Harman Stove Company P35I owner manual F. Factory-BuiltFireplace Installation

Page 11
F. Factory-Built Fireplace Installation

P35i Fireplace Insert

F. Factory-Built Fireplace Installation

When installing the P35i Insert into a factory built wood burning fireplace, several things need to be taken into consideration.

The size of the fireplace opening. Will the unit fit into the opening? Some of the factory built fireplaces have metal smoke shields inside the top that can be removed to gain height. Keep in mind that anything removed from the factory built fireplace must be attached to the fireplace with a metal wire. Floor protection guidelines, as listed previously, must also be followed.

The manufactured fireplace may not be altered be- yond the exceptions listed below. Never remove masonry bricks or mortar from an existing fireplace.

The following modifications are permissible:

Removal of the damper or lock in open position

Removal of smoke shelf or baffle

Removal of andirons or ember catchers

Removal of log grate

Removal of view screen or curtain

Removal of doors

External trim pieces, that do not affect the operation of the fireplace, may be removed providing they can be stored on or within the fireplace for reassembly if the insert is removed.

If the hearth extension is lower than the fireplace opening, the portion of the insert extending onto the hearth must be supported.

Final approval of this type of installation is contingent upon the authority having jurisdiction.

Hearth must be constructed to the proper height and finished with a non-combustible material.

The factory built chimney must be listed per UL 127 (US) and meet type HT requirements of UL 103 (US). Factory Built fireplace chimneys tested to UL 127-98 may be, at the fireplace manufacturers option, tested to the same criteria as UL 103HT requirements. If the chimney is not listed as meeting HT requirements, or if the factory built fireplace was tested prior to 1998, a full height listed chimney liner must be installed from the appliance flue collar to the chimney top. Liner must meet high temperature (2100 F) per UL1777 (US). The liner must be securely attached to both the flue collar and the chimney cap. To prevent room air passage to the chimney cavity of the fireplace, seal the damper area around the chimney liner with fiberglass batting.

IN CANADA: This fireplace insert must be installed with a continuous chimney liner of a minimum 3" diameter extending from the insert to the top of the chimney. The chimney Manual background liner must conform to the Class 3 requirements of CAN/ULC-S635, Standard for Lining Systems for Existing Masonry or Factory Built Chimneys and Vents, or CAN/ULC- S640, Standard for Lining Systems for New Masonry Chimneys.

When using single-wall

venting or flex,this section

of venting must be wrapped

with a non-combustible

insulation to prevent excess

temperatures within the

fireplace and on the fuel

hopper.

Note: If the Harman P35i Insert is installed into a factory built wood burning fireplace, this label (Harman part # 3-90-00675) must be attached to the altered fireplace.

Save These Instructions

3-90-775

Pellets or Corn/Pellet Mixture Only

11

Image 11
Contents Discard SAVE THESE INSTRUCTIONSModel Installed, a House Fire May Result TABLE OF CONTENTS A. Appliance Certification E. BTU & Efficiency SpecificationsC. Glass Specifications 1Listing and Code Approvals2Special Warnings and Notes SPECIAL NOTE3Getting Started A. Design, Installation & Location ConsiderationsB. Fire Safety Glass C. Component LocationsP35i Fireplace Insert Hopper Lid LatchFire Risk D. Pre- Use Check ListP35i Fireplace Insert 4Dimensions & ClearancesA. Appliance Dimensions 60.96 cmand Manufactured Fireplaces B. Clearances To CombustiblesD. Minimum Opening for Masonry Masonry or Manufactured FireplaceF. Factory-BuiltFireplace Installation A. Vent Termination Requirements Vent InformationOutside Air B. Avoiding Smoke and OdorsNegative Pressure, Shut-down,and Power Failure Vent ConfigurationsWARNING! RISK OF INJURY OR PROPERTY DAMAGE C.Venting Requirements and RestrictionsWARNING! RISK OF FIRE Sealing Plate D. Existing Fireplace InstallationNon-combustible Insulation Vent pipe seams must be accessible F.Optional Zero Clearance Cabinet InstallationE. Existing Fireplace, Rear Vent 6Mobile Home A. Mobile Home InstallationA. Outside Air Attachment 7Appliance Set-UpC. Routing the Power Cord B. Installing the SurroundE. Attaching the Venting D. Securing the Mounting FrameH. Room Sensor Installation F.Installing the Body into the Mounting FrameG. Control Board Installation J. Optional Trim Kit- #1-00-00775 K. Service Rail Kit- #1-00-774125I. Optional Log Kit B. Fuel and Fuel Storage A. Fire SafetyOperating Instructions2. Circuit Board C. General Operating Information1. ESP Exhaust Sensing Probe b. Mode Selection a. Feed Rate Adjustmentd. Blower Speed Adjustment e. Igniter Mode SwitchF. Starting a Fire - MANUAL E. Draft Test ProcedureD. Before Your First Fire J. Shut-Down G. Starting a Fire - AUTOMATICH. Maintaining the Fire I. Relaxation ModePossible Cause TroubleshootingError Message SymptomCAUTION! SHOCK AND SMOKE HAZARD Service & MaintenanceA. Shut-downProcedure B. Quick Reference Maintenance ChartC.General Maintenance Procedures By User 5.Cleaning Area Beneath Burn Pot Grate5.Cleaning Heat Exchanger & Exhaust WARNING! RISK OF FIREBy User 6.Inspect / Clean HopperSoot and Fly Ash Formation & Need for Removal 7.Cleaning the Door GlassBy User 8.Venting and Chimney SystemGlass D. Motors and ComponentsP35i Fireplace Insert Hopper Lid Latch3.ESP- Exhaust Sensing Probe 1.Feed Motor2.Combustion Blower 5.Feeder Body 4.Distribution Blower6.Igniter P35i Fireplace Insert 11Reference MaterialsPLUG PIN 11 WHITE P35i Fireplace Insert Addendum4 5 6 P35i Pellet InsertPellet Insert 9 10 11 12 13COMMENTS #4 Surround AssemblyP35i Pellet Insert DescriptionPART NUMBER P35i Pellet InsertDescription COMMENTSPART NUMBER P35i Pellet InsertDescription COMMENTSP35i Custom Surround Part #: 1-00-774221-SPL D. Custom Size SurroundHearth & Home Technologies Inc LIMITED LIFETIME WARRANTYWARRANTY COVERAGE WARRANTY PERIODLIMITATIONS OF LIABILITY WARRANTY CONDITIONSWARRANTY EXCLUSIONS This warranty is void ifP35i Fireplace Insert Service & Maintenance LogDate Of Service Description Of ServiceProudly Printed On 100% Recycled Paper