Honeywell VISTA-10PSIA, Ademco Security Systems setup guide Dialer Programming

Page 27

Dialer Programming

 

FIELD

 

 

TITLE and EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PABX Access Code

 

 

*40

 

 

 

 

 

 

 

Enter the PABX code, if used. To clear entries from field, press ∗40∗. If fewer than 6 digits need to be

 

 

 

 

 

entered, exit by pressing [∗], which advances to the next field.

 

 

 

 

 

Call Waiting: If the subscriber’s phone service has “call waiting” (and is not using PABX), enter “*70”

 

 

 

 

 

(“# + 11”) plus “# + 13” (pause) as the PABX entry to disable “call waiting” during control panel calls. If

 

 

 

 

 

the subscriber does not have “call waiting” and is not using PABX, make no entry in this field.

 

 

 

 

 

Important: 1. The call waiting disable feature cannot be used on a PABX line. 2. Using Call Waiting

 

 

 

 

 

Disable on a non-call waiting line will prevent successful communication to the central station.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If call waiting is used, enter call waiting disable digits as described above, and also set

 

 

 

 

 

 

 

 

VISTA-10PSIA:

 

 

 

 

 

 

Call Waiting Disable option in field *91.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*41

Primary Phone No.

 

 

Enter the primary phone number. If you enter fewer than 20 digits, exit by pressing [∗]. To clear

 

 

 

 

entries from field, press ∗41∗.

 

 

NOTE: Backup reporting (8 calls are made to the secondary phone number if no kissoff is received

 

 

after 8 attempts to the primary number) is automatic only if there is a secondary number (field ∗42).

 

*42

 

 

Secondary Phone No.

 

 

 

 

Enter the secondary phone number. If you enter fewer than 20 digits, exit by pressing [∗]. To clear

 

 

 

 

 

 

entries from field, press ∗42∗. See backup reporting note for field ∗41. Don’t fill unused spaces.

 

 

 

 

Primary Subs. Acct. No.

 

*43

 

 

 

 

Enter the primary subscriber account number. To clear entries from field, press ∗43∗.

 

 

 

 

Secondary Subs. Acct. No.

 

*44

 

 

 

 

Enter the secondary subscriber account number. To clear entries from field, press ∗44∗.

 

 

 

 

Phone System Select

 

*47

 

 

 

 

Select whether the system will be using pulse or tone dialing, and whether it is on a WATS line.

 

 

 

 

Report Format (Primary/Secondary)

 

*48

 

 

 

 

Select the report format for primary/secondary phone lines from the list on the Programming Guide.

 

 

 

 

Split/Dual Reporting

 

*49

 

 

 

 

Select the desired type of reports to be sent to the primary/secondary numbers. Make selection from the

 

 

 

 

table in the Programming Guide. If “0” selected, all reports go only to the primary number unless

 

 

 

 

unsuccessful, then control will attempt to dial secondary number.

 

 

 

 

Burglary Dialer Delay

 

*50

 

 

 

 

Enter the desired delay time (none, 15, 30, or 45 seconds) before a “BURGLARY ALARM” report is sent

 

 

 

 

to the central station. This delay allows time for the subscriber to avoid sending a false alarm if the

 

 

 

 

alarm was inadvertently caused. This delay does not apply to zone type 24 alarms (silent burglary) or

 

 

 

 

to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent

 

 

 

 

as soon as they occur. UL: must be “0”; SIA Guidelines: delay must be minimum of 30 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VISTA-10PSIA:

Delay Time: 1 = 15 secs; 2 = 30 secs; 3 = 45 secs

 

 

 

 

 

 

 

Delay Disable:

0 = use delay set in entry 1

 

 

 

 

 

 

 

1 = dial delay disabled for zones listed in zone list 6 (use zone list 6 to enter those zones that

 

 

 

 

 

 

 

require dial delay to be disabled; these zones ignore the setting in entry 1)

 

 

 

 

 

 

 

UL: Dial delay plus entry delay must not exceed one minute; use zone list 6 to disable dial delay

 

 

 

 

 

 

 

from appropriate zones, if necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SESCOA/Radionics Select

 

*53

 

 

 

 

 

 

Select whether SESCOA format is used.

 

*54

 

 

Dynamic Signaling Delay (Intended for use with Long Range Radio reporting)

Enter the desired time (0-255 seconds in 15-second increments) the panel should wait, per message, for acknowledgment from the first reporting destination (see ∗55) before it attempts to send a message to the second destination. Entering ”0” sends redundant reports to both Primary Dialer and LRR.

UL Installations: For Fire Alarm and UL Burglar Alarm installations without Line Security (Grade A), the maximum Dynamic Signaling Delay must be no more than 15 seconds.

For UL Burglar Alarm installations with Line Security (Grade AA), Dynamic Signaling Delay must be “0”. The reports will be sent to both the dialer and the LRR.

