Faber FEELING, MISTY Instructions for Installation, Example of how terminal position is measured

Page 10

UK/IRL

Example of how terminal position is measured

UK/IRL

4. INSTRUCTIONS FOR INSTALLATION

4.1Gas connection

1.Installation pipes should be in accordance with BS 6891. Pipe work from the meter to the appliance must be of adequate size.

2.The complete installation including the meter must be tested for soundness and purged as described in the above code.

3.A means of isolation must be provide in the supply to facilitate servicing.

4.The connection should be made in 8 mm copper or similar semi flexible tube. (max 1 meter). Ensure that the gas pipe does not interfere with the removal or replacement of the burner tray of the controls.

5.The gas connection is nut and olive suitable for 8 mm pipe.

fig. 4

3.2.2 Using an existing chimney as air inlet

You can connect the appliance onto an existing chimney. The existing chimney then functions as air supply, where a flexible stainless steel liner (to BS715) of 100 mm performs the flue function.

Requirements:

- Any existing chimney used as an air supply must only service this

appliance.

- A chimney that has previously been used for solid fuel must be swept

A & B = Behind surround - Sleeve pipe through surround C = Through wall - Pipe must be sleeved and sealed to fire

C

outer wall cavity

inner wall

A

gas supply routes when fire is fitted in a deep surround

B

surround

marble

fig. 5

before use.

- The existing chimney needs to be airtight.

- The existing chimney needs to have an opening of

min. 150 x 150 mm.

- The chimney needs to be intact and well looked after.

- Use the adjustable roof-mounted-terminal especially made for this,

and the chimney connection set.

- The minimum distance between two terminals should be at least

450 mm.

4.2Preparing the appliances Widescreen and Whisper

1.Open the ashtray door by pushing on the right side for the Silence/Feeling and on the left side for the Whisper. Remove the frame by loosening the screws A behind the door (see fig. 5). Lift and pull forward when you take it away.

16

 

 

 

17

 

 

Image 10
Contents Silence Feeling Whisper Spectra Nova Cadra Nova Misty Contents UK/IRLIntroduction General safetyPlease leave these instructions with the user Installation Requirements Builders opening and surroundFeeling Silence Whisper Cadra Misty NovaFlue requirements Flue restrictorTable Whisper and Spectra Nova with interior MV100 Table Silence and Feeling with interior WidescreenNumber is size in mm Misty with roundscreen Table Cadra Nova with interior MV150Flue requirements continuing Terminal position Flue terminal positions Terminal positionExample of how terminal position is measured Instructions for InstallationUsing an existing chimney as air inlet Gas connectionCCC Preparing the appliances Widescreen and Whisper continuingPreparing the appliance Misty Preparing the appliances Spectra Nova/Cadra Nova Preparing the appliances Spectra Nova/Cadra Nova continuingFitting the firebox Fitting the firebox continuingPlacing the log set Installation of the FlueConnections with use of concentric duct material Connection onto an existing chimney Connection onto an existing chimney continuingInstallation remote control Remote control if applicableSetting the right transmission code Functional burner check Commissioning functional checksCheck pilot ignition Functional balanced flue checkServicing Handing OverFinal check and customer briefing Burner tray assembly Cleaning the glassCleaning the combustion chamber and burner Pilot/thermocouple assemblyCombustion test Gas control blockCompany PartMV100 Whisper and Spectra Nova User Guide Safety Instructions for the User General safety instructionsKnob a Controlling the ApplianceLighting the fire Knob BRemote control version When the pilot extinguishesTo extinguish Remote control Changing the batteriesCleaning and Service Instructions