14
VENTING INSTALLATION
Installation for Horizontal Termination (Cont.)
VENTING INSTALLATION
Continued
3.Attach vent pipe assembly to the burner system. Set stove in front of it’s permanent location to insure minimum clearances. Mark the wall for a 10"(25.4cm) square hole (for noncombus- tible material such as masonry block or concrete, a 7 1/2" (19.1cm) diameter hole is acceptable). See Figure 25. The center of the hole should line up with the
4.Noncombustible Exterior Wall: Apply a bead of
WARNING: Do not recess vent termination in to any wall. This will cause a fire hazard.
Combustible Exterior Wall: For vinyl siding, stucco, or wood exteriors, a siding standoff must be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging siding materials. Siding materials must be cut to accommodate standoff. Bolt the vent cap to the stand- off. Apply
6.Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 1 1/4" (3.2cm). Fasten all vent pipe connections (except vent cap) with screws provided.
7.Combustible Exterior Wall Only: Slide the wall firestop against the interior wall surface and attach with screws pro- vided (see Figure 28).
Vent Cap
Wood Screw
Figure 26 - Installing Horizontal Vent Cap (Noncombustible Exterior)
Cut Vinyl Siding
Away to Fit Standoff
Standoff
Wood Screw
5.Combustible Exterior Wall Only: Slide the interior wall firestop over the vent pipe before connecting the horizontal run to the vent cap (see Figure 28).
Apply Mastic
to All Four Sides
Vent Cap
Bolt
Figure 25 - Vent Opening Requirements
Figure 27 - Installing Vinyl Siding Standoff (Combustible Exterior Wall)
Interior Wall
Surface
Interior Wall Firestop (Combustible Exterior Wall Only)
| Horizontal | |
| Vent Pipe | |
Vent Cap | Screw | |
(Horizontal | ||
| ||
Termination) |
|
Figure 28 - Connecting Vent Cap with Horizontal Vent Pipe
For..com