P35i Fireplace Insert
E. Existing Fireplace, Rear Vent:
The top of the chimney must also be sealed. Otherwise, it can become a nesting area or a water trap.
NOTE: When installed in a rear vent configuration, the maximum BTU may be reduced due to elevated ESP temperatures associated with the horizontal exhaust stream.
F.Optional Zero Clearance Cabinet Installation:
If passing through combustible material, the proper thimble from the vent manufacturer must be used.
wallMasonry
If installing using the optional zero clearance cabinet, Item
If finishing the interior with stone or masonry, the venting can be installed without the appliance. Install the cabinet and secure the venting using the Flue
Notice the side edges of the surround contain slotted openings. These openings allow room air to be drawn into the rear of the cabinet and circulated through the heat exchange and back into the room. These openings can not be blocked. If finishing with stone or
masonry keep the masonry a minimum of one inch from the sides of the surround. Mortar can be used to give a more finished look.
used in a constructed chase | to combustibles are met. |
Vertical Venting may be | providing all clearances |
|
|
Proper wall
3" Clearance
Vent pipe seams must be accessible.
16 Pellets or Corn/Pellet Mixture Only | Save These Instructions |