C.Venting Requirements and Restrictions

P35i Fireplace Insert

C.Venting Requirements and Restrictions

A combustion blower is used to extract the combus- tion gases from the firebox. This causes a negative pres- sure in the firebox and a positive pressure in the venting system. The longer the vent pipe and more elbows used in the system, the greater the flow resistance.

The recommended maximum flue lengths for the P35i Insert are as follows:

3" or 4" Stainless Steel Flex: 30 Lineal ft. Vertical*

4" PL Vent Pipe:

4" Pl Vent Pipe: 30 Lineal ft. Vertical*

4" Pl Vent Pipe: 14 ft. Vertical w/1-90oand 12 lineal ft. horizontal*

If additional 4" PL Vent fittings are required, the overall length must be reduced by:

Vertical 90o or T:

2.5'

Vertical 45o:

1.5'

Horizontal

90o or T:

5.0'

Horizontal

45o:

2.5'

3" PL Vent Pipe:

20 Lineal ft. vertical*

8 Lineal ft. vertical w/1-90o& 8 lineal ft. horizontal*

If additional 3" PL Vent fittings are required, the overall length must be reduced by:

Vertical 90o or T:

2.0'

Vertical 45o:

1.0'

Horizontal

90o or T:

4.0'

Horizontal

45o:

2.0'

*Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more frequent cleaning due to fly ash falling off inside and collecting directly above the combustion blower outlet.

Any use of horizontal venting will require more frequent cleaning. It is the responsibility of the installer to make sure the entire flue configuration is accessible for cleaning.

Stainless steel flex vent is only allowed for use in masonry fireplaces and chimneys or in factory built wood burning fireplace installations when used as a liner for a class A metal chimney. All pellet vent pipe must be secured together by means provided by pipe manufac- turer. The vent pipe must be secured to the appliance flue collar with a minimum of three screws.

It is also recommended that you seal all vent pipe joints with high temperature silicone.

Use only the specified venting components. Use of any other components will void the product warranty and may pose a hazard.

Do Not Install A Flue Damper In The Exhaust Venting System Of This Appliance.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

NOTE: If burning a shelled corn and pellet mixture, you must use approved venting components that are specifically designed for corn burning.

WARNING! RISK OF FIRE!

Only LISTED type L or PL Pellet venting compo- nents may be used.

NO OTHER type of venting materials or compo- nents may be used.

Substitute or damaged vent components may impair safe operation.

WARNING! RISK OF INJURY OR PROPERTY DAMAGE!

Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage.

Read and Refer to your owner's manual.

For assistance or additional information, consult a qualified installer, service agency or your dealer.

IN CANADA: This fireplace insert must be installed with a continuous chimney liner of a minimum 3" diameter extending from the insert to the top of the chimney. The chimney liner must conform to the Class 3 requirements of CAN/ULC- S635, Standard for Lining Systems for Existing Masonry or Factory Built Chimneys and Vents, or CAN/ULC-S640, Standard for Lining Systems for New Masonry Chimneys.

14 Pellets or Corn/Pellet Mixture Only

3-90-775

Save These Instructions

Image 14
Contents Discard SAVE THESE INSTRUCTIONSModel Installed, a House Fire May Result TABLE OF CONTENTS 1Listing and Code Approvals E. BTU & Efficiency SpecificationsC. Glass Specifications A. Appliance CertificationSPECIAL NOTE 2Special Warnings and Notes3Getting Started A. Design, Installation & Location ConsiderationsB. Fire Safety Hopper Lid Latch C. Component LocationsP35i Fireplace Insert GlassD. Pre- Use Check List Fire Risk60.96 cm 4Dimensions & ClearancesA. Appliance Dimensions P35i Fireplace InsertMasonry or Manufactured Fireplace B. Clearances To CombustiblesD. Minimum Opening for Masonry and Manufactured FireplacesF. Factory-BuiltFireplace Installation Vent Information A. Vent Termination RequirementsVent Configurations B. Avoiding Smoke and OdorsNegative Pressure, Shut-down,and Power Failure Outside AirWARNING! RISK OF INJURY OR PROPERTY DAMAGE C.Venting Requirements and RestrictionsWARNING! RISK OF FIRE Sealing Plate D. Existing Fireplace InstallationNon-combustible Insulation Vent pipe seams must be accessible F.Optional Zero Clearance Cabinet InstallationE. Existing Fireplace, Rear Vent A. Mobile Home Installation 6Mobile Home7Appliance Set-Up A. Outside Air AttachmentB. Installing the Surround C. Routing the Power CordD. Securing the Mounting Frame E. Attaching the VentingH. Room Sensor Installation F.Installing the Body into the Mounting FrameG. Control Board Installation J. Optional Trim Kit- #1-00-00775 K. Service Rail Kit- #1-00-774125I. Optional Log Kit Instructions A. Fire SafetyOperating B. Fuel and Fuel Storage2. Circuit Board C. General Operating Information1. ESP Exhaust Sensing Probe e. Igniter Mode Switch a. Feed Rate Adjustmentd. Blower Speed Adjustment b. Mode SelectionF. Starting a Fire - MANUAL E. Draft Test ProcedureD. Before Your First Fire I. Relaxation Mode G. Starting a Fire - AUTOMATICH. Maintaining the Fire J. Shut-DownSymptom TroubleshootingError Message Possible CauseB. Quick Reference Maintenance Chart Service & MaintenanceA. Shut-downProcedure CAUTION! SHOCK AND SMOKE HAZARDC.General Maintenance Procedures WARNING! RISK OF FIRE 5.Cleaning Area Beneath Burn Pot Grate5.Cleaning Heat Exchanger & Exhaust By User6.Inspect / Clean Hopper By User8.Venting and Chimney System 7.Cleaning the Door GlassBy User Soot and Fly Ash Formation & Need for RemovalHopper Lid Latch D. Motors and ComponentsP35i Fireplace Insert Glass3.ESP- Exhaust Sensing Probe 1.Feed Motor2.Combustion Blower 4.Distribution Blower 5.Feeder Body6.Igniter P35i Fireplace Insert 11Reference MaterialsPLUG PIN 11 WHITE Addendum P35i Fireplace Insert9 10 11 12 13 P35i Pellet InsertPellet Insert 4 5 6Description #4 Surround AssemblyP35i Pellet Insert COMMENTSCOMMENTS P35i Pellet InsertDescription PART NUMBERCOMMENTS P35i Pellet InsertDescription PART NUMBERD. Custom Size Surround P35i Custom Surround Part #: 1-00-774221-SPLWARRANTY PERIOD LIMITED LIFETIME WARRANTYWARRANTY COVERAGE Hearth & Home Technologies IncThis warranty is void if WARRANTY CONDITIONSWARRANTY EXCLUSIONS LIMITATIONS OF LIABILITYDescription Of Service Service & Maintenance LogDate Of Service P35i Fireplace InsertProudly Printed On 100% Recycled Paper