Heat & Glo LifeStyle BE-41C 787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 127 mm, 302 mm, 146 mm

Page 64

B. Vent Components Diagrams (continued)

 

 

 

 

 

31 in.

 

 

 

 

 

 

(787 mm)

 

 

13-1/4 in.

 

 

 

 

 

 

(367 mm)

 

 

24-5/8 in.

 

 

 

 

 

 

(625 mm)

 

 

 

24-5/8 in.

27-1/2 in.

 

 

 

 

 

(625 mm)

(127 mm)

 

 

 

13-1/4 in.

 

 

 

 

 

 

 

 

 

 

 

(367 mm)

 

RF6M

 

 

 

RF12M

 

 

Roof Flashing Multi-pak

 

 

 

 

 

 

 

Roof Flashing Multi-pak

 

 

 

 

 

 

 

13-3/4 in.

5 in.

 

 

11-7/8 in.

5 in.

 

(349 mm)

(127 mm)

 

 

(302 mm)

(127 mm)

 

13-3/4 in.

 

 

13-7/8 in.

 

 

 

 

 

(352 mm)

 

 

 

(349 mm)

 

 

 

 

 

 

 

 

 

 

 

BEK

 

 

 

DVP-BEK2

 

 

Trap Cap Brick Extension

 

DVP-HPC Cap Brick Extension

 

 

 

11-5/8 in.

 

 

 

 

 

 

(295 mm)

 

 

 

 

 

7-1/8 in.

 

12-1/8 in.

 

 

 

 

 

(308 mm)

 

 

 

 

(181 mm)

 

 

 

 

 

 

 

 

 

 

DVP-TRAPFL

 

5-3/4 in.

 

 

 

 

 

(146 mm)

COOL-ADD

 

 

Flashing

 

 

 

 

 

 

 

 

 

Cap Shield

 

 

 

 

 

 

 

26 in.

 

 

13-7/8 in.

9-1/2 in.

 

 

 

 

(352 mm)

(241 mm)

 

 

660 mm

 

 

 

 

 

 

 

 

14 in.

 

 

 

 

DVP-HSM-B

 

(356 mm)

 

 

 

 

Extended Heat Shield

 

 

 

 

 

 

Figure 16.4 DVP vent components

 

 

DRC-RADIUS

 

 

 

 

Cap Shield

 

 

 

 

 

 

64

Heat & Glo • BE-41C / LP,

BE-41IPIC / LP • 2105-900 Rev. P • 6/09

 

Image 64
Contents What to do if you smell gas Hot glass will cause burnsCongratulations Homeowner Reference InformationTable of Contents User GuideAppliance Setup TroubleshootingFinishing Reference MaterialsLimited Lifetime Warranty Limited Lifetime Warranty Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsOperating Instructions User Guide Gas Fireplace SafetyYour Fireplace Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesFan Kit optional Clear SpaceTurn off all electric power to the appliance On position. The ON/OFF switch mayLighting Instructions IPI Final inspection byFor Your Safety Read Before Lighting Lighting Instructions Lighting Instructions Standing PilotFrequently Asked Questions After Fireplace is LitMaintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Qualified Service Technician Gasket Seal and Glass Assembly InspectionVenting LogsEither cobrahead or SIT Getting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Any such action may cause a fire hazardFraming and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesCombustible Mantels Mantel and Wall ProjectionsCombustible Mantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Vent Information and Diagrams Approved PipeVent Table Key Use of ElbowsVent Diagrams Top Vent Horizontal Termination One ElbowTwo Elbows V1 Minimum H1 MaximumTop Vent Horizontal Termination Three Elbows Min MaxBreak Here Top Vent Vertical Termination Maximum + V 2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumHeat & Glo BE-41C / LP, BE-41IPIC / LP 2105-900 Rev. P 6/09 H1 Maximum V1 Minimum H1 + H2 Maximum Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Max Rear Vent Vertical Termination One Elbow H1 + H2 Maximum V1 MinimumRear Vent Vertical Termination Three Elbows V1 Minimum H1 + H2 + H3Vent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Appliance Preparation Top VentRear Vent Cut the metal retaining band and fold the sides outInstalling the Non-combustible Board Securing and Leveling the ApplianceInstalling Vent Pipe DVP and SLP Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections DVP Pipe Only Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall Decorative Wall Components SLP only Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination Ansi Z223.1 and CAN/CGA-B149 installation codes Install Horizontal Termination Cap DVP and SLP PipeRefer to of this manual Gas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements IntelliFire Ignition System WiringStanding Pilot Ignition System Wiring Optional Accessories RequirementsElectrical Service and Repair IntelliFire Pilot Ignition IPI Wiring DiagramJunction Box Installation Wall Switch Installation for Fan OptionalFinishing Facing MaterialDoors Finish Door FIT Material See Maximum ThicknessAppliance Setup LOG Assembly LOGS-6000BE Install the Log AssemblyLog Placement Tabs Install Trim and/or Surround Air Shutter SettingAir Shutter Settings BurnerSymptom Possible Causes Corrective Action TroubleshootingStanding Pilot Ignition System Troubleshooting Symptom Possible Cause Corrective ActionIntelliFire Ignition System Ues to spark, and main Reference Materials Appliance Dimension DiagramLocation Inches Millimeters Vent Components Diagrams DVP vent componentsHorizontal Termination Cap DVP vent components787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 127 mm Roof Flashing Multi-pak 13-3/4 11-7/8 349 mm302 mm 13-3/4 13-7/8 352 mm 349 mmDVP-TVHW DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP 165 mm 222 mm 168 mm Elbow Effective Height LengthHorizontal Pipe Support 2 in mm 152 mm 8 in mm 251 mm SLP-90ST 90 ElbowCathedral Ceiling SnorkelSupport Box-Black Termination Cap Ceiling FirestopContact Information