S E C T I O N 5
Menu Mode Programming
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Zone Programming Overview (∗56 and ∗58 Menu Modes)
Use ✱56 Zone Programming to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers, and identify the type of loop input device(s). This mode can also be used to enter alpha descriptors for programmed zones; however, we recommend entering descriptors in menu mode ✱82 (Alpha Descriptor Programming) after all zone programming has been completed. ✱58 Expert Programming Mode offers a faster method of zone programming for those who have had previous experience in programming control panels of this type.
✱56 Zone Programming Procedure
Zone Programming involves:
1.Entering the zone number to be programmed;
2.Making appropriate entries at the prompts;
3.Confirming the serial number of wireless transmitter zones.
Start Zone Programming mode by pressing ✱56 while in Data Programming mode. The following prompts are displayed:
| PROMPT | VALID ENTRIES and EXPLANATION |
|
|
|
SET TO CONFIRM? 0 = NO 1 = YES
If 1 (Yes) is entered, you will be prompted to confirm each transmitter after entering the serial and loop numbers (at the “XMIT TO CONFIRM” prompt later in this procedure). We
recommend that you confirm the programming of every transmitter.
Enter Zn Num. |
|
(00 = Quit) | 10 |
Enter the zone number that you wish to program (e.g. zone 10 as shown in the display). wired zones
Enter a report code for zone 91 to enable addressable device reporting. Enter a report code for zone 92 to enable duress reporting.
95, 96, 99 are emergency (panic) key zones.
00 to quit; [∗] to continue
Zn ZT RC In: L
10 00 10 RF: 1
A summary display appears.
“IN: L” appears for wireless zones and indicates input type and loop.
“HW: RT” appears for hardwire zones and indicates configuration (EOL, NO, NC,) and response time selection.
[∗] to continue
10 Zone Type
Perimeter 03
Each zone must be assigned to a zone type (list below), which defines the way in which the system responds to faults in that zone.
Note: If 00 is entered, Delete Zone ? will be displayed.
00 | = Not used | 07 | = | 20 | = |
01 | = Entry/exit #1 | 08 | = | 21 | = |
02 | = Entry/exit #2 | 09 | = Fire | 22 | = Disarm* |
03 | = Perimeter | 10 | = Interior w/Delay | 23 | = No Alarm Resp |
04 | = Interior Follower | 12 | = Monitor Zone | 24 | = Silent Burglary |
05 | = Trouble Day/Alarm Night | 14 | = Carbon Monoxide | 77 = Keyswitch | |
06 | = | 16 | = Fire w/Verify | 81 | = AAV Monitor Zone |
*5800 |
| 90 | = Configurable |