VENTING INSTALLATION
Installation Planning (Cont.) Installation for Horizontal Termination
13
VENTING INSTALLATION
Continued
Installing Vent System in a Chase
A chase is a vertical
NOTICE: Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must fol- low all local building codes.
Note: When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Minimum air space clearance between vent pipes and combustible materials and/or insulation is 1".
INSTALLATION FOR HORIZONTAL TERMINATION
CAUTION: Horizontally terminated venting con- figurations require one foot of vertical rise from the 45° elbow before any horizontal run can be made. Failure to meet venting requirements may cause performance problems and possible damage to the fireplace.
1.Determine the route your horizontal venting will take. Note: The location of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be blocked or obstructed.
WARNING: Do not recess vent terminal into a wall or siding.
Snorkel terminations are available for terminations requiring a vertical rise on the exterior of the building (see Figures 22 and 23). Snorkel kit
2.Vent pipes and fittings have special
Snorkel |
12" Minimum |
(30.5cm) |
Figure 22 - Snorkel Termination
Snorkel
12" Minimum
(30.5cm)
Adequate drainage
Figure 23 - Snorkel Termination with Drainage Pipe
Female
Locking Lugs
Male
Slots
Vent Pipe
Figure 24 - Vent Pipe Connections
For morevisit www..com