| 8.1.7 Combustion test |
8.1.6 Gas control block | A BS7967 combustion analysis check should be carried out using an |
| analyser to BS7927 positioned in the flue outlet. |
| A Ratio of CO/CO2 should be less than 0.01 within 30 minutes. |
| (100ppm CO per 1% CO2). |
| A reading of CO in the room centre should give a rise of less than |
| 9ppm over ambient, peak reading. |
BA
D CC
A Governor | fig. 26 |