4-3

Image 27
Contents Ademco VISTA-10P Ademco VISTA-10PSIA Recommendations for Proper Protection Table Of Contents Menu Mode Programming Testing the SystemSystem Communication and Operation Compatible Devices Features and Installation HighlightsCapabilities FunctionsImportant Installation Highlights Installer Please Read Mounting and Wiring the Control Cabinet and LockMounting the PC Board Alone no RF Receiver Mounting the PC Board and RF Receiver Mounting Board with RF ReceiverSize MA or less 100 mA 300 mA 500 mA 600 mA Wiring to KeypadsSupplementary Power optional Keypad AddressesDistance from control Wire Size Wiring the AC TransformerBackup Battery Wire Run ChartAC Power Outlet Ground Earth GroundMetal Cold Water Pipe Normally Open Zones/ Normally Open Eolr Zones Hardwire ZonesWire Smoke Detectors Smoke DetectorsInstalling the RF Receiver Installing a 5800TM ModuleRF Receiver No. of Zones Installing the Transmitters Installing a KeyswitchTransmitter Battery Life Keyswitch Wiring Connections Connecting Relay ModulesOn-Board Trigger Connector with 4-Wire Cable On-Board TriggersPhone Line/Phone Module Connections Long Range Radio Connections Phone Module ProblemsRJ31X Audio Alarm Verification Connections AAV, listen-InKeypads To enable keypadsProgramming Overview About ProgrammingOutput Devices Wireless Receiver, Transmitters, and Wireless Keys keyfobsPager Programming Function KeysZone Type Definitions Monitor Zone No Alarm ResponseKeyswitch ConfigurableTask Procedure Menu Mode Programming ∗56, *57, ∗58, ∗79, ∗80, ∗81, ∗82Loading Factory Defaults/Initializing for Download Exiting the Programming ModeTable of Device Addresses Reports as†† Enabled By…Programming Data Fields System Setup FieldsData Field Programming About Data Field ProgrammingZone Sounds & Timing Dialer Programming System Status Report Codes Bypass Restore Report Code Cancel Report CodeAlarm Restore Report Code Trouble Restore Report CodeMiscellaneous System Fields No. of Reports In Armed Period per Zone Swinger Suppression Event Log EnablesEvent Log Full Report Code Option SelectionPager Programming Fields Zone Type 90 Report Codes Configurable Zone Type Programming FieldsConfigurable Zone Type Configurable Zone Type OptionsZone Conditions Represented Entries Configurable Zone Type ChartsKeypad Programming Fields Installation Instructions SET to CONFIRM? 0 = no 1 = YES Menu Mode ProgrammingZone Programming Procedure Zone Programming Overview ∗56 and ∗58 Menu ModesXmit to Confirm Input Type RF TransInput S/N L Input S/N∗58 Expert Programming Mode Procedures Completing Zone ProgrammingProgram ALPHA? 0 = no 1 = YES Wireless Key Programming Templates RC in LTemplate ? Xmit to Confirm Press to Skip Wireless Key Predefined Default TemplatesWireless Key Transmitter Input S/N AXXX-XXXXOutput Device programming involves Output Device Programming Overview *79/*80 Menu ModeMenu Mode Output Device Mapping ∗79 Menu ModePrompt Entry Menu Mode Defining Output Functions∗80 Menu Mode Output Definition ComponentsE P Trig List No Used for… Zone List Overview ∗81 Menu ModeMenu Mode Zone List ProgrammingIs no longer available to be used as an end Function Key Programming Overview ∗57 Menu ModeProgramming Function Keys Press the desired function key, A-DAbout Descriptor Programming Overview ∗82 Menu Mode Programming Zone Descriptors Menu mode ∗82When defining descriptors Custom? ZN 01 Back D OORZN 01 Back Door ZN 01 Back DoorFor Entering Zone Descriptors Character Ascii Chart For Adding Custom WordsSystem Operation section Programming Installer and User Schedules= group number Installation Instructions System Communication and Operation System Communication OverviewReport Code Formats Code for Type +1/4+1 Report Standard Expanded WhereAdemco Contact ID Code DefinitionMaximum Setting the Real-Time Clock User Security CodesLevel User No Functions Function Description Keypad CommandsKeypad Functions Voice KeypadsKeys Displayed as Zone Various System Trouble DisplaysAlpha Display MeaningSystem Test Testing the SystemAbout Test Procedures Checking Transmitter Enrollment Sniffer ModeAutomatic Periodic Test Report Go/No Go Test ModeAutomatic Standby Battery Tests Dialer Communication Test and Periodic Test ReportsLong Range Radio Specifications & AccessoriesRelay Module Phone ModulesSeries Transmitter Input Loop Identification Compatible 5800 Series Transmitters TableModel Product Input Type Description Can be used to turn the burglary protection on and off 5827 Wireless KeypadInstallation Instructions FCC Part Industrie CanadaFederal Communications Commission FCC Part Industry CanadaSIA Quick Reference Guide UL NoticesLimitations of this Alarm System Limitations and Warranty10-2 Index 10-4 Summary of Connections K0735V3 10/04 Rev. B Limited Warranty