L.Install Horizontal Termination Cap (DVP and SLP Pipe)
WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.
•
Failure to maintain overlap may cause overheating and fire.
• | Vent termination must not be recessed in the wall. Siding |
| may be brought to the edge of the cap base. |
• | Flash and seal as appropriate for siding material at |
| outside edges of cap. |
Note: When using termination caps with
| HEAT SHIELD OR | HEAT SHIELD | |
| EXTENDED | ||
| |||
| HEAT SHIELD | ||
WALL SHIELD | OVERLAP | ||
| |||
|
| ||
FIRESTOP |
|
|
SLIP SECTION
CAN BE EXTENDED
• When installing a horizontal termination cap, follow |
the cap location guidelines as prescribed by current |
INNER VENT
OUTER VENT
SHEATHING
ANSI Z223.1 and |
and refer to Section 6 of this manual. |
CAUTION! Risk of Burns! Local codes may require in- stallation of a cap shield to prevent anything or anyone from touching the hot cap.
NOTICE: For certain exposures which require superior resistance to
INTERIOR | EXTERIOR |
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
(SEE CHART BELOW)
Figure 10.20 Venting through the wall
Cap Specification Chart
(depth without using additional pipe sections)
| |||||
| Top Vent | Rear Vent | Top Vent | Rear Vent | |
| Depth | Depth | Depth | Depth | |
| |||||
6000 | 5 in. | ||||
|
|
|
| ||
Series |
|
|
|
| |
|
| ||||
| |||||
| Top Vent | Rear Vent | Top Vent | Rear Vent | |
| Depth | Depth | Depth | Depth | |
| |||||
| 9 in. |
46 | Heat & Glo • |