UK/IRL
Example of how terminal position is measured
UK/IRL
4. INSTRUCTIONS FOR INSTALLATION
4.1Gas connection
1.Installation pipes should be in accordance with BS 6891. Pipe work from the meter to the appliance must be of adequate size.
2.The complete installation including the meter must be tested for soundness and purged as described in the above code.
3.A means of isolation must be provide in the supply to facilitate servicing.
4.The connection should be made in 8 mm copper or similar semi flexible tube. (max 1 meter). Ensure that the gas pipe does not interfere with the removal or replacement of the burner tray of the controls.
5.The gas connection is nut and olive suitable for 8 mm pipe.
fig. 4
3.2.2 Using an existing chimney as air inlet
You can connect the appliance onto an existing chimney. The existing chimney then functions as air supply, where a flexible stainless steel liner (to BS715) of 100 mm performs the flue function.
Requirements:
- Any existing chimney used as an air supply must only service this |
appliance. |
- A chimney that has previously been used for solid fuel must be swept |
A & B = Behind surround - Sleeve pipe through surround C = Through wall - Pipe must be sleeved and sealed to fire
C
outer wall cavity
inner wall
A
gas supply routes when fire is fitted in a deep surround
B
surround
marble
fig. 5
before use. |
- The existing chimney needs to be airtight. |
- The existing chimney needs to have an opening of |
min. 150 x 150 mm. |
- The chimney needs to be intact and well looked after. |
- Use the adjustable |
and the chimney connection set. |
- The minimum distance between two terminals should be at least |
450 mm. |
4.2Preparing the appliances Widescreen and Whisper
1.Open the ashtray door by pushing on the right side for the Silence/Feeling and on the left side for the Whisper. Remove the frame by loosening the screws A behind the door (see fig. 5). Lift and pull forward when you take it away.
16 |
|
|
| 17 |
|
|