.

MENU NAVIGATION NOTE: For *79 and *80 menus, press the [] key to accept an entry and advance to the next prompt. Use the [#] key to go back to the last question if needed (to check or change an entry). Press [] to go forward again.

Output Device programming involves:

1.Use *79 Menu Mode to assign module and output numbers and map them to device addresses. NOTE: You must map output devices using *79 Menu Mode before you can use *80 menu Mode.

2.Use *80 Menu Mode to create output definitions, which control the output devices.

*79 Menu Mode: Output Device Mapping

Use this menu to assign the Relay Module device address and specific relay numbers. The system is based on predefined module addresses. The address for the 4204 is 12. Refer to the “Module Address” prompt on the next page and set the module’s address (via module DIP switches) accordingly.

Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following prompts are displayed:

79 Menu Mode

PROMPT

ENTER OUTPUT NO.

00 = QUIT

xx

VALID ENTRIES and EXPLANATION

Enter the logical (or reference) relay number as used in the system.

01-04 = relays; 17-18 = on-board triggers (can be programmed for inverted output; see next prompt).

Use the worksheet on the Programming Form (printed separately) to organize device numbers.

[∗] to continue

17 OUT NORM LOW

 

0 = NO 1 = YES

0

This prompt appears only for Triggers 17 and 18.

0 = no (standard default); sets the trigger output level normally high

1 = yes; sets the trigger output normally low (can be used for resetting 4-wire smoke detectors by connecting trigger wire to the negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as zone type 54, fire zone reset, in *80 Menu mode)

[∗] to return to Output Number prompt (use *80 Menu mode to program the function of the trigger)

XXOUTPUT TYPE

DELETE?0

Enable or delete this output.

0 = delete this output number; 1 = enable output [∗] to continue

 

XX MODULE ADDR

 

Enter the module’s predefined address “12” (set the module’s DIP switches to “12”).

 

07-15

yy

[∗] to continue

 

 

 

 

 

 

 

Enter the actual (or physical) relay number, 1-4, with respect to the Relay Module upon

 

XX REL POSITION

 

 

1-4

zz

which it is located.

 

 

 

[∗] to return to the Output Number prompt for programming the next device

 

 

 

 

 

 

5-6

Image 42
Contents Ademco VISTA-10P Ademco VISTA-10PSIA Recommendations for Proper Protection Table Of Contents Menu Mode Programming Testing the SystemSystem Communication and Operation Functions Features and Installation HighlightsCapabilities Compatible DevicesImportant Installation Highlights Installer Please Read Mounting and Wiring the Control Cabinet and LockMounting the PC Board Alone no RF Receiver Mounting Board with RF Receiver Mounting the PC Board and RF ReceiverKeypad Addresses Wiring to KeypadsSupplementary Power optional Size MA or less 100 mA 300 mA 500 mA 600 mAWire Run Chart Wiring the AC TransformerBackup Battery Distance from control Wire SizeAC Power Outlet Ground Earth GroundMetal Cold Water Pipe Smoke Detectors Hardwire ZonesWire Smoke Detectors Normally Open Zones/ Normally Open Eolr ZonesInstalling the RF Receiver Installing a 5800TM ModuleRF Receiver No. of Zones Installing the Transmitters Installing a KeyswitchTransmitter Battery Life Connecting Relay Modules Keyswitch Wiring ConnectionsOn-Board Trigger Connector with 4-Wire Cable On-Board TriggersPhone Line/Phone Module Connections Phone Module Problems Long Range Radio ConnectionsAudio Alarm Verification Connections AAV, listen-In RJ31XAbout Programming To enable keypadsProgramming Overview KeypadsFunction Keys Wireless Receiver, Transmitters, and Wireless Keys keyfobsPager Programming Output DevicesZone Type Definitions Configurable No Alarm ResponseKeyswitch Monitor ZoneExiting the Programming Mode Menu Mode Programming ∗56, *57, ∗58, ∗79, ∗80, ∗81, ∗82Loading Factory Defaults/Initializing for Download Task ProcedureReports as†† Enabled By… Table of Device AddressesAbout Data Field Programming System Setup FieldsData Field Programming Programming Data FieldsZone Sounds & Timing Dialer Programming System Status Report Codes Trouble Restore Report Code Cancel Report CodeAlarm Restore Report Code Bypass Restore Report CodeMiscellaneous System Fields Option Selection Event Log EnablesEvent Log Full Report Code No. of Reports In Armed Period per Zone Swinger SuppressionPager Programming Fields Configurable Zone Type Options Configurable Zone Type Programming FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesKeypad Programming Fields Installation Instructions Zone Programming Overview ∗56 and ∗58 Menu Modes Menu Mode ProgrammingZone Programming Procedure SET to CONFIRM? 0 = no 1 = YESInput S/N Input Type RF TransInput S/N L Xmit to Confirm∗58 Expert Programming Mode Procedures Completing Zone ProgrammingProgram ALPHA? 0 = no 1 = YES Wireless Key Programming Templates RC in LTemplate ? Input S/N AXXX-XXXX Wireless Key Predefined Default TemplatesWireless Key Transmitter Xmit to Confirm Press to Skip∗79 Menu Mode Output Device Programming Overview *79/*80 Menu ModeMenu Mode Output Device Mapping Output Device programming involvesOutput Definition Components Menu Mode Defining Output Functions∗80 Menu Mode Prompt EntryE P Trig Zone List Programming Zone List Overview ∗81 Menu ModeMenu Mode List No Used for…Press the desired function key, A-D Function Key Programming Overview ∗57 Menu ModeProgramming Function Keys Is no longer available to be used as an endAbout Descriptor Programming Overview ∗82 Menu Mode Programming Zone Descriptors Menu mode ∗82When defining descriptors ZN 01 Back Door ZN 01 Back D OORZN 01 Back Door Custom?Character Ascii Chart For Adding Custom Words For Entering Zone DescriptorsProgramming Installer and User Schedules System Operation section= group number Installation Instructions System Communication and Operation System Communication OverviewReport Code Formats Where Code for Type +1/4+1 Report Standard ExpandedAdemco Contact ID Code DefinitionMaximum Setting the Real-Time Clock User Security CodesLevel User No Functions Voice Keypads Keypad CommandsKeypad Functions Function DescriptionMeaning Various System Trouble DisplaysAlpha Display Keys Displayed as ZoneChecking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportPhone Modules Specifications & AccessoriesRelay Module Long Range RadioSeries Transmitter Input Loop Identification Compatible 5800 Series Transmitters TableModel Product Input Type Description 5827 Wireless Keypad Can be used to turn the burglary protection on and offInstallation Instructions Industry Canada Industrie CanadaFederal Communications Commission FCC Part FCC PartUL Notices SIA Quick Reference GuideLimitations and Warranty Limitations of this Alarm System10-2 Index 10-4 Summary of Connections Limited Warranty K0735V3 10/04 Rev. B